Manual background

246723-YTG-J-1006

COOLING PERFORMANCE DATA

OUTDOOR UNIT MODEL NO.

CZB03611

 

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR COIL MODEL NO.

G2FD036S17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDENSER

ID CFM

 

 

 

1050

 

 

 

 

1200

 

 

 

 

1350

 

 

ENTERING AIR

ID DB (°F)

80

80

 

75

80

80

80

80

75

80

80

80

80

75

80

80

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ID WB (°F)

57

62

 

62

67

72

57

62

62

67

72

57

62

62

67

72

 

T.C.

32.7

33.4

 

31.9

34.6

38.3

34.4

34.2

32.1

35.6

38.5

36.1

34.9

32.4

36.6

38.7

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

30.7

30.6

 

24.4

24.3

19.2

31.9

32.4

26.2

33.4

20.7

33.1

34.1

28.0

42.5

22.1

 

K.W.

2.9

2.9

 

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

35.5

36.2

 

35.4

38.9

41.7

36.8

37.3

36.0

39.8

42.2

38.1

38.4

36.6

40.6

42.6

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

33.7

31.3

 

26.3

26.3

21.1

35.1

33.5

28.0

20.8

22.1

36.6

35.6

29.8

15.4

23.2

 

K.W.

2.5

2.5

 

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

 

T.C.

34.1

34.8

 

33.6

36.7

40.0

35.6

35.7

34.0

37.7

40.3

37.1

36.6

34.5

38.6

40.7

85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

32.2

31.0

 

25.3

25.3

20.1

33.5

32.9

27.1

27.1

21.4

34.8

34.9

28.9

29.0

22.7

 

K.W.

2.7

2.7

 

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

 

T.C.

32.4

32.9

 

31.6

34.8

37.5

33.8

33.8

32.0

35.6

37.8

35.1

34.7

32.4

36.4

38.2

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

30.5

29.7

 

24.4

24.6

19.4

31.8

31.4

26.1

26.3

20.6

33.0

33.1

27.8

28.0

21.8

 

K.W.

3.2

3.2

 

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

 

T.C.

30.7

31.0

 

29.5

32.9

35.1

31.9

31.9

30.0

33.5

35.4

33.1

32.8

30.4

34.2

35.6

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

28.9

28.3

 

23.5

23.8

18.6

30.0

29.8

25.0

25.5

19.8

31.1

31.2

26.6

27.1

21.0

 

K.W.

3.6

3.6

 

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

 

T.C.

29.0

29.1

 

27.6

31.0

32.7

30.1

30.0

28.0

31.5

33.0

31.2

30.9

28.4

32.1

33.2

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

27.3

27.0

 

22.6

23.0

17.8

28.3

28.2

24.0

24.6

19.0

29.3

29.5

25.5

26.2

20.2

 

K.W.

4.1

4.1

 

4.1

4.1

4.0

4.1

4.1

4.1

4.0

4.0

4.1

4.1

4.1

4.0

4.1

 

T.C.

27.4

27.2

 

25.6

29.1

30.3

28.3

28.2

26.0

29.5

30.5

29.3

29.1

26.4

29.9

30.8

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

25.7

25.7

 

21.7

22.3

17.1

26.6

26.7

23.0

23.8

18.2

27.5

27.7

24.4

25.3

19.3

 

K.W.

4.5

4.5

 

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

Air Handler

Coil

T.C.

S.C.

KW

MA12B

FC/MC36B

1.00

1.00

1.00

MA12B

FC/MC42B

1.01

1.00

1.00

MA12B

G*FD046H17

1.01

1.00

1.00

MA14D

G*FD048H24

1.01

1.00

1.00

MV12B

MC36B

1.01

1.00

1.00

MV12B

MC42B

1.01

1.01

1.00

AHP36

1.01

1.00

1.00

 

 

 

 

 

AHP42

1.01

1.00

1.00

 

 

 

 

 

AV36

1.01

1.00

0.95

 

 

 

 

 

F*FP036

1.01

1.01

1.00

 

 

 

 

 

F*FP042

1.02

1.01

1.00

 

 

 

 

 

FC/MC/PC/UC36

1.00

1.00

1.00

 

 

 

 

 

FC/MC/PC/UC42

1.01

1.00

1.00

 

 

 

 

 

G*FA048S17

1.01

1.00

1.00

 

 

 

 

 

G*FA048S21

1.01

1.00

1.00

 

 

 

 

 

G*FD036H21

1.01

1.00

1.00

 

 

 

 

 

G*FD042H21

1.01

1.00

1.00

 

 

 

 

 

G*FD046H17

1.01

1.00

1.00

 

 

 

 

 

G*FD048H21,24

1.01

1.00

1.00

 

 

 

 

 

HC36

1.01

1.00

1.00

 

 

 

 

 

HD36

1.00

1.00

1.00

 

 

 

 

 

Variable Speed

Coil

T.C.

S.C.

KW

Furnace

 

 

 

 

PV8*A12

FC/MC/PC36A

0.98

0.98

1.00

PV9*A12

FC/MC/PC36A

1.00

1.00

1.00

PV8*B16

FC/MC/PC36B

1.01

1.00

1.00

PV9*B12

FC/MC/PC36B

1.00

1.00

1.00

PV8*C16

FC/MC/PC36C

1.01

1.00

1.00

PV8*C20

FC/MC/PC36C

1.01

1.00

1.00

PV9*C16

FC/MC/PC36C

1.00

1.00

1.00

PV9*C20

FC/MC/PC36C

1.00

1.00

1.00

PV8*B16

FC/MC/PC42B

1.03

1.03

1.00

PV9*B12

FC/MC/PC42B

1.01

1.01

1.00

PV8*C16

FC/MC/PC42C

1.03

1.03

1.00

PV8*C20

FC/MC/PC42C

1.03

1.03

1.00

PV8*B16

HC36

1.01

1.00

1.00

PV9*B12

HC36

1.01

1.00

1.00

PV8*C16

HD36

1.01

1.00

1.00

PV9*C16

HD36

1.01

1.00

1.00

PV9*C20

HD36

1.01

1.00

1.00

14

Unitary Products Group

Page 14
Image 14
York CZB018 THRU 060 warranty Cooling Performance Data, YTG-J-1006, Outdoor Unit Model No