TW-2000 Parallel Plumbing Wiring Explanation TW-2
A)The wood system neutral is connected to the oil boiler neutral.
B)The line power for the wood boiler must come from the same power disconnect switch as the oil boiler.
C) | Single Aquastat (White Rodgers | Metal 160°F |
| This operates the circulation pump to circulate hot water between the two | |
| boilers when the wood boiler is in operation. |
|
| The N/O contacts on the single aquastat White Rodgers | |
| should be connected to the secondary circulation pump between the wood | |
| and oil boilers (as shown in plumbing diagram | |
D) | Double Aquastat (White Rodgers | High Limit Left |
This is the wood high limit. If the water temperature in the wood boiler reaches 200°F the wood boiler air damper is closed and the safety by- pass zone valve is opened. The end switch on the safety
| Metal 200°F |
|
| Brass 190°F |
|
E) | Double Aquastat (White Rodgers | Low Limit Right |
This is used to maintain the wood boiler at the set temperature by opening and closing the wood boiler air damper.
Metal 170°F
Brass 150°F
F)The triple aquastat on the oil boiler controls the oil boiler in the normal manner.
The safety
The supply from the wood boiler should only be connected to the plumbing system after the primary circulator, and in conjunction with a flow check valve on the wood supply line. This will not allow hot water to flow through the wood boiler when the secondary circulation pump is not in operation (no fire in wood boiler).
TW2000 | 21 | 10/6/05 |