System Configuration
2–14 976-0043-01-02
and inverter amperage per NEC/CEC guidelines. It is recommended that
the cable has battery acid resistant insulation and is rated for 90°C
(32 °F) or better.
Be sure to check with any local regulatory agencies for additional
requirements.
Battery cable lugs Battery cables must have crimped copper compression lugs or crimped
and soldered copper compression lugs. Soldered connections alone are
not acceptable.
High quality battery cables are available from Xantrex i n an assor tment of
lengths from 1½ to 10 feet in #2/0 AWG and from 1½ to 15 feet in
#4/0 AWG sizes. These cables are color-coded with pressure crimped,
sealed ring terminals.
Overcurrent
protection For safety and compliance with regulations, battery overcurrent
protection is required. Fuses and disconnects must be sized to protect the
wiring in the system and are required to open before the wire reaches its
maximum current carrying capability.
Xantrex DC175 and
DC250 The NEC/CEC requires both overcurrent protection and a disconnect
switch for residential and commercial electrical syste ms. T hes e item s are
not supplied as part of the inverter. However, Xantrex offers a DC circui t
breaker disconnect module specifically designed for use with Xantrex
Table 2-2
Recommendced Battery Cable Size Versus Length
Inverter
Model
Maximum
Continuous
DC ampsa
a. “Maximum Continuous DC amps”, as shown in this table , is bas ed o n low
battery voltage with an efficiency of 85%.
NEC
ampsb
b. “NEC amps”, as shown in this table, is based on low battery voltage, and
efficiency of 85%, and a 125% NEC derating.
Up to 5 Feet
One-way
Up to 10 Feet
One-way
Up to 15 Feet
One-way
2524 134 167 #2/0 AWG
(67.4 mm2)
#4/0 AWG
(107 mm2)
Not
Recommended
2548 67 84 #2/ 0 AWG
(67.4 mm2)
#4/0 AWG
(107 mm2)
#4/0 AWG x 2
(107 mm2 x 2)
4024 214 267 #4/0 AWG
(107 mm2)
#4/0 AWG x 2
(107 mm2 x 2)
Not
Recommended
4048 107 134 #2/0 AWG
(67.4 mm2)
#4/0 AWG
(107 mm2)
Not
Recommended
5548 147 184 #4/0 AWG
(107 mm2)
#4/0 AWG x 2
(107 mm2 x 2)
Not
Recommended