FIGURE 11 -UNIT DIMENSIONS DEG 3, 4, & 5 TON

036-21411-002-A-0204

RETURNAIR

TABLE 24: DEE/DEG UNIT CLEARANCES SUPPLYAIR

OUTDOORAIR

OUTDOORAIR (Economizer)

DEG UNITS 3-5 TON

FIGURE 11 -UNIT DIMENSIONS DEG 3, 4, & 5 TON

TABLE 24: DEE/DEG UNIT CLEARANCES

FRONT

 

DEE UNITS

24”

 

DEG UNITS

32”

 

 

 

 

 

 

 

 

 

12” (Less Economizer)

BACK

 

36” (With Economizer or

 

Fixed Air/Motorized

 

 

 

 

 

 

Damper)

 

 

 

 

LEFT SIDE (Filter Access)

 

24” (Less Economizer)

 

36” (With Economizer)

 

 

 

RIGHT SIDE (Cond. Coil)

 

24”

 

 

 

BELOW UNIT1

 

0”

ABOVE UNIT2

 

72” (For Condenser Air

 

Discharge)

 

 

 

1.Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.

2.Units must be installed outdoors. Overhanging struc- tures or shrubs should not obstruct condenser air dis- charge outlet.

Note: DEE Models and ductwork are approved for zero clearance to combustible materials when equipped with electric heaters.

Note: EG Models must have a 1” clearance between any combustible material and the supply air ductwork for a distance of 3 feet from the unit.

The products of combustion must not be allowed to accumu- late within a confined space and recirculate. Locate unit so that the vent air outlet hood is at least:

Three feet above any forced air inlet located within 10 horizontal feet (excluding those integral to the unit).

Four feet below, 4 horizontal feet from, or 1 foot above any door or gravity air inlet into the building.

Four feet from electric meters, gas meters, regulators and relief equipment.