![WIRING](/images/new-backgrounds/78779/787793x1.webp)
WIRING
All wiring must conform to local and national electrical codes and ordinances.
Connect in accordance with wiring diagrams provided by the equipment manufacturer. If none are provided, the following represents a typical installation.
Controls with one circuit (two terminals)
Low
temperature
limit
Temperature | High side | |
pressure control | ||
control | ||
(if used) | ||
| ||
L1 | To | |
Line | ||
Compressor | ||
L2 Note: Make L1 “HOT” on | Motor | |
| ||
120V installation |
|
Circuit showing temperature control con- trolling compressor directly.
Note: Make L1 “HOT” on
L1 | 120V installation |
|
|
|
|
| |
Line | Low temperature | Temperature | |
limit |
| control | |
|
| ||
L2 |
|
|
|
| High side | Suction | Solenoid |
| pressure | pressure | |
| refrigerant | ||
| control | control | |
| valve | ||
|
|
|
Motor starter
To
Compressor
Motor
Circuit showing temperature control to open and close refrigerant valve. Suction pressure control starts and stops compressor through motor starter.
Controls with two circuits (three terminals)
BLUE RED
WHITE
The blue terminal is common. The table below shows the maximum load allowed between terminals.
| MAXIMUM ALLOWABLE RATING | ||||
LOAD CONDITIONS | Full Load | Locked Rotor | |||
| 120V | 240V | 120V | 240V | |
|
|
|
|
| |
Load between Blue and Red | 7.4A | 3.7A | 44.5A | 22.2A | |
terminals must not exceed: | |||||
|
|
|
| ||
Load between Blue and White | 7.4A | 3.7A | 44.5A | 22.2A | |
terminals must not exceed: | |||||
|
|
|
|
This diagram shows a typical
Note: Make L1 “HOT” on | B |
| R | |
| ||||
120V installation |
| |||
|
| W | ||
|
|
|
| |
L1 |
|
|
| |
Line |
|
|
| |
|
|
|
| |
L2 |
|
|
| |
To |
|
|
| |
Compressor |
|
|
|
|
Motor |
|
|
|
|
|
|
|
|
BR W
Valve
No. 1
To
Additional
Units
Valve
No. 2
SETTING THE DIAL
The movable indicator (D) points to the temperature at which the compressor starts. The fixed indicator (B) points to the tempera- ture at which the compressor will stop. The difference between these two indicators is the differential. Follow these instructions to set the dial:
1.Insert a screwdriver in the adjusting slot (A) and turn the dial until the fixed indicator (B) points to the temperature at which the compressor is to stop.
2.Turn the differential adjusting screw (C) until the movable indicator (D) points to the temperature at which the com- pressor is to start.
“B” Fixed indicator
“C” Differential adjusting screw
“D” Movable indicator
“A” Adjusting slot
2