White Rodgers OPERATION OPTION SWITCHES 50A55-474only, Heat Mode, OPTION JUMPER 50A55-571only

Models: 50A55-474 50A55-571

1 8
Download 8 pages 2.48 Kb
Page 6
Image 6
OPERATION

OPERATION

OPTION SWITCHES

(50A55-474 only)

The option switches on the 50A55-474 control are used to determine the length of the cool delay-to-fan-off and heat delay-to-fan-off periods. The following tables show the time periods that will result from the various switch posi- tions.

OPTION SWITCH POSITIONS

COOL delay-

Set switch

to-fan-off:

 

#1

0 sec.

 

On

80 sec.

 

Off

 

 

 

 

COOL delay-

Set switch

to-fan-off:

#2

#3

60 sec.

On

Off

100 sec.

On

On

140 sec.

Off

On

180 sec.

Off

Off

OPTION JUMPER (50A55-571 only)

The option jumper on the 50A55-571 control is used to determine the length of the cool delay-to-fan-off period. The following table shows the time periods that will result from the various jumper conditions.

OPTION JUMPER CONDITION

COOL delay-

Jumper

to-fan-off:

Condition

 

 

0 sec.

Installed

80 sec.

Clipped (open)

 

 

HEAT MODE

In a typical system, a call for heat is initiated by closing the thermostat contacts. This starts the 50A55 control’s heat- ing sequence. The inducer blower and optional humidifier are energized and the ignitor is powered within one second.

These controls have an adaptive algorithm that adjusts the duration of the ignitor warm-up for the purpose of extending ignitor life. Upon initial application of power, the warm-up time is 17 seconds. The ignitor on-time will then be increased or decreased depending on whether or not flame is achieved. The warm-up time is limited to a maximum of 21 seconds. During the first 64 warm-up periods following power-up, the warm-up time may not be less than 17 seconds.

Upon a call for heat, if the warm-up time has not been locked, it will be decreased by one second. This reduction of the ignitor on-time will continue until flame fails to be achieved (resulting in a retry).

In the event of a retry, the warm-up time will be increased by two seconds and locked at that duration. Once the warm-up time is locked, it remains fixed until another call for heat results in a retry, in which case, the warm-up time is again increased by two seconds and remains locked.

In the event of two successive retry attempts, the warm- up time will be unlocked and set to 21 seconds. If flame is then achieved, the warm-up time will begin adapting again with the next call for heat. If, however, this third attempt fails to achieve flame, the control will go into system lockout.

At the end of the ignitor warm-up time, both valves in the 36E manifold gas valve are opened. Flame must be detected within 4 seconds. If flame is detected, the delay- to-fan-on period begins. After the delay-to-fan-on period ends, the circulator fan is energized at heat speed. If there is an optional electronic air cleaner on the system, the electronic air cleaner is also energized. When the thermo- stat is satisfied, the gas valve is de-energized. After proof of flame loss, the delay-to-fan-off period begins and the inducer blower remains energized to purge the system for 5 seconds. When the purge is complete, the inducer blower and humidifier are de-energized. After the delay- to-fan-off period ends, the circulator fan and electronic air cleaner are de-energized. If flame is not detected, both valves are de-energized, the ignitor is turned off, and the 50A55 control goes into the “retry” sequence.

The “retry” sequence provides a 60-second wait following an unsuccessful ignition attempt (flame not detected). After this wait, the ignition sequence is restarted with 2 seconds of ignitor warm-up time. If this ignition attempt is unsuccessful, one more retry will be made before the control goes into system lockout.

If flame is detected, then lost, the 50A55 control will repeat the initial ignition sequence for a total of ten “recycles”. After ten unsuccessful “recycle” attempts, the control will go into system lockout.

If flame is established for more than 10 seconds after ignition, the 50A55 controller will clear the ignition attempt (or retry) counter. If flame is lost after 10 seconds, it will restart the ignition sequence. This can occur a maximum of 11 times before system lockout.

During burner operation, a momentary loss of power of 50 milliseconds or longer will de-energize the main gas valve. When power is restored, the gas valve will remain de-energized and a restart of the ignition sequence will begin immediately.

A momentary loss of gas supply, flame blowout, or a shorted or open condition in the flame probe circuit will be sensed within 2.0 seconds. The gas valve will de-ener-

6

Page 6
Image 6
White Rodgers installation instructions OPERATION OPTION SWITCHES 50A55-474only, Heat Mode, OPTION JUMPER 50A55-571only