530.18-N8Y

TABLE 10 - ELECTRICAL DATA (BASIC UNIT) w/Direct-Drive Blower Motor

 

 

VOLTAGE

 

SCROLL

COND.

SUPPLY

 

MAX.

MAX.

 

 

LIMITATIONS

 

AIR

MINIMUM

FUSE

HACR

UNIT

POWER

 

COMPRESSOR

FAN

(SEE NOTE 1)

 

BLOWER

CIRCUIT

SIZE,

BREAKER

SIZE

SUPPLY

 

 

 

MOTOR,

 

 

 

 

 

MOTOR,

AMPACITY

(SEE NOTE 2)

SIZE,

 

 

MIN.

MAX.

 

RLA

LRA

FLA

 

 

 

FLA

 

AMPS

AMPS

 

 

 

 

 

 

 

 

 

 

208/230-1-60

187

253

 

18.0

105.0

1.3

4.4

28.2

45

45

036

208/230-3-60

187

253

 

11.4

90.0

1.3

4.4

20.0

30

30

460-3-60

414

504

 

6.2

45.0

0.8

2.2

10.8

15

15

 

 

 

575-3-60

518

630

 

5.0

36.0

0.8

2.2

9.3

15

-

 

208/230-1-60

187

253

 

24.4

140.0

1.3

5.0

36.8

60

60

048

208/230-3-60

187

253

 

14.1

105.0

1.3

5.0

23.9

35

35

460-3-60

414

504

 

7.1

55.0

0.8

2.2

11.9

15

15

 

 

 

575-3-60

518

630

 

5.6

44.0

0.8

2.2

10.1

15

-

 

208/230-1-60

187

253

 

28.9

165.0

1.3

6.6

44.0

70

70

060

208/230-3-60

187

253

 

16.0

125.0

1.3

6.6

27.9

40

40

460-3-60

414

504

 

8.0

67.0

0.8

3.3

14.1

20

20

 

 

 

575-3-60

518

630

 

6.4

50.0

0.8

3.3

12.1

15

-

 

208/230-3-60

187

253

 

20.3

146.0

1.3

6.8

33.5

50

50

072

460-3-60

414

504

 

10.2

73.0

0.8

3.6

17.2

25

25

 

575-3-60

518

630

 

8.2

58.4

0.8

3.6

14.7

20

-

NOTES: 1. Utilization Range “A” in accordance with ARI Standard 110.

2. Dual element, time delay type.

 

 

 

 

TABLE 11 - ELECTRICAL DATA (BASIC UNIT) w/Belt-Drive Blower Motor

 

 

VOLTAGE

SCROLL

COND.

SUPPLY

 

MAX.

MAX.

 

 

LIMITATIONS

AIR

MINIMUM

FUSE

HACR

UNIT

POWER

COMPRESSOR

FAN

(SEE NOTE 1)

BLOWER

CIRCUIT

SIZE,

BREAKER

SIZE

SUPPLY

 

 

MOTOR,

 

 

 

 

MOTOR,

AMPACITY

(SEE NOTE 2)

SIZE,

 

 

MIN.

MAX.

RLA

LRA

FLA

 

 

FLA

 

AMPS

AMPS

 

 

 

 

 

 

 

 

 

208/230-1-60

187

253

18.0

105.0

1.3

5.3

29.1

45

45

036

208/230-3-60

187

253

11.4

90.0

1.3

5.3

20.9

30

30

460-3-60

414

504

6.2

45.0

0.8

3.1

11.7

15

15

 

 

575-3-60

518

630

5.0

36.0

0.8

3.1

10.2

15

-

 

208/230-1-60

187

253

24.4

140.0

1.3

8.6

40.4

60

60

048

208/230-3-60

187

253

14.1

105.0

1.3

5.2

24.1

35

35

460-3-60

414

504

7.1

55.0

0.8

2.6

12.3

15

15

 

 

575-3-60

518

630

5.6

44.0

0.8

2.0

9.9

15

-

 

208/230-1-60

187

253

28.9

165.0

1.3

8.6

46.0

70

70

060

208/230-3-60

187

253

16.0

125.0

1.3

6.0

27.3

40

40

460-3-60

414

504

8.0

67.0

0.8

3.0

13.8

20

20

 

 

575-3-60

518

630

6.4

50.0

0.8

2.4

11.2

15

-

 

208/230-3-60

187

253

20.3

146.0

1.3

7.3

34.0

50

50

072

460-3-60

414

504

10.2

73.0

0.8

3.7

17.3

25

25

 

575-3-60

518

630

8.2

58.4

0.8

2.8

13.9

20

-

NOTES: 1. Utilization Range “A” in accordance with ARI Standard 110. 2. Dual element, time delay type.

TABLE 12 - SUPERHEAT CHARGING TABLE FOR MODEL 036

OUTDOOR

 

SUPERHEAT AT SCROLL COMPRESSOR SUCTION, °F, AIRFLOW = 400 CFM/TON

 

TEMPERATURE,

 

 

 

 

INDOOR WB TEMPERATURE, °F

 

 

 

 

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

55

57

59

61

 

63

65

67

 

69

71

73

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

25.6

26.8

28

29.2

 

30.4

31.6

32.8

 

33.3

33.9

34.4

34.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

20.1

21.7

23.3

24.9

 

26.5

28.1

29.6

 

30.6

31.5

32.4

33.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

14.6

16.6

18.5

20.5

 

22.5

24.5

26.5

 

27.8

29.1

30.5

31.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

9.0

11.4

13.8

16.2

 

18.5

20.9

23.3

 

25.0

26.8

28.5

30.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85

-

6.3

9.0

11.8

 

14.6

17.4

20.1

 

22.3

24.4

26.6

28.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90

-

-

6.7

9.1

 

11.4

13.8

16.2

 

18.9

21.7

24.4

27.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

95

-

-

-

6.3

 

8.3

10.3

12.3

 

15.6

18.9

22.2

25.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

-

-

-

5.3

 

6.8

8.4

10.0

 

13.4

16.8

20.2

23.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

105

-

-

-

-

 

5.4

6.5

7.7

 

11.2

14.7

18.2

21.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

110

-

-

-

-

 

-

-

5.4

 

9.0

12.6

16.2

19.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

115

-

-

-

-

 

-

-

-

 

6.8

10.5

14.1

17.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

Unitary Products Group

Page 12
Image 12
York D7CG 036, D7CG 048, D7CG 060, D2CG 072 installation instructions Superheat Charging Table For Model