AE01087

 

 

 

Overload indicator light (Red)

 

 

 

The overload indicator light 1 comes on when an over-

1

 

 

load of a connected electrical device is detected, the

 

 

inverter control unit overheats, or the AC output voltage

 

 

 

 

 

 

rises. Then, the AC protector will trip, stopping power

 

 

 

generation in order to protect the generator and any

 

7DK-021

 

 

connected electric devices. The AC pilot light (Green)

 

 

 

 

 

 

 

 

 

will go off and the overload indicator light (Red) will stay

on, but the engine will not stop running.

When the overload indicator light comes on and power generation stops, proceed as follows:

1.Turn off any connected electric devices and stop the engine.

2.Reduce the total wattage of connected electric devices within the rated output.

3.Check for blockages in the cooling air inlet and around the control unit. If any blockages are found, remove.

4.After checking, restart the engine.

TIP

The overload indicator light may come on for a few seconds at first when using electric devices that require a large starting current, such as a compressor or a submergible pump. However, this is not a malfunction.

Fuel tank cap

Remove the fuel tank cap by turning it counterclock- wise.

7DK-022

– 9 –