PROBLEM: Measured inverter output is too low.

Possible cause

Remedy

Standard "average reading" AC voltmeter used to measure output voltage, resulting in an apparent reading 5 to 15 V too low.

Inverter’s "modified sine wave" output requires "true RMS" voltmeter for accurate measurements.

Battery voltage is too low.Recharge battery.

PROBLEM: Alarm is sounding.

 

Possible cause

Remedy

Low voltage shutdown or thermal shutdown has occurred.

Shorten cables or use heavier cables. Recharge the battery. Allow the unit to cool. Improve air circulation around the unit. Move the unit to a cooler environment. Reduce the load if continuous operation is required.