York GHD, GHA, GFD, GNA Cooling Capacity - Coil Only, 036-21145-003Rev. A, Unitary Products Group

Models: GFA GUA GHD GNA GFD GHA

1 12
Download 12 pages 21.54 Kb
Page 3
Image 3

036-21145-003 Rev. A (0403)

COOLING CAPACITY - COIL ONLY*

Model Coil

Rated CFM

Entering Air °F

MBH@ Evaporator Temperature and Corresponding Pressure °F / PSIG

(Wet Bulb)

35 / 61.5

40 / 68.5

45 / 76.0

50 / 84.0

 

 

 

 

FULL-CASED “A” TYPE MULTI-POSITION

 

 

G2FD024(S,H)14(T)

 

72

36.3

33.0

29.5

25.6

850

67

33.4

30.2

26.7

23.1

G2FD024(S,H)17(T)

62

27.4

24.3

21.0

17.7

 

 

 

57

22.2

19.3

16.2

12.6

G2FD030(S,H)17(T)

 

72

41.5

37.8

33.7

29.5

1025

67

36.2

32.4

28.6

24.5

G2FD035(S,H)14(T)

62

29.1

25.3

24.0

19.2

 

 

 

57

24.1

21.5

18.7

15.8

 

 

72

52.0

47.3

42.3

37.3

G2FD036(S,H)17(T)

1250

67

41.7

36.8

32.3

27.4

62

32.5

27.3

29.8

22.2

 

 

 

 

57

27.9

25.8

23.8

22.2

 

 

72

53.4

48.6

43.4

38.3

G2FD036(S,H)21(T)

1200

67

42.8

37.8

33.1

28.2

62

33.4

28.1

30.6

22.8

 

 

 

 

57

28.7

26.5

24.5

22.8

G2FD046(S,H)17(T)

 

72

88.4

76.0

63.3

50.0

1400

67

70.8

59.4

48.4

37.0

G2FD042(S,H)21(T)

62

55.2

43.9

35.8

29.9

 

 

 

57

47.4

41.5

35.8

29.9

G2FD048(S,H)21(T)

 

72

100.5

86.4

72.0

56.8

1650

67

80.4

67.5

55.0

42.1

G2FD048(S,H)24(T)

62

62.7

49.9

40.7

34.0

 

 

 

57

53.9

47.2

40.7

34.0

 

 

72

119.9

101.0

80.0

62.2

G2FD060(S,H)24(T)

1825

67

96.0

79.2

62.6

45.8

62

74.8

58.6

46.2

37.0

 

 

 

 

57

64.3

55.4

46.2

37.0

 

 

72

124.8

105.2

85.3

64.7

G2FD061(S,H)24(T)

2000

67

99.9

82.5

65.2

47.7

62

77.9

61.1

48.1

38.6

 

 

 

 

57

66.9

57.7

48.1

38.6

*See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.

(T)indicates models with factory installed thermal expansion valve. Only available on coils with factory installed horizontal drain pan (H).

Notes:

G2FD coils available with a factory installed horizontal drain pan option (H).

G2FD061H24 is only available with a factory mounted horizontal pan.

COOLING CAPACITY - COIL ONLY*

 

RATED

ENTERING AIR

 

MBH @ EVAPORATOR TEMPERATURE AND

 

MODEL

°F

 

 

CORRESPONDING PRESSURE °F / PSIG

 

CFM

 

 

 

 

(WET BULB)

 

 

 

 

 

 

 

35/61.5

 

40/68.5

45/76.0

 

50/84.0

 

 

 

 

 

 

72

35.2

 

32.0

28.6

 

24.8

G1HA024H14(T)

800

67

32.4

 

29.3

25.9

 

22.4

62

26.6

 

23.6

20.4

 

17.2

 

 

 

 

 

 

57

21.5

 

18.7

15.7

 

12.2

 

 

72

49.1

 

44.7

39.9

 

35.2

G1HA036H14(T)

1150

67

39.4

 

34.8

30.5

 

25.9

62

30.7

 

25.9

28.2

 

22.8

 

 

 

 

 

 

57

26.4

 

24.4

22.5

 

21.0

 

 

72

73.4

 

63.1

52.5

 

41.5

G1HA036H17(T)

1200

67

58.8

 

49.3

40.2

 

30.7

62

45.8

 

36.4

29.7

 

24.8

 

 

 

 

 

 

57

39.3

 

34.4

28.1

 

23.2

 

 

72

94.4

 

81.2

67.6

 

53.4

G1HA048H21(T)

1550

67

75.6

 

65.4

51.7

 

39.5

62

59.0

 

46.9

38.2

 

32.0

 

 

 

 

 

 

57

50.6

 

44.4

35.6

 

29.7

 

 

72

112.8

 

95.0

77.0

 

58.4

G1HA060H24(T)

1800

67

90.3

 

74.5

58.8

 

43.1

62

70.3

 

55.1

43.4

 

34.9

 

 

 

 

 

 

57

60.4

 

52.1

40.4

 

31.9

*See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.

(T) indicates models with factory installed thermal expansion valve.

Unitary Products Group

3

Page 3
Image 3
York GHD, GHA, GFD, GNA, GUA, GFA specifications Cooling Capacity - Coil Only, 036-21145-003Rev. A, Unitary Products Group