174065-YIM-A-0206

TABLE 10 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB042

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,400 CFM/TON

 

 

TEMPERATURE

 

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

 

(F)

55

57

 

59

61

63

65

67

69

71

 

73

75

 

 

 

65

20.3

21.9

 

23.5

25.0

26.6

28.1

29.7

30.6

31.6

 

32.6

33.6

70

16.7

18.5

 

20.3

22.1

23.9

25.7

27.5

28.6

29.7

 

30.8

32.0

75

13.0

15.1

 

17.1

19.2

21.2

23.2

25.3

26.6

27.8

 

29.1

30.4

80

9.4

11.7

 

13.9

16.2

18.5

20.8

23.1

24.5

25.9

 

27.3

28.7

85

5.7

8.2

 

10.8

13.3

15.8

18.4

20.9

22.5

24.0

 

25.6

27.1

90

-

6.5

 

9.1

11.7

14.2

16.8

19.4

21.0

22.6

 

24.1

25.7

95

-

-

 

7.4

10.0

12.7

15.3

17.9

19.5

21.1

 

22.7

24.3

100

-

-

 

5.8

7.9

10.0

12.0

14.1

16.3

18.4

 

20.6

22.8

105

-

-

 

-

5.8

7.3

8.7

10.2

13.0

15.8

 

18.6

21.4

110

-

-

 

-

-

-

5.5

6.4

9.8

13.2

 

16.5

19.9

115

-

-

 

-

-

-

-

-

6.5

10.5

 

14.5

18.5

TABLE 11 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB048

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,600 CFM/TON

 

 

TEMPERATURE

 

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

 

(F)

55

57

 

59

61

63

65

67

69

71

 

73

75

 

 

 

65

13.5

15.4

 

17.3

19.1

21.0

22.8

24.7

26.1

27.6

 

29.0

30.5

70

10.7

12.7

 

14.7

16.8

18.8

20.9

22.9

24.7

26.5

 

28.2

30.0

75

7.8

10.0

 

12.2

14.5

16.7

18.9

21.2

23.3

25.4

 

27.5

29.6

80

-

7.3

 

9.7

12.1

14.5

17.0

19.4

21.8

24.2

 

26.7

29.1

85

-

-

 

7.2

9.8

12.4

15.0

17.6

20.4

23.1

 

25.9

28.6

90

-

-

 

6.1

7.7

9.4

11.0

12.7

16.6

20.5

 

24.4

28.3

95

-

-

 

-

5.7

6.3

7.0

7.7

12.7

17.8

 

22.8

27.9

100

-

-

 

-

5.3

5.9

6.5

7.1

11.1

15.1

 

19.1

23.0

105

-

-

 

-

-

5.5

6.0

6.6

9.5

12.4

 

15.3

18.2

110

-

-

 

-

-

5.0

5.5

6.0

7.8

9.7

 

11.6

13.4

115

-

-

 

-

-

-

-

5.4

6.2

7.0

 

7.8

8.6

TABLE 12 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB060

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 2,000 CFM/TON

 

 

TEMPERATURE

 

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

 

(F)

55

57

 

59

61

63

65

67

69

71

 

73

75

 

 

 

65

25.3

25.8

 

26.3

26.8

27.3

27.8

28.3

28.7

29.1

 

29.6

30.0

70

22.2

23.0

 

23.7

24.4

25.1

25.9

26.6

27.4

28.2

 

28.9

29.7

75

19.2

20.1

 

21.1

22.1

23.0

24.0

24.9

26.1

27.2

 

28.3

29.4

80

16.1

17.3

 

18.5

19.7

20.9

22.1

23.3

24.7

26.2

 

27.7

29.1

85

13.1

14.5

 

15.9

17.3

18.8

20.2

21.6

23.4

25.2

 

27.0

28.9

90

10.3

11.7

 

13.1

14.5

15.9

17.3

18.6

21.1

23.5

 

25.9

28.3

95

7.6

8.9

 

10.3

11.6

13.0

14.3

15.7

18.7

21.8

 

24.8

27.8

100

6.6

7.7

 

8.9

10.1

11.3

12.5

13.6

16.7

19.7

 

22.7

25.8

105

5.6

6.6

 

7.6

8.6

9.6

10.6

11.6

14.6

17.6

 

20.7

23.7

110

-

5.4

 

6.2

7.0

7.9

8.7

9.5

12.5

15.6

 

18.6

21.6

115

-

-

 

-

5.5

6.2

6.8

7.5

10.5

13.5

 

16.5

19.5

Unitary Products Group

9

Page 9
Image 9
York D2EB installation instructions YIM-A-0206