White Rodgers 241-2, 1609 Wiring, Setting The Dial, Controls with one circuit two terminals

Models: 1609 241-2

1 6
Download 6 pages 60.2 Kb
Page 2
Image 2
WIRING

WIRING

All wiring must conform to local and national electrical codes and ordinances.

Connect in accordance with wiring diagrams provided by the equipment manufacturer. If none are provided, the following represents a typical installation.

Controls with one circuit (two terminals)

Low

temperature

limit

Temperature

High side

pressure control

control

(if used)

 

L1

To

Line

Compressor

L2 Note: Make L1 “HOT” on

Motor

 

120V installation

 

Circuit showing temperature control con- trolling compressor directly.

Note: Make L1 “HOT” on

L1

120V installation

 

 

 

 

 

Line

Low temperature

Temperature

limit

 

control

 

 

L2

 

 

 

 

High side

Suction

Solenoid

 

pressure

pressure

 

refrigerant

 

control

control

 

valve

 

 

 

Motor starter

To

Compressor

Motor

Circuit showing temperature control to open and close refrigerant valve. Suction pressure control starts and stops compressor through motor starter.

Controls with two circuits (three terminals)

BLUE RED

WHITE

The blue terminal is common. The table below shows the maximum load allowed between terminals.

 

MAXIMUM ALLOWABLE RATING

LOAD CONDITIONS

Full Load

Locked Rotor

 

120V

240V

120V

240V

 

 

 

 

 

Load between Blue and Red

7.4A

3.7A

44.5A

22.2A

terminals must not exceed:

 

 

 

 

Load between Blue and White

7.4A

3.7A

44.5A

22.2A

terminals must not exceed:

 

 

 

 

This diagram shows a typical two-circuit applica- tion. Several zones receive refrigeration from the same compressor, but each zone requires its own solenoid refrigerant valve and temperature control.

Note: Make L1 “HOT” on

B

 

R

 

120V installation

 

 

 

W

 

 

 

 

L1

 

 

 

Line

 

 

 

 

 

 

 

L2

 

 

 

To

 

 

 

Compressor

 

 

 

 

Motor

 

 

 

 

 

 

 

 

BR W

Valve

No. 1

To

Controls with one circuit (two terminals) Additional

Units

Valve

No. 2

SETTING THE DIAL

The movable indicator (D) points to the temperature at which the compressor starts. The fixed indicator (B) points to the tempera- ture at which the compressor will stop. The difference between these two indicators is the differential. Follow these instructions to set the dial:

1.Insert a screwdriver in the adjusting slot (A) and turn the dial until the fixed indicator (B) points to the temperature at which the compressor is to stop.

2.Turn the differential adjusting screw (C) until the movable indicator (D) points to the temperature at which the com- pressor is to start.

“B” Fixed indicator (cut-out point)

“C” Differential adjusting screw

Controls with two circuits (three terminals)“D” Movable indicator

(cut-in point)

SETTING THE DIAL “A” Adjusting slot

2

Page 2
Image 2
White Rodgers 241-2, 1609 installation instructions Wiring, Setting The Dial, Controls with one circuit two terminals