White Rodgers 1F80-0224 specifications Troubleshooting, Reset Operation

Models: 1F80-0224

1 12
Download 12 pages 13.75 Kb
Page 9
Image 9
TROUBLESHOOTING

TROUBLESHOOTING

Reset Operation

If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, reset the thermostat

by pressing the Reset Operation , Manual background and TIME buttons simultaneously.

If the thermostat has power, has been reset and still does not function correctly contact your heating/cooling service person or place of purchase.

Symptom

Possible Cause

Corrective Action

 

 

 

No Heat/No Cool/No Fan

1. Blown fuse or tripped circuit breaker.

Replace fuse or reset breaker.

(common problems)

2. Furnace power switch to OFF.

Turn switch to ON.

 

3. Furnace blower compartment door or

Replace door panel in proper position to engage safety

 

panel loose or not properly installed.

interlock or door switch.

 

 

 

No Heat

1. System Switch not set to Heat.

Set System Switch to Heat and raise setpoint above room

 

 

temperature.

 

2. Loose connection to thermostat or

Verify thermostat and system wires are securely attached.

 

system

Diagnostic: Set System Switch to Heat and raise the

 

3. Heating System requires service or

setpoint above room temperature. Within a five minutes

 

thermostat requires replacement.

the thermostat should make a soft slick sound. This sound

 

 

usually indicates the thermostat is operating properly. If

 

 

the thermostat does not click, try the reset operation listed

 

 

above. If the thermostat does not click after being reset

 

 

contact your heating and cooling service person or place

 

 

of purchase for a replacement. If the thermostat clicks,

 

 

contact the furnace manufacturer or a service person to

 

 

verify the heating system is operating correctly.

 

 

 

No Cool

1. System Switch not set to Cool.

Set System Switch to Cool and lower setpoint below room

 

 

temperature.

 

2. Loose connection to thermostat or

Verify thermostat and system wires are securely attached.

 

system.

Same procedures as diagnostic for No Heat condition

 

3. Cooling System requires service or

except set the thermostat to Cool and lower the setpoint

 

thermostat requires replacement

below the room temperature. There may be up to a five

 

 

minute delay before the thermostat clicks in Cooling if the

 

 

compressor lock-out option is selected in the configuration

 

 

menu (Item 6).

 

 

 

Heat, Cool or Fan Runs

1. Possible short in wiring.

Check each wire connection to verify they are not shorted

Constantly

2. Possible short in thermostat.

or touching together. No bare wire should stick out from

 

3. Possible short in Heat/Cool/Fan

under terminal screws. Try resetting the thermostat as

 

system.

described below. If the condition persists, the manufacturer

 

4. Fan Switch set to Fan On.

of your system or service person can instruct you on how

 

 

to test the Heat/Cool/ system for correct operation. If the

 

 

system operates correctly, replace the thermostat.

 

 

 

Furnace Cycles Too Fast or

1. The location of the thermostat and/or

Item 3 (CR Heat) or 4 (CR Cool) in the Configuration

Too Slow

the size of the Heating or Cooling

Menu is the adjustment that controls the cycle rate. If an

Cooling Cycles Too Fast

System may be influencing the cycle

acceptable cycle rate is not achieved using the FA (Fast)

or Too Slow

rate.

or SL (Slow) adjustment contact a local service person for

(narrow or wide

 

additional suggestions.

temperature swing)

 

 

 

 

 

Thermostat Setting and

1. Thermostat thermometer setting

The thermometer can be adjusted +/- degrees as listed in

Thermometer Disagree

requires adjustment.

item 8 of the Configuration Menu. No other adjustment is

 

 

possible.

 

 

 

Clock Loses or Gains

1. Loss of power to thermostat.

The thermostat will maintain its program in memory even

Time

 

with no power but the clock time will be incorrect when

 

 

power is restored. See No Heat/No Cool /No Fan (common

 

 

problems) above for items to check in the system.

 

 

 

Heat or Cool Starts Early

1. EMR activated.

See Configuration Menu (Item 3)

 

 

 

Thermostat Does Not

1. AM or PM set incorrectly in program.

Check current clock and program settings including the AM

Follow Program

2. AM or PM set incorrectly on the

or PM designations for each time period. If a voltage spike

 

clock.

or static discharge occurs use the Reset Operation listed

 

3. Voltage spike or static discharge.

above.

 

4. See “Heat or Cool Starts Early”

 

 

above.

 

 

 

 

Blank Display and/or

1. Voltage Spike or Static Discharge.

If a voltage spike or static discharge occurs use the Reset

Keypad Not Responding

 

Operation listed above.

 

 

 

9

Page 9
Image 9
White Rodgers 1F80-0224 specifications Troubleshooting, Reset Operation