York 60, 36 SOUND POWER RATING1, CAPACITY RATINGS - ARI 210/2401, GAS HEAT RATINGS1, YTG-A-0506

Models: 48 60 36

1 44
Download 44 pages 16.54 Kb
Page 7
Image 7

255040-YTG-A-0506

TABLE 1: SOUND POWER RATING1

 

 

ESP

BLOWER

 

 

 

 

SOUND POWER (db 10-12

Watts)

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

Octave Band Centerline Frequency (Hz)

 

SWL

dB(A)

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

@

 

 

IWG

SPEED

KW

63

125

 

250

500

1,000

2,000

 

4,000

8,000

dB(A)

 

 

 

 

10Ft.2

 

 

 

 

 

036

1,200

0.6

LOW

0.60

84

84

 

74

67

69

62

 

57

52

74

41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048

1,600

0.55

HIGH

0.80

85

85

 

75

68

70

63

 

58

53

75

42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

2,000

0.45

HIGH

1.00

86

86

 

76

69

71

64

 

59

54

76

43

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

072

2,200

0.3

HIGH

1.35

87

87

 

77

70

72

65

 

60

55

77

44

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran- tee requiring a dBA value or sound data in any other form than sound power level ratings.

2.At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 210/240)1

MODEL

MBH

EER2

SEER3

D(CE, CG)036

36.0

9.1

10.0

D(CE, CG)048

47.4

9.0

10.0

D(CE, CG)060

59.0

9.1

10.0

D(CE, CG)072

72.0

9.0

-

1.80/67°F Indoor and 95°F outdoor.

2.EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).

3.SEER = Seasonal Energy Efficiency Ratio.

TABLE 3: GAS HEAT RATINGS1

MODEL

MBH

MBH

AFUE

TEMP

INPUT

OUTPUT

(%)

RISE ºF

 

DCG036N040

50

40

80.9

15 - 45

DCG036N079

100

80

80.5

40 - 70

DCG048N060

75

60

80.9

25 - 55

DCG048N099

125

100

80.3

45 - 75

DCG060N079

100

80

80.5

25 - 55

DCG060N099

125

100

80.3

35 - 65

DCG072N079

100

80

80.5

25 - 55

DCG072N099

125

100

80.3

35 - 65

1. All units are single-stage heating.