at the same time again.

(long cycles), you may want to adjust the anticipation setting.

!CAUTION

A cooling anticipation setting of less than 10 may cause decreased compressor life.

SET

To adjust heat anticipation, press CLOCK

and DAYSET at the same time. The display will

show HEAT 5 (this is the factory prepro- grammed heating anticipation setting). You may select any anticipation setting from 2 to 40 (note that for hydronic systems, a minimum anticipation setting of 15 is recommended). Whenever adjusting an- ticipation, increase or decrease the dis- played number by only one or two digits, then let the system run for a while to see if

the adjustment is sufficient. If the heat

cycles are too short, press TIMEFWD to increase the cycle time. If the heat cycles are too

TIME

long, press BACK to decrease the cycle

time. To set cooling anticipation, press

SET

and

SET

at the same time again.

CLOCK

DAY

The display will show COOL 14 (factory preprogrammed cooling anticipation). You may select any anticipation setting from 4 to

40. Use the

TIME

and

TIME

buttons to

FWD

BACK

adjust anticipation. Press

RUN

to return

PRGM

to your program.

LOW BATTERY INDICATOR — The word BATTERY will flash on the display if the "AA" alkaline batteries are low and should