ACCESSORIES
Refer to Price Manual for specific model numbers.
VERTICAL SUSPENSION KIT - The suspension kit is designed to be used with all sizes of fan coil units whenever the application requires vertical suspension of the unit.
ELECTRIC HEATERS - Models shown under Electrical Data include sequencers and temperature dual limit switches for safe, efficient operation. Circuit breakers are provided where shown.
LIMITATIONS
These units must be wired and installed in accordance with all national and local safety codes. Voltage limits are as fol- lows:
Normal Operating voltage Range1 |
1. Utilization range “A” in accordance with ARI Std. 110.
Air flow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units:
Entering Air Temperature Limits
Wet Bulb Temp. ºF | Dry Bulb Temp. ºF | ||
Min. | Max. | Min. | Max. |
57 | 72 | 65 | 95 |
EXTENDED AIRFLOW DATA1 FOR 230 VOLT - HEAT PUMP MODELS
| Blower Motor |
|
|
|
| 230 Volt |
|
|
|
|
| |
Models |
|
|
| CFM @ External Static Pressure - IWC |
|
|
| |||||
Speed |
|
|
|
|
|
| ||||||
|
| 0.10 | 0.20 | 0.30 | 0.40 | 0.50 | 0.60 | 0.70 |
| 0.80 | 0.90 | 1.00 |
| High | 950 | 910 | 865 | 835 | 775 | 730 | 662 |
| 590 | 502 | 400 |
F4FP024H06T2* | Med | 845 | 815 | 785 | 745 | 705 | 654 | 594 |
| 524 | 439 | 344 |
| Low | 650 | 630 | 605 | 575 | 540 | 508 | 450 |
| 383 | 285 | 158 |
| High | 1,270 | 1,210 | 1,150 | 1,085 | 1,015 | 946 | 862 |
| 769 | 645 | 502 |
F4FP030H06T2* | Med | 1,050 | 1,040 | 995 | 930 | 855 | 804 | 714 |
| 624 | 494 | 364 |
| Low | 855 | 820 | 780 | 735 | 680 | 624 | 550 |
| 447 | 333 | 190 |
| High | - | 1,310 | 1,250 | 1,175 | 1,120 | 1,053 | 983 |
| 894 | 779 | 645 |
F4FP036H06T2* | Med | 1,200 | 1,150 | 1,100 | 1,040 | 985 | 933 | 879 |
| 795 | 711 | 587 |
| Low | 1,060 | 1,015 | 970 | 925 | 860 | 809 | 740 |
| 661 | 572 | 453 |
| High | 1,270 | 1,210 | 1,150 | 1,085 | 1,015 | 946 | 802 |
| 769 | 645 | 502 |
F4FP040H06T2* | Med | 1,050 | 1,040 | 995 | 930 | 855 | 804 | 714 |
| 624 | 494 | 364 |
| Low | 855 | 820 | 780 | 735 | 680 | 624 | 550 |
| 447 | 333 | 190 |
| High | - | 1,575 | 1,500 | 1,420 | 1,350 | 1,273 | 1,192 |
| 1,102 | 996 | 871 |
F4FP042H06T2* | Med | 1,460 | 1,395 | 1,330 | 1,260 | 1,190 | 1,125 | 1,052 |
| 960 | 842 | 695 |
| Low | 1,250 | 1,200 | 1,155 | 1,100 | 1,050 | 1,001 | 931 |
| 851 | 751 | 631 |
| High | 1,575 | 1,535 | 1,475 | 1,390 | 1,310 | 1,245 | 1,147 |
| 1,030 | 897 | 735 |
F4FP045H06T2* | Med High | 1,375 | 1,315 | 1,255 | 1,185 | 1,110 | 1,040 | 944 |
| 848 | 732 | 606 |
Med Low | 1,210 | 1,160 | 1,110 | 1,050 | 980 | 921 | 844 |
| 737 | 640 | 533 | |
|
| |||||||||||
| Low | 1,035 | 990 | 940 | 890 | 825 | 770 | 698 |
| 616 | 524 | 432 |
| High | 2223 | 2158 | 2090 | 2029 | 1929 | 1861 | 1788 |
| 1679 | 1594 | 1501 |
| Med High | 1948 | 1904 | 1801 | 1815 | 1777 | 1741 | 1681 |
| 1618 | 1539 | 1453 |
F5FP048H06T2* | Med | 1741 | 1690 | 1649 | 1606 | 1564 | 1516 | 1476 |
| 1436 | 1387 | 1353 |
| Med Low | 1499 | 1454 | 1415 | 1370 | 1328 | 1269 | 1228 |
| 1191 | 1132 | 1093 |
| Low | 1286 | 1233 | 1177 | 1142 | 1092 | 1039 | 987 |
| 960 | 888 | 842 |
| High | 2195 | 2145 | 2070 | 2008 | 1920 | 1852 | 1754 |
| 1663 | 1570 | 1462 |
| Med High | 1938 | 1899 | 1873 | 1824 | 1791 | 1724 | 1679 |
| 1603 | 1521 | 1420 |
F5FP060H06T2* | Med | 1726 | 1681 | 1641 | 1607 | 1560 | 1517 | 1485 |
| 1433 | 1402 | 1349 |
| Med Low | 1525 | 1483 | 1441 | 1383 | 1356 | 1291 | 1253 |
| 1208 | 1169 | 1123 |
| Low | 1306 | 1254 | 1204 | 1160 | 1114 | 1061 | 1008 |
| 980 | 914 | 876 |
| High | 2,285 | 2,195 | 2,105 | 2,015 | 1,950 | 1,845 | 1,770 |
| 1,685 | 1,590 | 1,485 |
F4FV060H06T2* | Med. | 2,125 | 2,020 | 1,910 | 1,805 | 1,705 | 1,597 | 1,491 |
| 1,386 | 1,280 | 1,175 |
| Low | 1,655 | 1,605 | 1,550 | 1,500 | 1,450 | 1,398 | 1,326 |
| 1,245 | 1,153 | 1,052 |
|
|
|
|
|
|
|
|
|
|
|
|
|
NOTE: Air flow data shown above 0.50” W.C. external static pressure is for REFERENCE ONLY. Maximum allowable external static when electric heat is used is limited to 0.50” W.C. Maximum allowable external static pressure may also be limited by minimum CFM requirements for proper Heat Pump operation.
1. Includes Return Air Filter and Largest Electric Heater.
All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.
4 | Unitary Products Group |