York 48 warranty Description, Single Package Air-To-Air Heat Pumps, Features, Seer, SUNLINE 2000

Models: B6CH 048 B5CH 036 B3CH 036 48 60

1 24
Download 24 pages 35.6 Kb
Page 1
Image 1
TECHNICAL GUIDE

TECHNICAL GUIDE

DESCRIPTION

036-21564-002-A-0404

J￿

SINGLE PACKAGE

AIR-TO-AIR

HEAT PUMPS

B3CH 036, 048 & 060 (208/230, 460V) B5CH 036 & 060 (575V), B6CH 048 3, 4 AND 5 NOMINAL TONS

(10 SEER)

SUNLINE 2000

YORK Sunline 2000 Heat Pumps are convertible single package units with a common cabinet and common roof curb for the 3, 4 and 5 ton sizes. The units were designed for residential and light commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame.

All units are self--contained and assembled on rigid full perimeter base rails allowing for 3--way fork lift access and overhead rigging. Every unit is completely charged, wired, piped and tested at the factory to provide for a quick and easy field installation.

The units are available with supplemental electric heaters as field--installed accessories.

Both down and side discharge airflows are available without having to swap panels. The installer simply removes the duct covers for the desired configuration. Economizers may be used on either side or down discharge applications with no modifications required.

All models include a 1--year limited warranty on the complete unit. Compressors and electric heater elements each carry an additional 4--year warranty.

FEATURES

CONTROLS --These heat pumps utilize a unique time-- temperature defrost circuit which adjusts the time between defrost cycles based on the outdoor temperature to provide optimal comfort control and ensure reliable operation. The ambient--modified, time--temperature defrost control extends the time below 35°F and shortens the time above 35°F. The nominal defrost times are field adjustable to 50, 80 and 110 minutes. The defrost time is initiated and terminated by a liquid line control with a 10 minute override limit built into the defrost control.

COMMON FOOTPRINT/COMMON CABINET -- The 3, 4 and 5 ton units all share the exact same cabinet -- and therefore the same roof curb. You now have the flexibility of setting one curb and, after the internal load has been determined, placing the proper tonnage unit on that curb.

HIGH EFFICIENCY --All units have a minimum SEER of 10, a COP of 3.0 (high) and 2.0 (low) and an HSPF as high as 7.3. These efficiencies exceed all legislated minimum levels and provide low operating costs.

CONVERTIBLE AIRFLOW DESIGN -- Both the side and bottom duct openings are covered when they leave the factory. If a side supply/side return is desired, you simply remove the two side duct covers from the outside of the unit and discard them. If a bottom supply/return is desired, you simply remove the two bottom duct covers and discard them. No panel cutting or swapping is required! Convertible airflow design allows maximum field flexibility and minimum inventory.

FACTORY--INSTALLED OPTIONS -- Economizers can be installed at the factory. They are shipped installed and wired. The outdoor air hood needs only to be field assembled and installed.

Adjustable belt--drive blowers are available on most models from the factory for complete air flow flexibility.

FIELD--INSTALLED ACCESSORIES -- Accessories were designed for quick and easy installation. The motorized damper and economizers simply slide in and electrical connections are made by modular plugs. Electric heaters mount easily and knockouts are provided in the internal partitions to connect the elements to the control box single point kit.

The motorized air damper includes a slid--in/plug--in damper assembly with a rainhood and filters. The outdoor air dampers open when the indoor fan motor is energized. The damper is capable of providing 0% through 100% of outdoor return air opening.

The manual outdoor damper provides 0% through 35% or 0% through 100% of return air opening (field adjustable). Designed for duct mounted side or bottom supply/return applications. Includes rain hood assembly and filter.

The 14" high roof curb is shipped knocked down. A roof curb deck is not required because the bottom of the unit is insulated.

WIDE RANGE OF INDOOR AIRFLOWS -- All models operate over a wide range of design conditions with a 3--speeddirect-- drive fan motor. Belt--drive blowers are also available on all models.

FULL PERIMETER BASE RAILS --The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails provide fork lift access from 3 sides and rigging holes are also provided so that an overhead crane can be used to place the units on a roof.

Page 1
Image 1
York 48, 60 warranty Description, Single Package Air-To-Air Heat Pumps, Features, Seer, Technical Guide, SUNLINE 2000

FAQ

What are the features of York Sunline 2000 Heat Pumps?

Features include high efficiency, time-temperature defrost control, common cabinet and footprint, and convertible airflow design.

Are electric heaters and economizers available for York Sunline 2000 Heat Pumps?

Yes, electric heaters are available as field-installed accessories, and economizers can be installed at the factory.

What is the warranty for York Sunline 2000 Heat Pumps?

The units include a 1-year limited warranty on the complete unit, with compressors and electric heater elements carrying an additional 4-year warranty.