TABLE 34: ADDITIONAL STATIC RESISTANCE (METRIC)
M3S | Cooling Only1 | Economizer2 3 |
| Electric Heat kW2 |
| |||
9 | 18 | 24 | 36 | 54 | ||||
|
|
| ||||||
|
|
|
|
|
|
|
| |
0.89 | 14.9 | 5.0 | 12.4 | 14.9 | 17.4 | 19.9 | 24.8 | |
|
|
|
|
|
|
|
| |
0.99 | 17.4 | 5.0 | 14.9 | 17.4 | 19.9 | 22.4 | 27.3 | |
|
|
|
|
|
|
|
| |
1.08 | 19.9 | 5.0 | 17.4 | 19.9 | 22.4 | 24.8 | 32.3 | |
|
|
|
|
|
|
|
| |
1.18 | 22.4 | 5.0 | 19.9 | 22.4 | 24.8 | 27.3 | 34.8 | |
|
|
|
|
|
|
|
| |
1.27 | 27.3 | 7.5 | 22.4 | 24.8 | 29.8 | 32.3 | 39.7 | |
|
|
|
|
|
|
|
| |
1.36 | 29.8 | 7.5 | 24.8 | 27.3 | 32.3 | 34.8 | 44.7 | |
|
|
|
|
|
|
|
| |
1.46 | 34.8 | 7.5 | 29.8 | 32.3 | 37.3 | 39.7 | 49.7 | |
|
|
|
|
|
|
|
| |
1.55 | 39.7 | 7.5 | 32.3 | 34.8 | 42.2 | 44.7 | 54.6 | |
|
|
|
|
|
|
|
| |
1.65 | 44.7 | 9.9 | 37.3 | 39.7 | 47.2 | 49.7 | 59.6 | |
|
|
|
|
|
|
|
| |
1.74 | 49.7 | 9.9 | 42.2 | 44.7 | 52.2 | 49.7 | 64.6 | |
|
|
|
|
|
|
|
| |
1.83 | 57.1 | 9.9 | 47.2 | 49.7 | 57.1 | 59.6 | 69.5 | |
|
|
|
|
|
|
|
| |
1.93 | 62.1 | 9.9 | 52.2 | 54.6 | 62.1 | 64.6 | 77.0 | |
|
|
|
|
|
|
|
| |
1.02 | 69.5 | 12.4 | 57.1 | 59.6 | 69.5 | 72.0 | 84.4 | |
|
|
|
|
|
|
|
| |
2.12 | 74.5 | 12.4 | 62.1 | 64.6 | 74.5 | 77.0 | 91.9 | |
|
|
|
|
|
|
|
| |
2.21 | 82.0 | 12.4 | 69.5 | 72.0 | 82.0 | 84.4 | 99.3 | |
|
|
|
|
|
|
|
| |
2.30 | 89.4 | 12.4 | 74.5 | 77.0 | 86.9 | 91.9 | 106.8 | |
|
|
|
|
|
|
|
| |
2.40 | 96.9 | 14.9 | 82.0 | 84.4 | 94.4 | 99.3 | 114.2 | |
|
|
|
|
|
|
|
| |
2.49 | 104.3 | 14.9 | 86.9 | 91.9 | 101.8 | 106.8 | 121.7 | |
|
|
|
|
|
|
|
| |
2.59 | 111.8 | 14.9 | 94.4 | 99.3 | 109.3 | 114.2 | 131.6 | |
|
|
|
|
|
|
|
| |
2.68 | 119.2 | 14.9 | 101.8 | 106.8 | 116.7 | 121.7 | 139.1 | |
|
|
|
|
|
|
|
| |
2.77 | 129.1 | 17.4 | 109.3 | 114.2 | 124.2 | 131.6 | 146.5 | |
|
|
|
|
|
|
|
| |
2.87 | 139.1 | 17.4 | 116.7 | 121.7 | 131.6 | 139.1 | 154.0 | |
|
|
|
|
|
|
|
| |
2.96 | 149.0 | 17.4 | 124.2 | 131.6 | 139.1 | 146.5 | 161.4 | |
|
|
|
|
|
|
|
|
1.Add these resistance values to the available static resistance in the respective Blower Performance Tables.
2.Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
3.The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 62.1 Pa, the unit will deliver less M3S during full economizer operation.
TABLE 35: ELECTRIC HEAT MINIMUM SUPPLY AIR - IMPERIAL
| HEATER | UNIT MODEL SIZE, NOMINAL TONS | ||||
|
|
|
|
|
|
|
kW |
|
| VOLTAGE | 7.5 | 10 | 12.5 |
|
|
|
|
| ||
| MINIMUM SUPPLY AIR CFM | |||||
|
|
|
| |||
|
|
|
|
|
|
|
9 |
|
|
| 2250 | N/A | N/A |
|
|
|
|
|
|
|
18 |
|
|
| 2250 | 3000 | 3750 |
|
|
|
|
|
|
|
24 |
| 380/415 | 2250 | 3000 | 3750 | |
|
|
|
|
|
|
|
36 |
|
|
| 2250 | 3000 | 3750 |
|
|
|
|
|
|
|
54 |
|
|
| N/A | 3000 | 3750 |
|
|
|
|
|
|
|
TABLE 36: ELECTRIC HEAT MINIMUM SUPPLY AIR - METRIC
| HEATER | UNIT MODEL SIZE, NOMINAL TONS | |||
|
|
|
|
|
|
kW |
| VOLTAGE | 7.5 | 10 | 12.5 |
|
|
|
| ||
| MINIMUM SUPPLY AIR M3S | ||||
|
|
| |||
9 |
|
| 1.06 | N/A | N/A |
|
|
|
|
|
|
18 |
|
| 1.06 | 1.42 | 1.76 |
|
|
|
|
|
|
24 |
| 380/415 | 1.06 | 1.42 | 1.76 |
|
|
|
|
|
|
36 |
|
| 1.06 | 1.42 | 1.76 |
|
|
|
|
|
|
54 |
|
| N/A | 1.42 | 1.76 |
|
|
|
|
|
|
30 | Unitary Products |