TABLE 34: ADDITIONAL STATIC RESISTANCE (METRIC)

M3S

Cooling Only1

Economizer2 3

 

Electric Heat kW2

 

9

18

24

36

54

 

 

 

 

 

 

 

 

 

 

 

0.89

14.9

5.0

12.4

14.9

17.4

19.9

24.8

 

 

 

 

 

 

 

 

0.99

17.4

5.0

14.9

17.4

19.9

22.4

27.3

 

 

 

 

 

 

 

 

1.08

19.9

5.0

17.4

19.9

22.4

24.8

32.3

 

 

 

 

 

 

 

 

1.18

22.4

5.0

19.9

22.4

24.8

27.3

34.8

 

 

 

 

 

 

 

 

1.27

27.3

7.5

22.4

24.8

29.8

32.3

39.7

 

 

 

 

 

 

 

 

1.36

29.8

7.5

24.8

27.3

32.3

34.8

44.7

 

 

 

 

 

 

 

 

1.46

34.8

7.5

29.8

32.3

37.3

39.7

49.7

 

 

 

 

 

 

 

 

1.55

39.7

7.5

32.3

34.8

42.2

44.7

54.6

 

 

 

 

 

 

 

 

1.65

44.7

9.9

37.3

39.7

47.2

49.7

59.6

 

 

 

 

 

 

 

 

1.74

49.7

9.9

42.2

44.7

52.2

49.7

64.6

 

 

 

 

 

 

 

 

1.83

57.1

9.9

47.2

49.7

57.1

59.6

69.5

 

 

 

 

 

 

 

 

1.93

62.1

9.9

52.2

54.6

62.1

64.6

77.0

 

 

 

 

 

 

 

 

1.02

69.5

12.4

57.1

59.6

69.5

72.0

84.4

 

 

 

 

 

 

 

 

2.12

74.5

12.4

62.1

64.6

74.5

77.0

91.9

 

 

 

 

 

 

 

 

2.21

82.0

12.4

69.5

72.0

82.0

84.4

99.3

 

 

 

 

 

 

 

 

2.30

89.4

12.4

74.5

77.0

86.9

91.9

106.8

 

 

 

 

 

 

 

 

2.40

96.9

14.9

82.0

84.4

94.4

99.3

114.2

 

 

 

 

 

 

 

 

2.49

104.3

14.9

86.9

91.9

101.8

106.8

121.7

 

 

 

 

 

 

 

 

2.59

111.8

14.9

94.4

99.3

109.3

114.2

131.6

 

 

 

 

 

 

 

 

2.68

119.2

14.9

101.8

106.8

116.7

121.7

139.1

 

 

 

 

 

 

 

 

2.77

129.1

17.4

109.3

114.2

124.2

131.6

146.5

 

 

 

 

 

 

 

 

2.87

139.1

17.4

116.7

121.7

131.6

139.1

154.0

 

 

 

 

 

 

 

 

2.96

149.0

17.4

124.2

131.6

139.1

146.5

161.4

 

 

 

 

 

 

 

 

1.Add these resistance values to the available static resistance in the respective Blower Performance Tables.

2.Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

3.The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 62.1 Pa, the unit will deliver less M3S during full economizer operation.

TABLE 35: ELECTRIC HEAT MINIMUM SUPPLY AIR - IMPERIAL

 

HEATER

UNIT MODEL SIZE, NOMINAL TONS

 

 

 

 

 

 

 

kW

 

 

VOLTAGE

7.5

10

12.5

 

 

 

 

 

 

MINIMUM SUPPLY AIR CFM

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

2250

N/A

N/A

 

 

 

 

 

 

 

18

 

 

 

2250

3000

3750

 

 

 

 

 

 

 

24

 

380/415

2250

3000

3750

 

 

 

 

 

 

 

36

 

 

 

2250

3000

3750

 

 

 

 

 

 

 

54

 

 

 

N/A

3000

3750

 

 

 

 

 

 

 

TABLE 36: ELECTRIC HEAT MINIMUM SUPPLY AIR - METRIC

 

HEATER

UNIT MODEL SIZE, NOMINAL TONS

 

 

 

 

 

 

kW

 

VOLTAGE

7.5

10

12.5

 

 

 

 

 

MINIMUM SUPPLY AIR M3S

 

 

 

9

 

 

1.06

N/A

N/A

 

 

 

 

 

 

18

 

 

1.06

1.42

1.76

 

 

 

 

 

 

24

 

380/415

1.06

1.42

1.76

 

 

 

 

 

 

36

 

 

1.06

1.42

1.76

 

 

 

 

 

 

54

 

 

N/A

1.42

1.76

 

 

 

 

 

 