White Rodgers 50A55-474 Specifications, Max. Input Current @ 25 VAC 0.45 amp, Humidity Range

Models: 50A55-474 50A55-571

1 8
Download 8 pages 2.48 Kb
Page 2
Image 2
SPECIFICATIONS

SPECIFICATIONS

ELECTRICAL RATINGS [@ 77°F (25°C)]: Input Voltage: 25 VAC 50/60 Hz

Max. Input Current @ 25 VAC: 0.45 amp

Relay Load Ratings:

Valve Relay: 1.5 amp @ 25 VAC 50/60 Hz 0.6 pf

Ignitor Relay: 6.0 amp @ 120 VAC 50/60 Hz (resistive)

Flame Current Requirements:

Minimum current to insure flame detection: 1 μa DC*

Maximum current for non-detection: 0.1 μa DC*

Maximum allowable leakage resistance: 100 M ohms

*Measured with a DC microammeter in the flame probe lead

OPERATING TEMPERATURE RANGE:

-40°to 175°F (-40°to 80°C)

HUMIDITY RANGE:

5% to 93% relative humidity (non-condensing)

MOUNTING:

Surface mount multipoise

 

Timing Specs: (@ 60 Hz**)

 

 

maximum

Flame Establishing Time:

0.8 sec

Flame Failure Response Time:

2.0 sec

**At 50 Hz, all timing specifications should be increased by 20%.

Gases Approved: Natural, Manufactured, Mixed, Liquified Petroleum, and LP Gas Air Mixtures are all approved for use.

TIMING SPECIFICATIONS

(All times are in seconds, unless noted otherwise)

 

50A55-474

50A55-571

 

 

 

PRE-PURGE

0

0

 

 

 

TRIAL FOR IGNITION

4

4

PERIOD

 

 

 

 

 

IGNITION ACTIVATION

1

1

PERIOD

 

 

 

 

 

RETRIES

2 times

2 times

 

 

 

VALVE SEQUENCE

12

12

PERIOD

 

 

 

 

 

INTERPURGE

60

60

 

 

 

POST-PURGE

5

5

 

 

 

LOCKOUT TIME

300

300

 

 

 

DELAY TO HEAT ON

45

45

 

 

 

DELAY TO HEAT OFF

60/100/

100

140/180*

 

 

 

 

 

DELAY TO COOL ON

2

2

 

 

 

DELAY TO COOL OFF

0/80*

0/80

MINIMUM IGNITOR

11

11

WARM-UP

 

 

 

 

 

MAXIMUM IGNITOR

21

21

WARM-UP

 

 

 

 

 

INITIAL IGNITOR

17

17

WARM-UP (1st 64

 

 

attempts)

 

 

 

 

 

HUMIDIFIER

YES

NO

 

 

 

ELECTRONIC AIR

YES

NO

CLEANER

 

 

 

 

 

*These times will vary depending on option switch position. The control is factory-set at 0 sec. delay to cool off and 100 sec. delay to heat off. See OPERATION section for further information.

This time will vary depending on the condition of the jumper. With the jumper installed, the delay-to- cool-off is set at 0 seconds. To obtain an 80- second delay-to-cool-off, clip the jumper wire and separate the jumper legs.

2

Page 2
Image 2
White Rodgers 50A55-474 Specifications, Max. Input Current @ 25 VAC 0.45 amp, Flame Current Requirements, Humidity Range