|
|
| |
| TABLE 10 - LIMIT CONTROL SETTING |
| |
|
| Capacity, MBH | Limit Control |
I G N . C O N T R O L # 2 Input | Output | Opens, ° F | |
| 300 | 240 | 195 |
I G N . C O N T R O L # 1 | 400 | 320 | 195 |
|
|
|
|
|
| R O L L O U T S W . | ||
S E N S O R # 1 | G V 1 | ||||
|
| ||||
|
|
|
| G A S | |
|
|
|
| ||
|
|
|
| V A L | V E |
|
|
|
|
G V 2 |
|
|
G A S |
| I G N I T O R |
|
| |
V A L V E |
|
|
I G N I T O R | # 2 | S E N S O R |
|
HEAT ANTICIPATOR SETPOINTS
It is important that the anticipator setpoint be correct. Too high of a setting will result in longer heat cycles and a greater temperature swing in the conditioned space. Reducing the value below the correct setpoint will give shorter “ON” cycles and may result in the lowering of the temperture within the conditioned space.
|
|
|
|
| |
# 1 | Gas Valve | Anticipator Setpoint | |||
|
| 1st Stage | 2nd Stage | ||
|
|
| |||
| Honeywell VR8440 | 0.30 amp | 0.11 amp | ||
# | White2 | ||||
|
|
PRE-START CHECK LIST
Complete the following checks before starting the unit.
| 1. | Check the type of gas being supplied. Be sure that it is the |
B U R N E R | C O M P A RsameTasMlistedEon Nthe unitT nameplate. | |
FIG | 2. | Make sure that the vent and combustion air hoods have been |
|
| properly installed. |
START-UP
6.Auxiliary Limit Switch (AUX) This control is located inside
the heat exchanger compartment and is set to open at 190° F. It is a manual reset switch. If AUX limit trips, then the primary limit has not functioned correctly., Replace the primary limit
OPERATING INSTRUCTIONS
CAUTION: This furnace is equipped with an intermittent pilot and automatic
TO LIGHT PILOT AND MAIN BURNERS:
1.Turn “off” electric power to unit.
2.Turn room thermostat to lowest setting.
3.Turn gas valve knob to “on” position.
4.Turn “on” electric power to unit.
5.Set room thermostat to desired temperature.
(If thermostat “set” temperature is above room temperature, pilot burner ignition will occur and, after an interval to prove pilot flame, main burners will ignite).
TO SHUT DOWN:
1.Turn “off” electric power to unit.
2.Depress knob of gas valve while turning to “off” position.
POST-START CHECK LIST (GAS)
After the entire control circuit has been energized and the heating section is operating, make the following checks:
1.Check for gas leaks in the unit piping as well as the supply piping.
2.Check for correct manifold gas pressures. See “Checking Gas Input”.
3.Check the supply gas pressure. It must be within the limits shown on rating nameplate. Supply pressure should be checked with all gas appliances in the building at full fire. At no time should the standby gas line pressure exceed 13", nor the operating pressure drop below 5.0" for natural gas units. If gas pressure is outside these limits, contact the
HIGH FIRE ADJ. (UNDER SCREW)
PILOT ADJ. (UNDER SCREW)
FIG. 14 - TYPICAL GAS VALVE
local gas utility for corrective action.
MANIFOLD GAS PRESSURE ADJUSTMENT
Small adjustments to the
Adjust as follows:
1.Remove the cap on the regulator. It’s located next to the
2.To decrease the gas pressure, turn the adjusting screw counterclockwise.
Unitary Products Group | 17 |