York R407C manual Roomtop, 7 to 30 kW, Technical features, Compatibility table / Codes

Models: R407C

1 2
Download 2 pages 41.92 Kb
Page 2
Image 2
R407C

R407C

Roomtop

7 to 30 kW

Technical features

Cooling only models

 

 

RTC 07 K

RTC 10 K

RTC 15 K

 

RTC 20 K

RTC 25 K

RTC 30 K

 

 

 

 

 

 

 

 

 

 

 

Cooling capacities

 

kW

6.90

8.90

14.00

 

17.90

21.80

27.00

 

 

 

 

 

 

 

 

 

 

 

Power input in cooling

 

kW

2.95

4.04

6.80

 

8.95

10.10

13.00

In duct outdoor side sound power level

 

dB(A)

71

71

69

 

74

76

76

 

 

 

 

 

 

 

 

 

 

 

In duct indoor side sound power level

 

dB(A)

70

71

67

 

73

75

75

 

 

 

 

 

 

 

 

 

 

 

Heat pump models

 

 

RTH 07 K

RTH 10 K

RTH 15 K

 

RTH 20 K

RTH 25 K

RTH 30 K

 

 

 

 

 

 

 

 

 

 

 

Cooling capacities

 

kW

6.80

9.00

14.00

 

18.00

20.20

27.00

 

 

 

 

 

 

 

 

 

 

 

Power input in cooling

 

kW

3.09

4.09

6.80

 

9.00

10.00

12.30

 

 

 

 

 

 

 

 

 

 

 

Heating capacities

 

kW

7.00

10.40

14.50

 

18.00

20.20

27.50

 

 

 

 

 

 

 

 

 

 

 

Power input in heating

 

kW

2.92

4.35

5.29

 

6.20

7.51

11.20

In duct outdoor side sound power level

 

dB(A)

70

80

74

 

74

83

81

 

 

 

 

 

 

 

 

 

 

 

In duct indoor side sound power level

 

dB(A)

65

80

73

 

73

83

81

 

 

 

 

 

 

 

 

 

 

 

Common characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply

 

 

230V/1/50Hz

 

 

 

400V/3 + N/ 50Hz

 

 

 

 

 

 

 

 

 

 

 

 

Nominal / Starting current

 

A

17 / 72

10.1 / 45

13 / 62

 

15.4 / 79

18.7 / 77

21.8 / 80

 

 

 

 

 

 

 

 

 

 

 

Main switch (1)

 

A

25

20

25

 

25

25

32

 

 

 

 

 

 

 

 

 

 

 

Main cable (1)

 

Nbr. x mm2

3 x 4

5 x 2,5

5 x 4

 

5 x 4

5 x 4

5 x 6

Cable to standard thermostat (2)

 

Nbr. x mm2

 

 

 

10 x 0,22

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator fan at nominal airflow

 

Airflow

m3/h

1 970

2 430

4 000

 

4 485

5 000

5 850

 

 

 

 

 

 

 

 

 

 

 

Standard ESP

Pa

25

37

50

 

50

62

62

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Condenser fan at nominal airflow

 

Airflow

m3/h

2 380

3 450

4 350

 

5 255

5 200

6 400

 

 

 

 

 

 

 

 

 

 

 

Standard ESP

Pa

50

50

50

 

50

50

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

mm

478

555

555

 

585

640

640

Nett dimensions

 

 

 

 

 

 

 

 

 

 

 

Length

mm

1 100

1 150

1 310

 

1 570

1 750

1 750

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

mm

1 100

1 150

1 310

 

1 570

1 650

2 050

 

 

 

 

 

 

 

 

 

 

 

Nett weight

 

RTC

kg

154

180

214

 

275

345

405

 

 

 

 

 

 

 

 

 

 

 

Nett weight

 

RTH

kg

163

190

224

 

285

350

412

(1)For information only. These should be checked for compliance with local regulations depending also on installation and cable type

(2)Shield type cable only

All the data are at EUROVENT conditions with 230V/1/50Hz or 400V/3+N/50Hz.

Cooling : Entering indoor coil temp. 27ºC / 19ºC WB and outdoor temperature 35ºC

Heating : Entering indoor coil temp. 20ºC and outdoor temperature 7ºC / 6ºC WB

Compatibility table / Codes

Cooling only models

 

 

 

RTC 07 K

RTC 10 K

RTC 15 K

 

RTC 20 K

RTC 25 K

RTC 30 K

 

 

 

661210741

661211043

661211543

 

661212043

661212543

661213043

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat pump models

 

 

 

RTH 07 K

RTH 10 K

RTH 15 K

 

RTH 20 K

RTH 25 K

RTH 30 K

 

 

 

662050741

662051043

662051543

 

662052053

662052543

662053043

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat

 

 

 

 

 

 

 

 

 

 

Delivered as standard with the unit

 

 

 

 

DPC-1

 

 

 

Accessories or options

Remarks

Code

 

 

 

 

 

 

 

 

 

 

5 kW / 1ph.

611760561

 

l

 

 

 

 

 

 

 

 

5 kW / 3ph.

611760573

 

l

l

 

 

 

 

 

Electrical Heaters *

 

10 kW / 3ph.

611761033

A

l

l

 

 

 

 

 

(in duct)

 

5 kW / 3ph.

611760653

 

 

l

 

l

l

l

 

 

 

 

 

 

 

10 kW / 3ph.

611761083

 

 

 

l

 

l

l

l

 

 

15 kW / 3ph.

611761513

 

 

 

l

 

l

l

l

Low ambient regulation

 

613111531

O

l

l

l

 

 

 

 

 

613113085 *

 

 

 

 

l

l

l

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Copper-copper coils unit

 

 

O

l

l

l

 

l

l

l

Anti-corrosion blue fin coil

 

 

O

l

l

l

 

l

l

l

A = Accessory (supplied loose)

O = Option (factory fitted)

O/A = If you want this item factory fitted, precise it in the order form.

* Not protected against external conditions.

E-COM-R0701

Page 2
Image 2
York R407C manual Roomtop, 7 to 30 kW, Technical features, Compatibility table / Codes