York D1EE036, D1EG warranty Static Resistances, 036-21411-002-A-0204

Models: D1EG D1EE036

1 32
Download 32 pages 59.56 Kb
Page 14
Image 14

036-21411-002-A-0204

TABLE 11: SUPPLY AIR BLOWER PERFORMANCE - DEE/DEG036-060 W/ DIRECT DRIVE1

MODEL

MOTOR

 

AVAILABLE EXTERNAL STATIC PRESSURE - IWG2

 

 

 

 

 

 

DEE/DEG

SPEED

0.20

 

 

0.30

 

0.40

 

 

0.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

WATTS

CFM

 

WATTS

CFM

 

WATTS

 

CFM

 

WATTS

 

 

 

 

HI

-

-

-

 

-

1699

 

825

 

1650

 

785

 

 

 

036

MED

1684

800

1631

 

780

1582

 

750

 

1524

 

720

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

1487

710

1464

 

690

1421

 

670

 

1367

 

650

 

 

 

 

HI

1996

960

1933

 

936

1868

 

910

 

1795

 

880

 

 

 

048

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MED

1804

838

1765

 

810

1714

 

785

 

1650

 

765

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

1681

760

1640

 

738

1604

 

715

 

1541

 

695

 

 

 

 

HI

2400

1155

2338

 

1125

2274

 

1095

 

2167

 

1045

 

 

 

060

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MED

2290

1105

2214

 

1065

2145

 

1030

 

2071

 

990

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

2150

1020

2100

 

990

2029

 

950

 

1965

 

910

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

MOTOR

 

 

AVAILABLE EXTERNAL STATIC PRESSURE - IWG1

 

 

 

DEE/DEG

SPEED

0.6

 

 

0.70

 

0.80

 

 

0.90

 

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

WATTS

CFM

 

WATTS

CFM

 

WATTS

 

CFM

 

WATTS

CFM

 

WATTS

 

HI

1570

755

1430

 

725

1360

 

700

 

1280

 

680

1180

 

655

036

MED

1410

690

1324

 

650

1260

 

630

 

1185

 

610

1100

 

590

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

1315

620

1246

 

605

1185

 

590

 

1110

 

570

1020

 

545

 

HI

1722

845

1635

 

820

1544

 

790

 

1419

 

765

1300

 

740

048

MED

1589

735

1508

 

705

1407

 

675

 

1306

 

645

1195

 

625

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

1490

670

1416

 

645

1337

 

620

 

1230

 

595

1120

 

575

 

HI

2096

1010

1990

 

980

1887

 

945

 

1771

 

905

1629

 

855

060

MED

1990

950

1911

 

920

1828

 

885

 

1724

 

835

1604

 

798

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

1905

880

1816

 

838

1724

 

800

 

1644

 

770

1531

 

710

1.Side Duct application (230/460/575 Volts)

2.Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to Table 12 for resistance val- ues on applications other than gas / electric units with side duct airflows.

TABLE 12: STATIC RESISTANCES

 

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

DESCRIPTION

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

1000

1200

1400

1600

1800

2000

2200

2400

2600

2800

3000

ECONOMIZER1 2

 

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.30

ELECTRIC HEATERS1

5 - 15 kW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

0.19

0.22

 

 

 

 

 

 

 

 

 

 

 

 

20 - 30 kW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

 

BOTTOM DUCT CONNECTIONS1

 

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

0.19

0.22

COOLING ONLY3

 

0.08

0.10

0.12

0.14

0.16

0.18

0.20

0.23

0.26

0.29

0.32

1.Deduct these resistance values from the available external static pressure shown on Tables 8, 9, 10, and 11.

2.The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

3.Add these resistance values to the available static resistance in the respective Blower Performance Table (see Tables 8, 9, 10, and 11).

14

Unitary Products Group

Page 14
Image 14
York D1EE036, D1EG warranty Static Resistances, 036-21411-002-A-0204