TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION

UNIT

AIR

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE-IWG3

 

 

 

 

 

 

FLOW

 

0.20

 

0.30

 

0.40

 

0.50

 

0.60

 

0.70

 

0.80

TONNAGE

 

 

 

 

 

 

 

 

CFM

RPM

 

WATTS

RPM

 

WATTS

RPM

 

WATTS

RPM

 

WATTS

RPM

 

WATTS

RPM

 

WATTS

RPM

 

WATTS

 

 

 

 

 

 

 

 

 

 

3200

1150

 

2325

1182

 

2425

1212

 

2525

-

 

-

-

 

-

-

 

-

-

 

-

 

3000

1100

 

2010

1129

 

2090

1157

 

2150

1185

 

2225

1215

 

2290

1242

 

2360

-

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2800

1045

 

1700

1074

 

1780

1102

 

1850

1131

 

1940

1160

 

2025

1190

 

2075

1217

 

2130

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

61, 2

2600

985

 

1425

1015

 

1475

1045

 

1540

1075

 

1630

1103

 

1715

1135

 

1760

1163

 

1825

2400

930

 

1240

958

 

1300

990

 

1350

1020

 

1400

1051

 

1430

1081

 

1490

1111

 

1600

 

 

 

 

 

 

 

 

 

2200

-

 

-

905

 

1070

933

 

1160

965

 

1210

997

 

1250

1028

 

1285

1060

 

1325

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2000

-

 

-

-

 

-

-

 

-

919

 

1025

950

 

1100

982

 

1130

1014

 

1160

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1800

-

 

-

-

 

-

-

 

-

-

 

-

909

 

925

939

 

1005

968

 

1030

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

AIR

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE-IWG3

 

 

 

 

 

 

FLOW

 

0.90

 

1.00

 

1.10

 

1.20

 

1.30

 

1.40

 

1.50

TONNAGE

 

 

 

 

 

 

 

 

CFM

RPM

 

WATTS

RPM

 

WATTS

RPM

 

WATTS

RPM

 

WATTS

RPM

 

WATTS

RPM

 

WATTS

RPM

 

WATTS

 

 

 

 

 

 

 

 

 

 

3200

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3000

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

 

2800

1245

 

2190

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

61, 2

2600

1193

 

1920

1222

 

1990

1250

 

2060

-

 

-

-

 

-

-

 

-

-

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2400

1142

 

1675

1173

 

1730

1205

 

1800

1234

 

1885

-

 

-

-

 

-

-

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2200

1090

 

1380

1124

 

1450

1155

 

1550

1186

 

1640

1217

 

1710

1249

 

1775

-

 

-

 

2000

1045

 

1175

1077

 

1200

1109

 

1275

1140

 

1360

1170

 

1460

1205

 

1545

1235

 

1600

 

1800

998

 

1050

1028

 

1060

1058

 

1060

1087

 

1075

1118

 

1150

1148

 

1250

1176

 

1360

1.230/460/575 Volts

2.For 208 Volts multiply values by 0.95.

3.Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for resistance values on applications other than gas / electric units with side duct airflows.