Installation
2–20 975-0402-01-01
This guide for use by qualified installers only
Installing AC Wiring
Before connecting AC wiring, make sure the AC source
circuit is protected by a breaker switch of the correct size and
type, to comply with the electrical code for your location and
application. The current rating of the input breaker should not
be larger than 20A for 120 Vac applications and 16A for
230 Vac applications, but may be required to be lower
depending on the wire size used.
1. Plan the route that the AC supply wiring will follow from
the source (usually an AC distribution panel) to the
Truecharge™ 2 Battery Charger.
2. Measure and cut the required length of three-conductor
(L, N, GND) cable allowing some extra length for
connections and providing some slack.
3. Route the AC supply wiring from the charger (in its
mounted position) to the source.
4. Unscrew the wiring compartment cover from the left rear
of the Truecharge™ 2 Battery Charger to expose the AC
wiring access hole and charger’s AC pigtail leads.
WARNING: Shock hazard
Disconnect the AC source by turning off the breaker feeding the
circuit, unplugging from shore power and disconnecting any other
power sources (such as a generator).
wiring compartment
cover
AC wiring access hole AC pigtail leads