York D2EB Clearances, Duct Work, Filters, Condensate Drain, Service Access, Thermostat

Models: D2EB

1 16
Download 16 pages 40.19 Kb
Page 3
Image 3
CLEARANCES

174065-YIM-A-0206

CLEARANCES

All units require certain clearances for proper operation and service. Refer to Figure 3 for the clearances required for com- bustion, construction, servicing and proper unit operation.

WARNING: Do not permit overhanging structures or shrubs to obstruct the condenser air discharge outlet.

DUCT WORK

These units are adaptable to downflow use as well as rear sup- ply and return air duct openings. To convert to downflow, use the following steps:

1.Remove the duct covers found in the bottom return and supply air duct openings. There are four (4) screws secur- ing each duct cover (save these screws to use later).

2.Install the duct covers, removed in step one, to the rear sup- ply and return air duct openings. Secure with the four (4) screws used in step one.

3.Seal the duct covers with silicone caulking.

Downflow units must have an L-shaped supply duct without any outlets or registers located directly below the supply outlet of the unit.

Duct work should be designed and sized according to the methods of the Air Conditioning Contractors of America (ACCA), as set forth in their Manual D.

A closed return duct system shall be used. This shall not pre- clude use of economizers or ventilation air intake. Flexible joints may be used in the supply and return duct work to mini- mize the transmission of noise.

FILTERS

Single phase units are shipped without a filter and is the responsi- bility of the installer to secure a filter in the return air ductwork or install a Filter/Frame Kit (1FF0114).

A filter rack and a filters are standard on three phase units.

Filters must always be used and must be kept clean. When fil- ters become dirt laden, insufficient air will be delivered by the blower, decreasing your units efficiency and increasing operat- ing costs and wear-and-tear on the unit and controls.

Filters should be checked monthly especially since this unit may be used for both heating and cooling.

CONDENSATE DRAIN

A condensate trap is required to be installed in the condensate drain. The plumbing must conform to local codes. Use a seal- ing compound on male pipe threads. Install the condensate drain line (3 4“ NPTF) to spill into an open drain.

SERVICE ACCESS

Access to all serviceable components is provided by the follow- ing removable panels:

Blower service access

Electrical/filter access

Compressor service access

Refer to Figure 3 for location of these access panels and mini- mum clearance.

CAUTION: When fastening duct work to the side duct flanges on the unit, insert the screws through the duct flanges only. DO NOT insert the screws through the casing. Outdoor duct work must be insulated and waterproofed.

NOTE: Be sure to note supply and return openings.

Refer to Figure 3 for information concerning rear and bottom supply and return air duct openings.

TABLE 3 - PHYSICAL DATA

THERMOSTAT

The room thermostat should be located on an inside wall ap- proximately 56" above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appli- ances. Follow manufacturer's instructions enclosed with the thermostat for general installation procedure. Four or five color coded insulated wires (minimum #18 AWG) should be used to connect thermostat to unit. See Figure 2.

 

MODELS

 

 

 

DEB

 

 

 

 

018

024

030

036

042

048

060

 

 

EVAPORATOR

CENTRIFUGAL BLOWER (Dia. x Wd. in.)

9 X 6

10 X 8

10 X 8

10 x 8

11 X 10

11 x 10

11 x 10

BLOWER

FAN MOTOR HP (Three Speed)

2

2

2

4

4

4

1

 

 

1

1

1

3

3

3

 

EVAPORATOR

ROWS DEEP

2

2

2

2

2

2

3

FINS PER INCH

13

15

15

15

15

13

16

COIL

FACE AREA (Sq. Ft.)

2.19

2.81

4.38

4.38

4.38

5.62

5.26

 

CONDENSER

PROPELLER DIA. (in.)

22

22

22

22

22

22

22

FAN MOTOR HP

1

1

1

1

1

1

1

FAN

4

4

4

4

4

4

4

NOM. CFM TOTAL

1,800

2,200

2,400

2,400

2,400

2,800

2,800

 

CONDENSER

ROWS DEEP

1

1

1

1

1

1

1

FINS PER INCH

18

16

20

18

16

13

20

COIL

FACE AREA (Sq. Ft.)

8.3

8.3

8.3

8.3

11.7

16.4

16.4

 

CHARGE

REFRIGERANT 22 (lbs./oz.)

3 / 4

3 / 5

3 / 13

3 / 10

4 / 7

5 / 15

5 / 15

FILTER

FACE AREA (Sq. Ft. / Qty. / Size)

 

 

2.14 / 2 / 14" x 22"

 

 

COMPRESSOR

HERMETIC Type, (Qty. = 1)

Recip

Recip

Recip

Recip

Recip

Scroll

Scroll

Unitary Products Group

3

Page 3
Image 3
York D2EB installation instructions Clearances, Duct Work, Filters, Condensate Drain, Service Access, Thermostat