York 60 Static Resistances, Heater / Cfm Limitations, Field Wiring, Control Wiring, Power Wiring

Models: B6CH 048 B5CH 036 B3CH 036 48 60

1 24
Download 24 pages 35.6 Kb
Page 10
Image 10
STATIC RESISTANCES

036-21564-002-A-0404

STATIC RESISTANCES

EXTERNAL STATIC PRESSURE DROP

 

 

 

 

 

 

RESISTANCE, IWG

 

 

 

DESCRIPTION

 

 

 

 

CFM

 

 

 

 

 

 

 

1000

1200

1400

1600

1800

2000

2200

2400

2600

Economizer1, 2

 

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

Electric Heaters1

 

5 - 15 KW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

 

20 - 30 KW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

 

 

Bottom Duct Connections1

 

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

1Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

HEATER / CFM LIMITATIONS

HEATER

VOLTAGE1

UNIT MODEL SIZE, NOMINAL TONS

SIZE

3

4

5

NOM. KW

 

MINIMUM SUPPLY AIR CFM

5

 

1,100

1,300

1,600

7

 

1,100

1,300

1,600

10

208 /

1,200

1,300

1,600

15

230-1-60

1,200

1,300

1,600

20

 

1,3002

1,3002

1,600

30

 

-

-

1,600

5

 

1,100

1,300

1,600

7

 

1,100

1,300

1,600

10

208 /

1,200

1,300

1,600

15

230-3-60

1,200

1,300

1,600

20

 

1,3002

1,3002

1,600

30

 

-

-

1,600

HEATER

VOLTAGE1

UNIT MODEL SIZE, NOMINAL TONS

SIZE

3

4

5

NOM. KW

 

MINIMUM SUPPLY AIR CFM

7

 

1,100

1,300

1,600

10

 

1,200

1,300

1,600

15

460-3-60

1,200

1,300

1,600

20

 

1,300

1,300

1,600

30

 

-

-

1,600

10

 

1,200

1,300

1,600

15

575-3-60

1,200

1,300

1,600

20

1,300

1.400

1,600

 

30

 

-

-

1,800

1208/230 and 460 volt heaters are UL approved. 208/230 and 575 volt heaters are CGA approved.

2CGA minimum is 1,400 CFM.

FIELD WIRING

CONTROL WIRING

2

124-volt thermostat with subbase: —2TH11700224 for manual changeover. —2TH11704124 for automatic changeover.

2Only required on units with supplemental electric heat.

2

3

4

TO REMOTE SENSOR 2TH04702224 IF USED

REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, THE WIRING AND OVERCURRENT PROTECTION

POWER WIRING

REFER TO ELECTRICAL DATA

TABLES TO SIZE THE

DISCONNECT SWITCH, THE

WIRING AND OVERCURRENT

PROTECTION

10

Unitary Products Group

Page 10
Image 10
York 60, 48, B3CH 036, B5CH 036 Static Resistances, Heater / Cfm Limitations, Field Wiring, Control Wiring, Power Wiring

FAQ

What are the static resistances in the York Air Conditioner manual?

The manual provides detailed information on static resistances, including external static pressure drop for various CFM levels.

Are there any limitations on heater/CFM in the York Air Conditioner manual?

Yes, the manual outlines heater/CFM limitations based on different nominal ton sizes and minimum supply air CFM.

How should I handle the power wiring for the York Air Conditioner?

Refer to the electrical data tables in the manual to correctly size the disconnect switch, wiring, and overcurrent protection for the power wiring.