York DM 240 DM VOLTAGE LIMITATIONS1, Physical Data, YTG-B-0107, Models, DM180, DM240, DM300

Models: DM 180 DM 240 DM 300

1 40
Download 40 pages 35.24 Kb
Page 28
Image 28
TABLE 22: DM VOLTAGE LIMITATIONS1

262259-YTG-B-0107

TABLE 22: DM VOLTAGE LIMITATIONS1

VOLTAGE LIMITATIONS

VOLTAGE

LIMITATIONS

POWER

VOLTAGE

SUPPLY

 

 

MIN.

MAX.

208/230-3-60

187

253

 

 

 

460-3-60

414

506

575-3-60

518

630

 

 

 

1.Utilization Range “A” in accordance with ARI Standard 110.

TABLE 23: PHYSICAL DATA

 

MODELS

 

 

DM180

DM240

DM300

 

 

 

 

 

 

 

 

EVAPORATOR

CENTRIFUGAL BLOWER (Dia. x Wd.)

 

 

15x15

18x15

18x15

BLOWER

FAN MOTOR HP, STANDARD/HI STATIC

 

 

5.0

7.5

10/15

 

ROWS DEEP

 

 

 

3

3

4

EVAPORATOR COIL

FINS PER INCH

 

 

 

 

13.5

 

 

FACE AREA (Sq. Ft.)

 

 

15.5

20

20.52

CONDENSER FAN

PROPELLER DIA. (In.) (Each)

 

 

 

30

 

FAN MOTOR HP

(Each)

 

 

 

1

 

(Two Per Unit)

 

 

 

 

NOM. CFM TOTAL

(Each)

 

 

6,500

7,200

7,200

 

 

 

CONDENSER

ROWS DEEP

 

 

 

2

2

2

FINS PER INCH

 

 

 

13

20

20

COIL

 

 

 

FACE AREA (Sq. Ft.)

 

 

36

43.3

43.3

 

 

 

COMPRESSOR

5 TON HERMETIC (RECIP.)

 

 

1

-

-

10 TON TANDEM (RECIP.)

 

 

11

2

-

(Qty. Per Unit)

 

 

12.5 TON (SCROLL)

 

 

-

-

2

 

 

 

 

QUANTITY PER UNIT (12" X 24" X 2" or 4”)

 

-

-

-

 

QUANTITY PER UNIT (16" X 20" X 2" or 4”)

 

-

4

4

FILTERS

QUANTITY PER UNIT (16" X 25" X 2" or 4”)

 

-

4

4

 

QUANTITY PER UNIT (18" X 24" X 2" or 4”)

 

5

-

-

 

TOTAL FACE AREA (Sq. Ft.)

 

 

15

20

24

CHARGE

REFRIGERANT

SYSTEM No.1

 

 

17/8

18/0

18/0

22 (Lb./Oz.)

SYSTEM No. 2

 

 

8/8

18/0

18/0

 

 

 

 

 

COOLING ONLY

 

 

1900

2100

2291

 

BASIC UNIT

GAS / ELECTRIC

N24

2100

2300

2491

 

 

N32

2140

2340

2531

 

 

 

 

 

ECONOMIZER

 

 

 

160

 

 

 

ECONOMIZER WITH

 

 

 

245

 

 

 

POWER EXHAUST

 

 

 

 

 

 

 

 

 

 

 

 

OPTIONS

MOTORIZED DAMPER

 

 

150

 

OPERATING

ELECTRIC HEATER

 

54 KW

 

35

 

 

 

 

 

18 KW

 

25

 

 

 

 

 

36 KW

 

30

 

WEIGHTS

 

 

 

 

 

 

 

 

 

 

72 KW

 

40

 

(LBS.)

 

 

 

 

 

 

HOT GAS BYPASS

 

 

 

10

 

 

 

 

 

 

 

 

 

SUPPLY FAN VFD

 

 

 

See Table 24

 

 

ACCESSORIES

ROOF CURB

 

 

175

185

185

 

 

BAROMETRIC DAMPER

 

 

45

 

 

 

ECONOMIZER / MOTORIZED

 

55

 

 

 

DAMPER RAIN HOOD

 

 

 

 

 

 

 

 

 

 

 

ECONOMIZER / POWER

 

 

90

 

 

 

EXHAUST RAIN HOOD

 

 

 

 

 

 

 

 

 

 

 

WOOD SKID

 

 

200

220

220

1. This compressor will be energized first.

28

Unitary Products Group

Page 28
Image 28
York DM 240, DM 300, DM 180 warranty DM VOLTAGE LIMITATIONS1, Physical Data, YTG-B-0107, Models, DM180, DM240, DM300