241-2 & 1609 Series
WHITE-RODGERS Refrigeration Temperature Controls
INSTALLATION INSTRUCTIONS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
This hydraulic action temperature control is applicable for all types of commercial or industrial refrigeration applications. This control will close contacts on rise in temperature and open them on a fall in temperature.
The
DESCRIPTION
This
!WARNING
FIRE/SHOCK HAZARD
Disconnect power to system at main fuse or circuit breaker box before installation.
Do not use on circuits exceeding speci- fied voltages.
CAUTION
FREEZE HAZARD
Install low temperature limit device.
System malfunction may cause freeze damage.
PRECAUTIONS
THIS CONTROL MUST BE INSTALLED BY A QUALIFIED INSTALLER.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.
This control has been accurately calibrated at the factory. Any attempt to
If in doubt about whether your wiring is millivolt, low or line voltage, have it inspected by a qualified heating and air condi- tioning contractor or a licensed electrician.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Following installation or replacement, follow appliance manu- facturers’ recommended installation/service instructions to in- sure proper operation.
The switch mechanism of this control may be mounted in any location, provided that the temperature and humidity of the air in which it is located do not cause a condensation on the switch parts.
The sensitive element, or “bulb”, should be located in the average temperature of the controlled area.
Capillary tubing should be led over a path that protects it from damage from blows, cuts, etc., and should be installed without kinking or twisting. The tubing should be attached to some surface at frequent intervals along its length, and should not
INSTALLATION
hang loosely. Excess tubing should be coiled and secured at a convenient protected location close to the switch mechanism.
The bulb should be handled with reasonable care, as a dent or sharp bend may change the calibration and cause the control to cycle at a temperature different from the dial setting.
| |
EMERSON ELECTRIC CO. |
|
9797 REAVIS RD., ST. LOUIS, MO. |
|
(314) | Printed in U.S.A. |
| |
9999 HWY. 48, MARKHAM, ONT. L3P 3J3 |
|
(905) |
|
PART NO. 37-1104F
Replaces