The AC load will not operate. No inverter lights are on.

Possible Cause

Suggested Remedy

Battery is defective.

The inverter has been connected with reverse DC input polarity.

Loose cable connections.

Check battery and replace if required.

Check connection to battery. The inverter has likely been damaged and needs to be repaired. Have the unit repaired (not covered under warranty).

Check cables and connections. Tighten as required.

Inverter will run some small loads, but not larger ones.

Possible Cause

Suggested Remedy

 

 

Voltage drop across DC cables.

Shorten cables or use heavier

 

cables.