TW2000
2.6.1Free Standing
Free Standing installation requires additional components, which are not included in the TW2000 boiler kit. Check wiring diagrams TW – 5 and TW – 6 for additional required components.
In the freestanding, or
function aquastat and an additional transformer must be purchased separately and installed in place of the dual aquastat supplied with the boiler. An alternative
2.6.2Parallel
In the PARALLEL SYSTEM the water is circulating between the two boilers by means of an auxiliary circulator. In this system the flow of water from the existing boiler (supply) is teed and piped to the return of the Kerr TW2000 boiler. The return pipe to the existing boiler is teed, and piped to the outlet nipple of the Kerr TW2000 boiler. Therefore the TW2000 is maintaining heat in both boilers. If the TW2000 is not being utilized the system warm return water is not keeping the wood boiler warm.
In the parallel system an auxiliary circulating pump keeps the temperature even between the two boilers. It is controlled by a separate aquastat on the Kerr TW2000 boiler. When the water in the Kerr TW2000 boiler is hotter than the set point of the single aquastat, the circulator comes on and circulates the hot water between the two units.
This system allows the domestic hot water coil in the existing boiler to supply the household with hot water without an additional coil in the Kerr TW2000 boiler.
TW2000 | 16 | 10/6/05 |