WHITE-RODGERS
TYPE 668-451
Intermittent Ignition* – Non Recycling
OIL BURNER CONTROL
With Series 956 Flame Detector (For use with 40VA Cooling Load)
INSTALLATION INSTRUCTIONS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
DESCRIPTION
This Type 668 Oil Burner Control provides safe operation of oil burners on heating plants where ignition during the entire burner cycle is desired. It is capable of powering external cooling loads up to 40 VA. A
* Formerly called constant ignition.
PRECAUTIONS
If in doubt about whether your wiring is millivolt, line, or low voltage, have it inspected by a qualified heating and air conditioning contractor, electrician, or someone familiar with basic electricity and wiring.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument, and should be handled carefully. Rough handling or distorting compo- nents could cause the control to malfunction.
!CAUTION
To prevent electrical shock and/or equipment damage, disconnect electric power to system, at main fuse or circuit breaker box, until installation is complete.
!WARNING
Do not use on circuits exceeding specified volt- ages. Higher voltages will damage control and could cause shock or fire hazard.
|
|
| SPECIFICATIONS |
|
|
| |
ELECTRICAL DATA | Room Thermostat: | ||
Input voltage: 120 VAC, 60Hz. | Set adjustable heat anticipator at 0.4 Amps. | ||
Maximum Load Current: | Low Voltage Rating (Terminals R&C): | ||
Oil Burner Motor (Orange Wire): | Maximum cooling load of 40VA @ 24v. 60 Hz. | ||
10 Amps F.L. 60 Amps L.R. | Continuous duty. W & C cycled through thermostat. | ||
Ignition Transformer: | Safety Timing: 45 seconds | ||
360VA (3.0 Amps) |
|
|
|
Relay Voltage: 24 Volts AC, 60Hz. |
|
|
|
|
| INSTALLATION AND WIRING | |
|
|
The proper Location and Mounting of the primary oil burner control panel on the burner and the flame detector with respect to the oil flame shall be determined by the furnace, boiler, or burner manufacturer.
If this control, supplied as part of a furnace, boiler or burner, is wired to the equipment or if the manufacturer of such equipment provides instructions for wiring this
control, then follow his recommendations. If no special wiring instructions are given, then follow the electrical connections shown.
For more complicated systems, especially for hot water heating, consult the manufacturer of the heating plant for full details of the desired sequence of control operation.
| |