York F*FV, F*FP Physical and Electrical Data, ELECTRICAL DATA - Cooling Only, YTG-B-0707

Models: F*FV F*FP

1 16
Download 16 pages 57.55 Kb
Page 7
Image 7

295421-YTG-B-0707

Physical and Electrical Data

MODEL

F4FP024H06T2*

F4FP030H06T2*

F4FP036H06T2*

F4FP040H06T2*

 

 

 

 

 

 

Blower - Diameter Width

10x6

10x8

10x8

10x8

 

 

 

 

 

 

 

 

Motor

 

HP

1/4

1/3

1/2

1/3

 

Nominal RPM

1075

1075

1075

1075

 

 

 

 

 

 

 

 

 

Voltage

 

 

208/230

 

 

 

 

 

 

 

 

 

 

AMPS

 

Full Load

1.6/1.4

2.5/2.2

3.3/2.9

2.5/2.2

 

Locked Rotor

3.3/2.9

6.2/5.5

7.4/6.5

6.2/5.5

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

Disposable/Permanent

 

Filter1

 

 

 

 

 

 

 

 

Size

16x20x1

16x20x1

20x20x1

20x20x1

 

 

Permanent Type Kit

1PF0601BK

1PF0601BK

1PF0602BK

1PF0601BK

 

 

 

 

 

 

 

Shipping/Operating Weight (lbs.)

98/93

105/100

115/109

121/115

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

F4FP042H06T2*

F4FP045H06T2*

F5FP048H06T2*

F5FP060H06T2*

F4FV060H06T2*

Blower - Diameter x Width

10x8

10x10

11x10

11x10

11x10

 

 

 

 

 

 

 

 

Motor

 

HP

3/4

1/3

1.0

1.0

1.0

 

 

 

 

 

 

 

 

Nominal RPM

1130

925

1050

1050

1200

 

 

Voltage

208/230

 

230

 

 

 

 

 

 

 

 

 

Amps

 

Full Load

4.4/3.8

3.0/2.7

7.6

7.6

7.8/7.0

 

 

 

 

 

 

 

 

Locked Rotor

11.9/10.3

4.8/4.1

 

 

 

 

Type

 

Disposable/Permanent

 

Filter1

 

 

 

 

 

 

 

 

Size

20x20x1

22x20x1

22x20x1

22x20x1

22x20x1

 

 

Permanent Type Kit

1PF0602BK

1PF0603BK

1PF0603BK

1PF0603BK

1PF0603BK

Shipping/Operating Weight (lbs.)

121/115

150/144

153/147

160/154

160/154

1.

Field Supplied.

 

 

 

 

 

ELECTRICAL DATA - Cooling Only

 

Total Motor Amps

Minimum Circuit

Max. O.C.P.1 Amps/

Minimum Wire

Models

ampacity

 

 

 

 

 

 

 

Type

Size A.W.G.

 

208V

240V

208V

 

240V

 

 

 

 

F4FP024H06T2*

1.6

1.5

2.0

 

1.8

15

14

 

 

 

 

 

 

 

 

F4FP030H06T2*

2.5

2.3

3.2

 

2.8

15

14

 

 

 

 

 

 

 

 

F4FP036H06T2*

3.3

3.0

4.2

 

3.7

15

14

 

 

 

 

 

 

 

 

F4FP040H06T2*

2.5

2.3

3.2

 

2.8

15

14

 

 

 

 

 

 

 

 

F4FP042H06T2*

4.4

4.0

5.5

 

4.8

15

14

 

 

 

 

 

 

 

 

F4FP045H06T2*

3.1

2.6

3.9

 

3.4

15

14

 

 

 

 

 

 

 

 

F5FP048H06T2*

7.6

7.6

9.5

 

9.5

15

14

 

 

 

 

 

 

 

 

F5FP060H06T2*

7.6

7.6

9.5

 

9.5

15

14

 

 

 

 

 

 

 

 

VARIABLE SPEED MODEL

 

 

 

 

 

 

 

F4FV060H06T2*

 

15

14

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay Fuse.

Unitary Products Group

7

Page 7
Image 7
York F*FV, F*FP Physical and Electrical Data, ELECTRICAL DATA - Cooling Only, YTG-B-0707, Unitary Products Group