530.18-N8Y

INSTALLATION

LIMITATIONS

These units must be installed in accordance with the current editions of the following national and local safety codes:

In the U.S.A.:

1.National Electrical Code ANSI/NFPA No. 70.

2.National Fuel Gas Code Z223.1.

3.Gas-Fired Central Furnace Standard ANSI Z21.47-1993.

4.Local gas utility requirements.

In Canada:

1.Canadian Electrical Code CSA C22.1

2.Current Gas Installation Codes CAN/CGA-2.3-M93.

3.Local plumbing and waste water codes.

4.Other applicable local codes.

Refer to Table 1 for Unit Application Data and to Table 2 for Gas Heat Application Data.

If components are to be added to a unit to meet local codes, they are to be installed at the dealer’s and / or the customer’s expense.

Size of unit for proposed installation should be based on heat loss / heat gain calculation made according to the methods of Air Conditioning Contractors of America (ACCA).

4.Roof structures must be able to support the weight of the unit and its options and / or accessories. Unit must be installed on a solid level roof curb or appropriate angle iron frame.

CAUTION: If a unit is to be installed on a roof curb or special frame other than a YORK roof curb, gasketing must be applied to all surfaces that come in contact with the unit underside.

5.Maintain level tolerance to 1/2" maximum across the entire length or width of the unit.

6.Elevate the unit sufficiently to prevent any blockage of the air entrances by snow in areas where there will be snow accumulation. Check the local weather bureau for the expected snow accumulation in your area.

RIGGING AND HANDLING

Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails. Spreaders, whose length exceeds the largest dimension across the unit, MUST be used across the top of the unit.

BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY.

TABLE 1 - UNIT APPLICATION DATA

UNIT SIZE

 

036

048

060

072

Voltage Variation

208/230V

 

187 / 253

 

 

460V

 

414 / 504

 

Min. / Max.1

 

 

 

 

575V

 

518/630

 

 

 

 

 

Supply Air CFM, Nom.

 

1200

1600

2000

2400

Wet Bulb Temperature (°F) of

57 / 72

57 / 72

57 / 72

57 / 72

Air on Evaporator Coil,

 

Min. / Max.

 

 

 

 

 

Dry Bulb Temperature (°F) of

45 / 120

45 / 120

45 / 120

45 / 120

Air on Condenser Coil,

 

Min.2 / Max.

 

 

 

 

 

1Utilization range “A” in accordance with ARI Standard 110.

2A low ambient accessory is available for operation down to 0°F.

LOCATION

Use the following guidelines to select a suitable location for these units.

1.Unit is designed for outdoor installation only.

2.Condenser coils must have an unlimited supply of air. Where a choice of location is possible, position the unit on either north or east side of building.

WARNING: Excessive exposure of this furnace to contami- nated combustion air may result equipment dam- age or personal injury. Typical contaminates include: permanent wave solutions, chlorinated waxes and cleaners, chlorine based swimming pool chemicals, water softening chemicals, carbon tetrachloride, Halogen type refrigerants, cleaning solvents (e.g. perchloroethylene), printing inks, paint removers, varnishes, hydrochloric acid, ce- ments and glues, antistatic fabric softeners for clothes dryers, masonry acid washing materials.

3.For ground level installation, a level pad or slab should be used. The thickness and size of the pad or slab used should meet local codes and unit weight. Do not tie the slab to the building foundation.

Units may also be moved or lifted with a forklift. Slotted openings in the base rails are provided for this purpose.

LENGTH OF FORKS MUST BE A MINIMUM OF 42".

Remove the nesting brackets from the four corners on top of the unit. All screws that are removed when taking these brackets off must be replaced on the unit.

CAUTION: An adhesive backed label is provided over the outside of the combustion air inlet opening to pre- vent moisture from entering the unit which could cause damage to electrical components. Allow this closure label to remain in place until the combus- tion air hood is to be installed (refer to Figure 5).

Refer to Table 5 for unit weights and to Figure 8 for approximate center of gravity.

CLEARANCES

All units require certain clearances for proper operation and service. Installer must make provisions for adequate combustion and ventilation air in accordance with Section 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 (in U.S.A.) or Sections 7.2, 7.3 or 7.4 of Gas Installation Codes CAN/CGA-B149.1 and .2 (in Canada) and/or applicable provisions of the local building codes. Refer to Figure 9 for the clearances required for combustible construction, servicing, and proper unit operation.

WARNING: Do not permit overhanging structures or shrubs to obstruct condenser air discharge outlet, combustion air inlet or vent outlet.

DUCTWORK

Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America (ACCA).

A closed return duct system shall be used. This shall not preclude use of economizers or outdoor fresh air intake. The supply and return air duct connections at the unit should be made with flexible joints to minimize the transmission of noise.

Unitary Products Group

3

Page 3
Image 3
York D2CG 072, D7CG 036, D7CG 048, D7CG 060 installation instructions Installation

D2CG 072, D7CG 060, D7CG 048, D7CG 036 specifications

The York D7CG 060, D7CG 048, D7CG 036, and D2CG 072 are advanced rooftop unit models designed for enhanced energy efficiency, reliability, and ease of use in commercial HVAC applications. These models are known for their robust features and technologies aimed at providing optimal indoor climate control.

The D7CG series, including the 060, 048, and 036 models, is built around a highly efficient design. They incorporate scroll compressors that operate quietly, contributing to a comfortable environment. The units are designed for high-ambient performance, enabling them to function efficiently even in extreme temperature conditions. The D7CG series also features an intelligent control system that allows for seamless integration with building management systems, optimizing energy usage and enhancing overall system performance.

One of the standout features of the D7CG models is their advanced heat exchanger technology, which improves heat transfer and overall efficiency. The coil design allows for superior airflow and enhanced temperature regulation, ensuring consistent comfort levels throughout the space. With variable-speed fans, these units adjust airflow dynamically, providing further energy savings and tailored climate control.

The D2CG 072 model, on the other hand, accentuates versatility and robustness. This unit also boasts a high-efficiency compressor and features a unique multi-stage heating and cooling process. Its modular design allows for easy installation and maintenance. The D2CG 072 is engineered for flexible configurations, accommodating various building sizes and layouts without compromising performance.

All four models are equipped with user-friendly digital controls that offer precise adjustments and monitoring capabilities. This feature allows building operators to quickly respond to changing conditions, ensuring optimal comfort for occupants while maintaining energy efficiency. Furthermore, they adhere to stringent environmental standards, incorporating low-GWP refrigerants that minimize their ecological footprint.

In summary, the York D7CG 060, D7CG 048, D7CG 036, and D2CG 072 models represent cutting-edge technology and innovative design in the commercial HVAC sector. Their high efficiency, advanced features, and user-centric controls make them suitable for a wide range of applications, ensuring reliable performance and comfort in diverse environments.