York E1FB240, E1FB180 installation manual System Sequence Of Operation, General

Models: E1FB240 E1FB180

1 20
Download 20 pages 61.58 Kb
Page 11
Image 11
OPERATION

035-16192-001-A-1001

INDOOR

NON-ADJUSTABLE

NON-ADJUSTABLE

 

COIL

THERMAL EXPANSION

OUTDOOR

 

THERMAL EXPANSION

 

VALVE FOR HEATING

COIL

 

VALVE FOR COOLING

 

(5°F SUPER HEAT)

 

 

(10°F SUPER HEAT)

 

 

 

 

SYSTEM SEQUENCE OF OPERATION FILTER DRIERS

CHECK

VALVE

 

FIELD-INSTALLED

BRAZED

LIQUID LINE

REVERSING

CONNECTIONS

 

VALVE WITH

 

24-VOLT

 

SOLENOID

 

FIELD-INSTALLED

 

VAPOR LINE

KEY

COOLING CYCLE FLOW

HEATING CYCLE FLOW

SERVICE VALVES WITH

COPPER STUB CONNECTIONS

COMPRESSOR SUCTION LINE

ACCUMULATOR

FIG. 6 - REFRIGERANT FLOW DIAGRAM

OPERATION

GENERAL

During the cooling cycle, when the reversing valve solenoids becomes energized, operation will be the same as any conven- tional air conditioning system.

During the heating cycle, when the reversing valve solenoids becomes de-energized, compressor discharge gas will be di- verted to the indoor coil and the outdoor coil will become the evaporator.

Refer to Figure 6 for illustration showing the flow of refrigerant through a heat pump system.

CAUTION: Reversing valves and check valves are precise mechanical devices and will not tolerate any me- chanical abuse such as hammering. If a refrigerant system isn't properly cleaned after a compressor burn-out, scale may build up at these devices and prevent them from operating properly.

SYSTEM SEQUENCE OF OPERATION

The following sequences of operation are based on using the manual changeover thermostat. Refer to the respective unit wiring diagram.

COOLING OPERATION

The following controls will be1. energized through terminal O on the thermostat to put the system in the cooling mode.

Relays RY3, RY4, RY5, and RY6

If the fan switch on the thermostat2. is in the “ON” position, in- door section blower motor contactor 10M will be energized through terminal G to provide continuous blower operation. If the switch is in the “AUTO” position, the blower will oper- ate only when the thermostat calls for cooling operation.

3.When TC1 of the thermostat closes on demand for cooling, a circuit is made from the Y terminal on DC1 and DC2

Unitary Products Group

11

Page 11
Image 11
York E1FB240, E1FB180 installation manual System Sequence Of Operation, General