York 60, B3CH 036, B5CH 036, B6CH 048 warranty ELECTRICAL DATA - Basic Unit Direct-Drive

Models: B6CH 048 B5CH 036 B3CH 036 48 60

1 24
Download 24 pages 35.6 Kb
Page 11
Image 11

036-21564-002-A-0404

ELECTRICAL DATA - Basic Unit (Direct-Drive)

 

 

VOLTAGE

 

 

OUTDOOR

SUPPLY

 

MAX.

MAX.

 

 

LIMITATIONS

COMPRESSOR

AIR

MINIMUM

FUSE

HACR

MODEL

POWER SUP-

FAN

(SEE NOTE 1)

 

 

BLOWER

CIRCUIT

SIZE,

BREAKER

BCH

PLY

 

 

MOTOR,

 

 

 

 

MOTOR,

AMPACITY

(SEE NOTE 2)

SIZE,

 

 

MIN.

MAX.

RLA

LRA

FLA

 

 

FLA

 

AMPS

AMPS

 

 

 

 

 

 

 

 

 

208/230-1-60

187

253

19.0

105

1.7

4.4

29.9

45

45

036

208/230-3-60

187

253

11.9

85

1.7

4.4

21.0

30

30

460-3-60

414

504

5.9

42

1.0

2.2

10.6

15

15

 

 

575-3-60

518

630

4.8

34

1.0

2.2

10.2

15

15

 

208/230-1-60

187

253

25.0

105

2.3

5.0

38.6

50

60

048

208/230-3-60

187

253

14.7

130

2.3

5.0

25.7

40

40

460-3-60

414

504

7.7

64

1.4

2.2

13.2

20

20

 

 

575-3-60

518

630

6.4

52

1.4

2.2

11.6

15

15

 

208/230-1-60

187

253

32.1

169

2.3

6.6

49.0

80

80

060

208/230-3-60

187

253

19.3

123

2.3

6.6

33.0

50

50

460-3-60

414

504

10.0

62

1.4

3.3

17.2

25

25

 

 

575-3-60

518

630

7.9

50

1.4

3.3

14.6

20

20

NOTES:

1. Rated in accordance with ARI Standard 110, utilization range “A”.

 

 

 

 

 

 

2. Dual element, time delay type.

 

 

 

 

 

 

 

 

ELECTRICAL DATA - Heat Pump with Supplemental Electric Heat (Direct-Drive)

 

 

HEATER

SUPPLY

 

ELECTRIC HEATERS

MINIMUM

MAX.

MAX.

 

 

AIR

 

 

 

 

SIZE

 

MODEL

POWER

ACCESSORY

 

 

 

 

FUSE

2

BLOWER

 

 

 

 

CIRCUIT

HACR

BCH

SUPPLY

MODEL

KW

 

STAGES

TOTAL

SIZE1

 

 

 

NUMBER

MOTOR

 

AMPS

AMPACITY

AMPS

BREAKER

 

 

FLA

 

 

 

 

AMPS

 

 

 

 

 

 

 

 

 

 

 

2CE04500506

 

4.0

 

1

19.1

53.8

60

60

 

 

 

2CE04500706

 

5.6

 

1

27.1

63.7

70

70

 

 

208-1-60

2CE04501006

4.4

8.0

 

1

38.3

77.7

80

80

 

 

 

2CE04501506

 

11.9

 

2

57.4

101.6

110

110

 

 

 

2CE04502006

 

15.9

 

2

76.6

125.5

150

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2CE04500506

 

5.3

 

1

22.1

57.5

70

70

 

 

 

2CE04500706

 

7.5

 

1

31.2

68.9

80

80

 

 

230-1-60

2CE04501006

4.4

10.6

 

1

44.2

85.1

90

90

 

 

 

2CE04501506

 

15.9

 

2

66.2

112.7

125

125

 

 

 

2CE04502006

 

21.2

 

2

88.3

140.3

150

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2CE04500525*

 

4.0

 

1

11.0

34.8

40

40

 

 

 

2CE04500725*

 

5.6

 

1

15.6

40.5

45

45

 

 

208-3-60

2CE04501025

4.4

8.0

 

1

22.1

48.6

50

50

 

036

 

2CE04501525

 

11.9

 

2

33.1

62.4

70

70

 

 

2CE04502025

 

15.9

 

2

44.2

76.2

80

80

 

 

 

 

 

 

 

 

2CE04500525*

 

5.3

 

1

12.7

36.9

45

45

 

 

 

2CE04500725*

 

7.5

 

1

18.0

43.5

50

50

 

 

230-3-60

2CE04501025

4.4

10.6

 

1

25.5

52.8

60

60

 

 

 

2CE04501525

 

15.9

 

2

38.2

68.8

70

70

 

 

 

2CE04502025

 

21.2

 

2

51.0

84.7

90

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2CE04500746*

 

6.8

 

1

8.2

21.2

25

25

 

 

460-3-60

2CE04501046*

2.2

10.1

 

1

12.1

26.4

30

30

 

 

2CE04501546*

13.6

 

1

16.4

31.9

35

35

 

 

 

 

 

 

 

 

2CE04502046*

 

19.5

 

2

23.5

41.2

45

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2CE04501058

 

10.6

 

1

10.2

15.5

20

20

 

 

575-3-60

2CE04501558

2.2

15.9

 

1

15.3

21.9

25

25

 

 

 

2CE04502058

 

21.2

 

1

20.4

28.2

30

30

 

1Dual element, time delay type

2Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.

*These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code ((eg., Chicago), the following fuse

block accessories are available for field installation.

 

Nominal Voltage

 

Voltage

KW Cap

 

 

Multipier

 

 

 

 

 

 

 

 

 

Electric Heat

208

 

208

1.00

 

 

 

 

Correction

240

 

230

0.92

Factors

 

 

 

 

 

 

480

 

460

0.92

 

 

 

 

 

 

600

 

575

0.92

 

 

 

 

 

Fuse Block

2FB04700425

 

208/240 Volts

 

 

 

 

2FB04700546

 

460 Volts

 

 

 

 

 

 

 

Unitary Products Group

11

Page 11
Image 11
York 60, B3CH 036, B5CH 036, B6CH 048 warranty ELECTRICAL DATA - Basic Unit Direct-Drive