a.
b.Filter drier/strainer to eliminate any moisture or for- eign matter.
c.Accessible service gage connections on both suc- tion and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.
d.The refrigeration system shall provide at least 15 ºF of liquid
4.Unit Controls:
a.Unit shall be complete with self contained
b.Unit shall incorporate a
I.
II.
III.
If any of the above safety devices trip, an LED
c.Unit shall incorporate AUTO RESET compressor over temperature, over current protection.
d.Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy
GAS HEATING SECTION (DEG MODELS)
1.Shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition and redundant main gas valve. Ventor wheel shall be con- structed of stainless steel for corrosion resistance.
2.The heat exchanger shall be of the tubular type, con- structed of
3.Burners shall be of the
4.All gas piping shall enter the unit cabinet at a single loca- tion, through either the side or bottom, without any field modifications.
5.An integrated control board shall provide timed control of evaporator fan functioning and burner ignition.
6.Heating section shall be provided with the following mini- mum protection:
a.Primary and auxiliary
b.Induced draft motor speed sensor.
c.Flame roll out switch (automatic reset).
d.Flame proving controls.
ELECTRIC HEATING SECTION (DEE MODELS)
1.An electric heating section, with nickel chromium ele- ments, shall be provided in a range of 5 through 30 KW, offering two stages of capacity - 16 KW and above on 208/230 volt heaters and 20 KW and above on 460 and 575 volt heaters.
2.The heating section shall have a primary limit control(s) and automatic reset, to prevent the heating element sys- tem from operating at an excessive temperature.
3.The Heating Section assembly shall slide out of the unit for easy maintenance and service.
4.Units with Electric Heating Sections shall be wired for a single point power supply with branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
1.Unit shall be capable of starting and running at 125 ºF outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240.
2.The compressor, with standard controls, shall be capable of operation down to 45 ºF outdoor temperature. Acces- sory low ambient kit shall be available for operation down to 0 ºF.
3.Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up. (Gas heat only.)
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES
•Compressor- 5 Years
•Heat Exchanger- 10 Years
•Elect. Heat. Elem.- 5 Years
•Parts - 1 Year
Unitary Products Group | 31 |