TYPICAL WIRING DIAGRAM LEGEND

174065-YIM-A-0206

TYPICAL WIRING DIAGRAM LEGEND

CB

CIRCUIT BREAKER 24V, 3 AMP

CCH

CRANKCASE HEATER (OPTIONAL)

COMPR

COMPRESSOR

DS

DEFROST SENSOR, CLOSES @ 31˚F, OPENS @ 55˚F.

F1 F2 F3

FUSES, LINE VOLTAGE - 60 AMP (10, 15, 20 & 25 KW ELEC HEAT)

F4 F5 F6

FUSES, LINE VOLTAGE - 30 AMP (10, 15, 20 & 25 KW ELEC HEAT)

F7 F8 F9

FUSES, LINE VOLTAGE - 30 AMP (20, 25 KW ELEC HEAT)

F24

FUSE 24V SECONDARY, 5 AMP

FS

FREEZESTAT SWITCH (OPTIONAL ACCESSORY) OPEN @ 26˚ F

HP

HIGH PRESSURE SWITCH (OPTIONAL ACCESSORY) OPENS @ 280 PSIG

HTR 1

ELECTRIC HEATER (OPT. ACCSSRY: ALL KW ELEC HEAT)

HTR 2

ELECTRIC HEATER (OPT. ACCSSRY: 7.5, 10, 15, 20 & 25 KW ELEC HEAT)

HTR 3

ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)

HTR 4

ELECTRIC HEATER (OPT. ACCSSRY: 15, 20 & 25 KW ELEC HEAT)

HTR 5

ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)

HTR 6

ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)

K1

RELAY INDOOR FAN MOTOR

K2

RELAY ELECTRIC HEATER

K3

RELAY ELECTRIC HEATER, 24 VDC COIL

K7

RELAY LIMIT TRIP, 25 VDC COIL

LP

LOW PRESSURE SWITCH (OPTIONAL ACCESSORY) OPEN @ 7 PSIG

LS

LIMIT SWITCH, ELECTRIC HEAT (PART OF ELEC HEAT ACCESSORY)

M1

CONTACTOR, COMPRESSOR & OUTDOOR FAN

M2

CONTACTOR, ELECTRIC HEAT, 230V COIL

M3

CONTACTOR, ELECTRIC HEAT, 230V COIL

PTCR

START ASSIST (OPTIONAL DEVICE)

RC1/RC2

COMPRESSOR START & OUTDOOR FAN RUN CAPACITOR

RC1

COMPRESSOR START CAPACITOR (ALTERNATE)

RC2

OUTDOOR FAN RUN CAPACITOR (ALTERNATE)

RC3

INDOOR FAN RUN CAPACITOR

RVS

REVERSING VALVE SOLENOID

S2/P2

SOCKET/PLUG CONNECTION ON FAN CONTROL BOARD, LOW VOLTAGE

S3/P3

SOCKET/PLUG CONNECTION ON FAN CONTROL BOARD, LINE VOLTAGE

S4/P4

SOCKET/PLUG CONNECTION ON ID FAN MOTOR, 24V

S3/P3

SOCKET/PLUG CONNECTION ON ID FAN MOTOR, 230V

T1

TRANSFORMER, 24V, 40 VA

TB2

TERMINAL BLOCK ECM MOTOR "SPEED" CONNECTIONS

 

IDENTIFIED TERMINAL ON RUN CAPACITOR

 

ROOM THERMOSTAT 24V CONNECTIONS

 

TB1 ON FAN/ELEC HEAT CONTROL BOARD

 

FACTORY WIRING AND DEVICES

 

OPTIONAL WIRING AND DEVICES

 

FIELD WIRING

TYPICAL WIRING DIAGRAM NOTES