TABLE 9: RP 048 @ 1600 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS

EWT

GPM

WPD

 

 

Cooling

 

 

(ºF)

(PSI)

EAT

TC

SC

KW

THR

 

(db/wb)

(MBH)

(MBH)

(MBH)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75/62

51.2

39.6

2.80

60.7

 

7.5

3.9

80/67

56.9

39.5

2.88

66.7

50

 

 

85/72

59.9

38.1

3.04

70.2

 

 

75/62

52.2

40.1

2.70

61.4

 

 

 

 

 

 

 

 

 

 

 

 

12.0

9.6

80/67

58.0

40.0

2.77

67.4

 

 

 

 

 

 

 

 

 

 

 

85/72

62.1

38.9

2.84

71.7

 

 

 

75/62

48.4

38.5

3.08

58.9

 

7.5

3.7

80/67

53.7

38.3

3.17

64.5

60

 

 

85/72

56.7

37.1

3.34

68.1

 

 

75/62

49.8

39.1

2.94

59.8

 

 

 

 

 

 

 

 

 

 

 

 

12.0

9.2

80/67

55.4

38.9

3.03

65.7

 

 

 

 

 

 

 

 

 

 

 

85/72

59.3

37.9

3.01

69.8

 

 

 

75/62

46.2

37.5

3.31

57.4

 

7.5

3.5

80/67

51.3

37.4

3.42

62.9

70

 

 

85/72

54.2

36.2

3.59

66.4

 

 

75/62

47.3

38.0

3.19

58.1

 

 

 

 

 

 

 

 

 

 

 

 

12.0

8.7

80/67

52.8

37.9

3.27

63.9

 

 

 

 

 

 

 

 

 

 

 

85/72

56.1

36.8

3.40

67.7

 

 

 

75/62

42.9

36.2

3.64

55.3

 

7.5

3.3

80/67

47.2

35.8

3.87

60.4

60

 

 

85/72

49.3

34.6

4.27

63.8

 

 

75/62

43.5

36.4

3.58

55.7

 

 

 

 

 

 

 

 

 

 

 

 

12.0

8.3

80/67

48.6

36.4

3.62

60.9

 

 

 

 

 

 

 

 

 

 

 

85/72

51.6

35.3

3.84

64.7

 

 

 

75/62

38.7

34.4

4.03

52.4

 

7.5

3.2

80/67

43.2

34.4

4.01

57.1

100

 

 

85/72

45.1

33.2

4.45

60.2

 

 

75/62

39.3

34.7

3.98

52.8

 

 

 

 

 

 

 

 

 

 

 

 

12.0

7.9

80/67

44.1

34.7

4.02

57.8

 

 

 

 

 

 

 

 

 

 

 

85/72

47.0

33.8

4.27

61.5

EWT(ºF)

GPM

 

Heating

 

EAT

HC

KW

H Absrp.

 

 

(db)

(MBH)

(MBH)

 

 

 

 

 

60

44.3

3.11

33.7

 

7.5

70

43.7

3.31

32.4

50

 

80

43.2

3.50

31.2

 

60

45.3

3.13

34.6

 

 

 

 

 

 

 

 

 

12.0

70

44.6

3.34

33.2

 

 

 

 

 

 

 

 

80

44.1

3.54

32.0

 

 

60

49.7

3.25

38.6

 

7.5

70

48.9

3.47

37.1

60

 

80

48.3

3.68

35.8

 

60

52.5

3.33

41.1

 

 

 

 

 

 

 

 

 

12.0

70

51.6

3.55

39.5

 

 

 

 

 

 

 

 

80

50.9

3.76

38.1

 

 

60

57.4

3.46

45.6

 

7.5

70

56.4

3.69

43.8

70

 

80

55.6

3.91

42.2

 

60

59.9

3.52

47.9

 

 

 

 

 

 

 

 

 

12.0

70

58.8

3.76

46.0

 

 

 

 

 

 

 

 

80

58.0

3.99

44.3

 

 

60

62.8

3.59

50.6

 

7.5

70

61.7

3.83

48.6

80

 

80

60.7

4.06

46.9

 

60

66.1

3.67

53.6

 

 

 

 

 

 

 

 

 

12.0

70

64.9

3.92

51.5

 

 

 

 

 

 

 

 

80

63.8

4.16

49.6

NOTE: All capacity data shown is NET - includes motor power/heat at design CFM and HI fan speed. Tabulated kW values do not include allowance for external pumping power.

TC = TOTAL COOLING CAPACITY

SC = SENSIBLE COOLING CAPACITY

THR = TOTAL HEAT REJECTION

HC = TOTAL HEATING CAPACITY

WPD = WATER PRESSURE DROP

AIR FLOW CORRECTION FACTORS

AIRFLOW

 

 

HEATING

 

 

 

COOLING

 

% OF

 

CFM

HC

Input

Heat

TC

SC

 

Input

THR

Nominal

 

Power

Absrp.

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

1280

0.986

1.058

0.969

0.966

0.893

 

0.992

0.971

90

 

1440

0.993

1.029

0.985

0.983

0.947

 

0.996

0.986

 

 

 

 

 

 

 

 

 

 

 

100

 

1600

1.000

1.000

1.000

1.000

1.000

 

1.000

1.000

110

 

1760

1.007

0.977

1.014

1.011

1.049

 

1.004

1.011

115

 

1840

1.010

0.965

1.021

1.017

1.074

 

1.006

1.016

 

 

 

 

 

 

 

 

 

 

 