York D2CG300 Adjustment Of Temperature Rise, Checking Gas Input, Gas Rate - Cubic Feet Per Hour

Models: D2CG300 D2CE

1 24
Download 24 pages 32.97 Kb
Page 19
Image 19
ADJUSTMENT OF TEMPERATURE RISE

 

530.18-N11Y

2. Insert at least 8" of 1/4 inch tubing into each of these holes

NOTE: DE-ENERGIZE THE COMPRESSORS BEFORE TAKING ANY TEST

for sufficient penetration into the air flow on both sides of

MEASUREMENTS TO ASSURE A DRY INDOOR COIL.

the indoor coil.

 

NOTE: The tubes must be inserted and held in a position perpendicular to the air flow so that velocity pres- sure will not affect the static pressure readings.

3.Using an inclined manometer, determine the pressure drop across a dry evaporator coil. Since the moisture on an

evaporator coil may vary greatly, measuring the pressure drop across a wet coil under field conditions would be inaccurate. To assure a dry coil, the compressors should

CHECKING GAS INPUT be deactivated while the test is being run.

4.Knowing the pressure drop across a dry coil, the actual CFM through the unit and clean 2" filters, can be determined from the curve in the Pressure Drop Verses Supply Air CFM figure.

WARNING: Failure to properly adjust the total system air quan-

FIG. 18 - PRESSURE DROP ACROSS A DRY INDOOR COIL VS SUPPLY AIR CFM

tity can result in extensive blower damage.

After readings have been obtained, remove the tubes and reinstall the two 5/16" dot plugs that were removed in Step 1.

CFM =

Btuh Input x 0.8

1.08 x oF Temp. Rise

 

ADJUSTMENT OF TEMPERATURE RISE

The temperature rise (or temperature difference between the return air and the heated air from the furnace) must lie within the range shown on the ETL rating plate.

After the temperature rise has been determined, the cfm can be calculated as follows:

After about 20 minutes of operation, determine the furnace temperature rise. Take readings of both the return air and the heated air in the ducts (about six feet from the furnace) where they will not be affected by radiant heat. Increase the blower cfm to decrease the temperature rise; decrease the blower cfm to increase the rise. Refer to the Blower Motor And Drive Data table.

BELT DRIVE BLOWER

All units have belt drive single-speed blower motors. The variable pitch pulley on the blower motor can be adjusted to obtain the desired supply air CFM. Tighten belts enough to prevent slipping. but do not over tighten. Belt deflection should be between 1/4" and 1/2" per foot. Refer to the table for Blower Motor And Drive Data.

CHECKING GAS INPUT

NATURAL GAS

1.Turn off all other gas appliances connected to the gas meter.

2.With the furnace turned on, measure the time needed for one revolution of the hand on the smallest dial on the meter. A typical gas meter usually has a 1/2 or a 1 cubic foot test dial.

3.Using the number of seconds for each revolution and the size of the test dial increment, find the cubic feet of gas consumed per hour from the Gas RateTable.

TABLE 11 - GAS RATE - CUBIC FEET PER HOUR

Seconds

Size of Test Dial

for One

1/2 cu. ft.

1 cu. ft.

Rev.

 

 

4

450

900

6

300

600

8

228

450

10

180

360

12

150

300

14

129

257

16

113

225

18

100

200

20

90

180

22

82

164

24

75

150

26

69

138

28

64

129

Example: By actual measurement, it takes 13 seconds for the hand on the 1-cubic foot dial to make a revolution with just a 300,000 Btuh furnace running. Read across to the column in the table above, headed “1 Cubic Foot”, where you will see that 278 cubic feet of gas per hour are consumed by the furnace at that rate. Multiply 278 x 1050 (the Btu rating of the gas obtained from the local gas company). The result is 292,425 Btuh, which is close to the 300,000 Btuh rating of the furnace.

SECURE OWNER’S APPROVAL: When the system is functioning properly, secure the owner’s approval. Show him the location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust temperature settings within the limitations of the system.

Unitary Products Group

19

Page 19
Image 19
York D2CG300, D2CE Adjustment Of Temperature Rise, Checking Gas Input, Gas Rate - Cubic Feet Per Hour