COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. | CZB04811 |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
INDOOR COIL MODEL NO. | G1FA060S24 |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CONDENSER | ID CFM |
|
|
| 1400 |
|
|
|
| 1600 |
|
|
|
| 1800 |
|
|
ENTERING AIR | ID DB (°F) | 80 | 80 |
| 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 |
TEMPERATURE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ID WB (°F) | 57 | 62 |
| 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | |
| T.C. | 43.3 | 45.9 |
| 42.8 | 48.1 | 55.4 | 45.5 | 46.7 | 43.4 | 49.0 | 54.8 | 47.7 | 47.5 | 44.0 | 49.9 | 54.3 |
65 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S.C. | 39.3 | 43.5 |
| 33.0 | 34.3 | 27.3 | 41.5 | 44.4 | 35.4 | 36.7 | 28.5 | 43.7 | 45.3 | 37.7 | 39.1 | 29.7 | |
| K.W. | 3.9 | 3.9 |
| 3.9 | 3.9 | 3.9 | 3.9 | 3.9 | 3.9 | 4.0 | 3.9 | 3.9 | 3.9 | 4.0 | 4.0 | 3.9 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| T.C. | 48.0 | 49.5 |
| 47.8 | 53.7 | 57.7 | 50.0 | 50.7 | 48.6 | 54.2 | 58.2 | 52.1 | 51.9 | 49.3 | 54.8 | 58.7 |
75 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S.C. | 43.5 | 42.5 |
| 35.8 | 36.2 | 28.6 | 45.2 | 45.3 | 38.2 | 38.6 | 30.2 | 46.9 | 48.2 | 40.5 | 41.0 | 31.8 | |
| K.W. | 3.3 | 3.4 |
| 3.3 | 3.4 | 3.4 | 3.3 | 3.4 | 3.3 | 3.4 | 3.4 | 3.3 | 3.4 | 3.3 | 3.4 | 3.4 |
| T.C. | 45.6 | 47.7 |
| 45.3 | 50.9 | 56.6 | 47.8 | 48.7 | 46.0 | 51.6 | 56.5 | 49.9 | 49.7 | 46.7 | 52.3 | 56.5 |
85 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S.C. | 41.4 | 43.0 |
| 34.4 | 35.3 | 27.9 | 43.3 | 44.9 | 36.8 | 37.7 | 29.3 | 45.3 | 46.8 | 39.1 | 40.1 | 30.7 | |
| K.W. | 3.6 | 3.6 |
| 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.7 | 3.6 | 3.6 | 3.6 | 3.6 | 3.7 | 3.6 |
| T.C. | 43.3 | 44.9 |
| 42.4 | 47.9 | 52.4 | 45.2 | 45.9 | 43.1 | 48.5 | 52.4 | 47.0 | 46.9 | 43.8 | 49.1 | 52.4 |
95 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S.C. | 39.3 | 40.5 |
| 33.3 | 34.2 | 26.7 | 41.0 | 42.3 | 35.4 | 36.5 | 28.1 | 42.7 | 44.2 | 37.5 | 38.8 | 29.5 | |
| K.W. | 4.2 | 4.2 |
| 4.1 | 4.2 | 4.2 | 4.2 | 4.2 | 4.2 | 4.2 | 4.2 | 4.2 | 4.2 | 4.2 | 4.3 | 4.2 |
| T.C. | 41.0 | 42.0 |
| 39.5 | 44.8 | 48.2 | 42.6 | 43.1 | 40.2 | 45.4 | 48.2 | 44.1 | 44.1 | 40.8 | 45.9 | 48.3 |
105 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S.C. | 37.1 | 38.1 |
| 32.1 | 33.0 | 25.5 | 38.6 | 39.8 | 34.0 | 35.3 | 26.9 | 40.1 | 41.6 | 35.9 | 37.6 | 28.3 | |
| K.W. | 4.7 | 4.8 |
| 4.7 | 4.8 | 4.8 | 4.7 | 4.7 | 4.7 | 4.8 | 4.8 | 4.7 | 4.7 | 4.7 | 4.8 | 4.8 |
| T.C. | 38.8 | 39.3 |
| 36.7 | 41.9 | 44.1 | 40.0 | 40.3 | 37.3 | 42.3 | 44.2 | 41.2 | 41.4 | 38.0 | 42.8 | 44.3 |
115 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S.C. | 35.0 | 35.7 |
| 31.0 | 32.0 | 24.2 | 36.3 | 37.4 | 32.7 | 34.2 | 25.7 | 37.5 | 39.1 | 34.4 | 36.5 | 27.2 | |
| K.W. | 5.2 | 5.3 |
| 5.2 | 5.3 | 5.4 | 5.2 | 5.3 | 5.2 | 5.3 | 5.4 | 5.2 | 5.3 | 5.3 | 5.4 | 5.4 |
| T.C. | 36.6 | 36.5 |
| 33.9 | 38.9 | 40.0 | 37.5 | 37.6 | 34.5 | 39.3 | 40.2 | 38.4 | 38.6 | 35.1 | 39.7 | 40.3 |
125 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S.C. | 33.0 | 33.3 |
| 29.8 | 30.9 | 23.0 | 34.0 | 34.9 | 31.3 | 33.1 | 24.5 | 35.0 | 36.5 | 32.8 | 35.3 | 26.0 | |
| K.W. | 5.8 | 5.8 |
| 5.8 | 5.9 | 5.9 | 5.8 | 5.8 | 5.8 | 5.9 | 5.9 | 5.8 | 5.8 | 5.8 | 5.9 | 5.9 |
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between
Air Handler | Coil | T.C. | S.C. | KW |
MA20D | FC/MC60D | 1.00 | 1.00 | 1.00 |
MA16C | FC60C | 1.00 | 1.00 | 1.00 |
MA20D | G*FD060H24 | 1.00 | 1.00 | 1.00 |
MA20D | G*FD061H24 | 1.02 | 1.01 | 1.00 |
MV20D | MC60D | 1.01 | 1.00 | 1.00 |
AHP/SHP48 | – | 1.01 | 1.00 | 1.00 |
|
|
|
|
|
AHP/SHP60 | – | 1.01 | 1.00 | 1.00 |
|
|
|
|
|
AV/SV48 | – | 1.00 | 1.00 | 0.98 |
|
|
|
|
|
AV/SV60 | – | 1.00 | 1.00 | 0.95 |
|
|
|
|
|
F*FV060 | – | 1.02 | 1.01 | 1.00 |
|
|
|
|
|
– | FC/MC/PC/UC60 | 1.00 | 1.00 | 1.00 |
|
|
|
|
|
– | G*FD060H24 | 1.00 | 1.00 | 1.00 |
|
|
|
|
|
– | G*FD061H24 | 1.02 | 1.01 | 1.00 |
|
|
|
|
|
– | HC60 | 1.00 | 1.00 | 1.00 |
|
|
|
|
|
– | HD60 | 1.00 | 1.00 | 1.00 |
|
|
|
|
|
Variable Speed | Coil | T.C. | S.C. | KW |
Furnace |
|
|
|
|
PV9*D20 | FC/MC/PC60D | 1.01 | 1.00 | 1.00 |
PV9*C20 | FC/PC60C | 1.01 | 1.00 | 1.00 |
PV8*C20 | HC60 | 1.01 | 1.00 | 1.00 |
PV9*D20 | HC60 | 1.01 | 1.00 | 1.00 |
PV8*C20 | HD60 | 1.01 | 1.00 | 1.00 |
PV9*D20 | HD60 | 1.01 | 1.00 | 1.00 |
PV9*C20 | MC60D | 1.01 | 1.00 | 1.00 |
16 | Unitary Products Group |