York F*FP Accessories, Limitations, Refer to Price Manual for specific model numbers, YTG-B-0707

Models: F*FV F*FP

1 16
Download 16 pages 57.55 Kb
Page 4
Image 4
ACCESSORIES

ACCESSORIES

Refer to Price Manual for specific model numbers.

VERTICAL SUSPENSION KIT - The suspension kit is designed to be used with all sizes of fan coil units whenever the application requires vertical suspension of the unit.

ELECTRIC HEATERS - Models shown under Electrical Data include sequencers and temperature dual limit switches for safe, efficient operation. Circuit breakers are provided where shown.

BOLT-ON THERMAL EXPANSION VALVE - TXV kits are available for enhanced efficiency. These fan coil units have factory installed TXV’s.

295421-YTG-B-0707

LIMITATIONS

These units must be wired and installed in accordance with all national and local safety codes. Voltage limits are as fol- lows:

Normal Operating voltage Range1

187-253

1. Utilization range “A” in accordance with ARI Std. 110.

Air flow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units:

Entering Air Temperature Limits

Wet Bulb Temp. ºF

Dry Bulb Temp. ºF

Min.

Max.

Min.

Max.

57

72

65

95

EXTENDED AIRFLOW DATA1 FOR 230 VOLT - HEAT PUMP MODELS

 

Blower Motor

 

 

 

 

230 Volt

 

 

 

 

 

Models

 

 

 

CFM @ External Static Pressure - IWC

 

 

 

Speed

 

 

 

 

 

 

 

 

0.10

0.20

0.30

0.40

0.50

0.60

0.70

 

0.80

0.90

1.00

 

High

950

910

865

835

775

730

662

 

590

502

400

F4FP024H06T2*

Med

845

815

785

745

705

654

594

 

524

439

344

 

Low

650

630

605

575

540

508

450

 

383

285

158

 

High

1,270

1,210

1,150

1,085

1,015

946

862

 

769

645

502

F4FP030H06T2*

Med

1,050

1,040

995

930

855

804

714

 

624

494

364

 

Low

855

820

780

735

680

624

550

 

447

333

190

 

High

-

1,310

1,250

1,175

1,120

1,053

983

 

894

779

645

F4FP036H06T2*

Med

1,200

1,150

1,100

1,040

985

933

879

 

795

711

587

 

Low

1,060

1,015

970

925

860

809

740

 

661

572

453

 

High

1,270

1,210

1,150

1,085

1,015

946

802

 

769

645

502

F4FP040H06T2*

Med

1,050

1,040

995

930

855

804

714

 

624

494

364

 

Low

855

820

780

735

680

624

550

 

447

333

190

 

High

-

1,575

1,500

1,420

1,350

1,273

1,192

 

1,102

996

871

F4FP042H06T2*

Med

1,460

1,395

1,330

1,260

1,190

1,125

1,052

 

960

842

695

 

Low

1,250

1,200

1,155

1,100

1,050

1,001

931

 

851

751

631

 

High

1,575

1,535

1,475

1,390

1,310

1,245

1,147

 

1,030

897

735

F4FP045H06T2*

Med High

1,375

1,315

1,255

1,185

1,110

1,040

944

 

848

732

606

Med Low

1,210

1,160

1,110

1,050

980

921

844

 

737

640

533

 

 

 

Low

1,035

990

940

890

825

770

698

 

616

524

432

 

High

2223

2158

2090

2029

1929

1861

1788

 

1679

1594

1501

 

Med High

1948

1904

1801

1815

1777

1741

1681

 

1618

1539

1453

F5FP048H06T2*

Med

1741

1690

1649

1606

1564

1516

1476

 

1436

1387

1353

 

Med Low

1499

1454

1415

1370

1328

1269

1228

 

1191

1132

1093

 

Low

1286

1233

1177

1142

1092

1039

987

 

960

888

842

 

High

2195

2145

2070

2008

1920

1852

1754

 

1663

1570

1462

 

Med High

1938

1899

1873

1824

1791

1724

1679

 

1603

1521

1420

F5FP060H06T2*

Med

1726

1681

1641

1607

1560

1517

1485

 

1433

1402

1349

 

Med Low

1525

1483

1441

1383

1356

1291

1253

 

1208

1169

1123

 

Low

1306

1254

1204

1160

1114

1061

1008

 

980

914

876

 

High

2,285

2,195

2,105

2,015

1,950

1,845

1,770

 

1,685

1,590

1,485

F4FV060H06T2*

Med.

2,125

2,020

1,910

1,805

1,705

1,597

1,491

 

1,386

1,280

1,175

 

Low

1,655

1,605

1,550

1,500

1,450

1,398

1,326

 

1,245

1,153

1,052

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Air flow data shown above 0.50” W.C. external static pressure is for REFERENCE ONLY. Maximum allowable external static when electric heat is used is limited to 0.50” W.C. Maximum allowable external static pressure may also be limited by minimum CFM requirements for proper Heat Pump operation.

1. Includes Return Air Filter and Largest Electric Heater.

All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.

4

Unitary Products Group

Page 4
Image 4
York F*FP, F*FV specifications Accessories, Limitations, Refer to Price Manual for specific model numbers, YTG-B-0707