035-16192-001-A-1001

TABLE 5 - LIQUID LINES

 

 

Nominal

Refrigerant

Type L

Pressure Drop3

 

 

 

Vertical

Model Designation

Capacity

Flow Rate1

Copper Tubing

Friction2

 

 

(Tons)

(Lbs./Min.)

(Inches O.D.)

(PSI/100 Ft.)

Rise

 

 

(PSI/Ft.)

 

 

 

 

 

 

180

System 1

7-1/2

22.5

5/8

3.5

0.5

System 2

 

 

 

 

 

 

240

System 1

10

30.0

5/8

5.8

0.5

System 2

 

 

 

 

 

 

1Based on Refrigerant-22 at the nominal capacity of the condensing unit, a liquid temperature of 105°F and a suction temperature of 40°F.

2These friction losses do not include any allowances for a strainer, filter-drier, solenoid valve, isolation valve or fittings.

3The total pressure drop of the liquid line for both friction and vertical rise must not exceed 40 PSI. If the pressure drop exceeds 40 PSI, the liquid refrigerant could flash before it reaches the

TABLE 6 - REFRIGERANT LINE CHARGE

Refrigerant

Line Size,

Refrigerant1 Charge

Line2

OD (In.)

(Lb/Ft)

Liquid

5/8

0.113

Vapor

1-1/8

0.013

1-3/8

 

 

1Charges are based on 40°F suction temperature and 105°F liquid temperature. 2Type “L” copper tubing.

Use these line charges to adjust the system operating charge when the refrigerant lines are more or less than the 25 feet listed in Table 2.

Turn the stem in (or clockwise)3. between 1/4 and 1/2 turn to open the access port.

As soon as some internal pressure is relieved, close the ac-

cess port. DO NOT remove the entire holding charge.

NOTE: The copper disc on the liquid connection will prevent any internal pressure from being relieved through the main port of the liquid line stop valve.

If the unit has already lost its holding charge, it should be leak tested and the necessary repairs should be made. If the unit has maintained its holding charge, you can assume that it has no leaks and proceed with the installation.

CAUTION: Dry nitrogen should always be supplied through a connection while it is being brazed or unbrazed be- cause the temperature required to make or break a brazed joint is sufficiently high to cause oxidation of the copper unless an inert atmosphere is pro- vided. The flow of nitrogen should be continued until the joint has cooled.

WARNING The dry nitrogen must always be supplied through a pressure regulating valve.

Before installing the liquid line between the outdoor and in- door units, remove the copper disc from the liquid connection on the outdoor unit per the following procedure:

Make sure the refrigerant 1in. the line has been recovered and that the liquid service valve on the unit is front-seated and closed. The valve stem should be turned to its maxi- mum clockwise position.

Drill a small hole through the2.disc before unbrazing it to per- mit a flow of dry nitrogen through the connection while it is being unbrazed.

WARNING: This hole is also required to prevent the internal pressure from building up as the disc is being un- brazed and from blowing the disc off.

This warning applies to any disc being removed from a service valve, coil connection, etc.

Remove the cap from the 1/4"3. access port on the liquid line stop valve.

Connect a supply of dry nitrogen4. to this access port.

Unbraze the copper disc from5. the liquid connection while maintaining a minimum flow of dry nitrogen through the connection.

After the disc has been removed,

Burnish the external surfaces1. of the liquid connection on the outdoor unit and the end of the field-supplied piping be- ing used for the liquid line.

NOTE: Clean surfaces are essential for a well brazed connec- tion.

2.Carefully clean the internal surfaces of the above. Any par- ticles left on these surfaces may lead to a future system malfunction.

NOTE: Use only copper tubing that has been especially cleaned and dehydrated for refrigerant use. If the tub- ing has been open for an extended period of time, it should be cleaned before being used.

The liquid line connections can now be brazed while maintain- ing a minimum flow of dry nitrogen through the piping.

NOTE: A filter-drier is factory-mounted in the outdoor unit for the heating cycle and in the indoor unit for the cooling cycle.

Do NOT install another filter-drier in the field-supplied liquid line because refrigerant will flow in both direc- tions on a heat pump system.

Recover the holding charge of the indoor unit and then remove the sealing caps or discs from both its liquid and vapor connec- tions per the following procedure:

1.Make sure the refrigerant in the lines has been recovered, then drill a small hole through both the liquid disc and the vapor disc. If the holding charge has already been lost, the coil should be leak-tested and the necessary repairs should be made.

2.Move the dry nitrogen supply from the access port on the liquid line service valve of the outdoor unit to the hole through the vapor disc on the indoor unit.

3.Unbraze the coil's liquid line disc while maintaining a flow of dry nitrogen across the connection and through the hole in the liquid line disc.

8

Unitary Products Group

Page 8
Image 8
York E1FB180, E1FB240 installation manual Liquid Lines, Refrigerant Line Charge

E1FB240, E1FB180 specifications

The York E1FB180 and E1FB240 are part of York's advanced series of commercial heating and cooling systems, specifically designed to meet the dynamic needs of modern edifices. These models stand out due to their balance of efficiency, reliability, and innovative technology, making them ideal solutions for a myriad of industrial and commercial applications.

One of the main features of the York E1FB series is its impressive energy efficiency. Both the E1FB180 and E1FB240 incorporate high-efficiency compressors that significantly reduce electricity consumption while providing optimal performance. This energy efficiency is crucial not only for reducing operational costs but also for ensuring compliance with increasingly stringent environmental regulations.

In terms of technology, the E1FB series utilizes advanced inverter-driven technology. This feature allows the system to adjust its cooling and heating output based on real-time demand, enabling it to operate at varying speeds. Consequently, this results in quieter operation and a reduction in wear and tear on the components, prolonging the lifespan of the equipment.

Moreover, both models possess robust construction to withstand the rigors of commercial environments. They are built using high-quality materials that ensure durability and reliability even in challenging conditions. This is complemented by an array of corrosion-resistant features, making them suitable for installation in diverse geographical locations, including coastal areas where salt and moisture are prevalent.

The York E1FB180 and E1FB240 also come equipped with sophisticated control systems. These smart controls allow for easy integration into building management systems, enabling real-time monitoring and management. This integration facilitates better energy management practices, yielding further operational savings and improved efficiency.

Additionally, the E1FB series incorporates environmentally friendly refrigerants that align with global initiatives for reducing greenhouse gas emissions. This commitment to sustainability is a cornerstone of York’s design philosophy and is increasingly important for businesses seeking to enhance their green credentials.

In summary, the York E1FB180 and E1FB240 are exemplary models that reflect the brand's commitment to efficiency, durability, and advanced technology. Their innovative features make them a preferred choice for businesses looking to invest in reliable HVAC solutions that not only meet but exceed contemporary performance and environmental standards.