York AY012MA321 warranty Physical And Electrical Data, YTG-D-0606, C A B

Models: AY012MA321

1 16
Download 16 pages 4.59 Kb
Page 2
Image 2
PHYSICAL AND ELECTRICAL DATA

246814-YTG-D-0606

PHYSICAL AND ELECTRICAL DATA

MODEL

 

AY012MA321

AY018MA321

AY024MA321

AY030MA321

AY036MA321

Unit Supply Voltage

 

 

208 - 230V, 1 Phase, 60Hz

 

Minimum Circuit Ampacity

 

8.9

9.5

12.0

14.5

18.2

Maximum Overprotection Device1

 

15

15

20

25

30

Rated Load Amps

 

6.7

7.2

8.9

11

13.5

 

Model

2K20S236T6A

2K22S236SUB

2J29S236A1A

2J35S236B1A

H21J30BABCA

 

Brand

Panasonic

Panasonic

Panasonic

Panasonic

Bristol

Compressor

Type

Rotary

Rotary

Rotary

Rotary

Recip

LRA

33.0

40.0

60.0

68.0

78.0

 

 

Start Kit

Yes

Yes

Yes

Yes

No

 

CCH

No

No

No

No

No

 

Length (in)

21-3/4

21-3/4

21-3/4

21-3/4

21-3/4

Dimensions

Width (in)

21-3/4

21-3/4

21-3/4

21-3/4

21-3/4

Height (in)

22-1/2

22-1/2

24-1/4

26-3/4

30-3/4

 

 

Weight (lbs)

85

90

105

110

140

 

HP

1/12

1/12

1/8

1/8

1/4

 

RPM

1100

1100

1075

1075

1100

Fan & Motor

FLA

0.5

0.5

0.8

0.8

1.4

 

CFM

1450

1450

1700

1800

2150

 

Dia (in)

17-1/2

17-1/2

17-1/2

17-1/2

17-1/2

 

Area (ft^2)

7.26

7.26

7.89

8.77

10.17

OD Coil

Rows

1

1

1

1

1

 

Fins / Inch

23

23

23

23

23

Connection OD

Liquid (in)

3/8

3/8

3/8

3/8

3/8

Suction (in)

3/4

3/4

3/4

3/4

3/4

 

Line Set OD

Liquid (in)

3/8

3/8

3/8

3/8

3/8

Suction (in)

5/8

5/8

5/8

3/4

3/4

 

Refrigerant

 

R-22

R-22

R-22

R-22

R-22

Unit Charge (lbs - oz) 2

 

2 - 14

2 - 14

3 - 6

3 - 14

3 - 8

Charge Per Foot - oz

 

0.66

0.66

0.66

0.68

0.68

1.Dual element fuses or HACR circuit breaker.

2.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or

subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

C

A

B

All dimensions are in inches. They are subject to change without notice. certified dimensions will be provided upon request.

 

 

 

 

 

Refrigerant

Unit

Weight

Dimensions (Inches)

Connection

Model

(Lbs.)

 

 

 

Service Valve Size

 

 

A1

B

C

Liquid

Vapor

 

 

 

 

 

 

012

85

22-1/2 21-3/4

21-3/4

 

 

018

90

22-1/2 21-3/4

21-3/4

 

 

 

 

 

 

3/8”

3/4”

024

105

24-1/4 21-3/4

21-3/4

030

110

26-3/4

21-3/4

21-3/4

 

 

036140 30-3/4 21-3/4 21-3/4

1.Including Fan Guard

2

Unitary Products Group