CFM, STATIC PRESSURE, AND POWER - ALTITUDE AND TEMPERATURE CORRECTIONS

The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level.

The air flow rates listed in the standard blower performance tables are based on standard air at sea level. As the altitude or temperature increases, the density of air decreases. In order to

TABLE 10: ALTITUDE CORRECTION FACTORS

use the indoor blower tables for high altitude applications, certain corrections are necessary.

A centrifugal fan is a "constant volume" device. This means that, if the rpm remains constant, the CFM delivered is the same regardless of the density of the air. However, since the air at high altitude is less dense, less static pressure will be generated and less power will be required than a similar application at sea level. Air density correction factors are shown in Table 10 and Figure 11.

AIR TEMP

 

 

 

 

ALTITUDE (FEET)

 

 

 

 

 

0

1000

2000

3000

4000

5000

6000

7000

8000

9000

10000

 

40

1.060

1.022

0.986

0.950

0.916

0.882

0.849

0.818

0.788

0.758

0.729

50

1.039

1.002

0.966

0.931

0.898

0.864

0.832

0.802

0.772

0.743

0.715

60

1.019

0.982

0.948

0.913

0.880

0.848

0.816

0.787

0.757

0.729

0.701

70

1.000

0.964

0.930

0.896

0.864

0.832

0.801

0.772

0.743

0.715

0.688

80

0.982

0.947

0.913

0.880

0.848

0.817

0.787

0.758

0.730

0.702

0.676

90

0.964

0.929

0.897

0.864

0.833

0.802

0.772

0.744

0.716

0.689

0.663

100

0.946

0.912

0.880

0.848

0.817

0.787

0.758

0.730

0.703

0.676

0.651

The examples below will assist in determining the airflow performance of the product at altitude.

Example 1: What are the corrected CFM, static pressure, and BHP at an elevation of 5,000 ft. if the blower performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP?

Solution: At an elevation of 5,000 ft the indoor blower will still deliver 6,000 CFM if the rpm is unchanged. However, Table 10 must be used to determine the static pressure and BHP. Since no temperature data is given, we will assume an air temperature of 70°F. Table 10 shows the correction factor to be 0.832.

Corrected static pressure = 1.5 x 0.832 = 1.248 IWC

Corrected BHP = 4.0 x 0.832 = 3.328

Example 2: A system, located at 5,000 feet of elevation, is to deliver 6,000 CFM at a static pressure of 1.5". Use the unit

blower tables to select the blower speed and the BHP requirement.

Solution: As in the example above, no temperature information is given so 70°F is assumed.

The 1.5" static pressure given is at an elevation of 5,000 ft. The first step is to convert this static pressure to equivalent sea level conditions.

Sea level static pressure = 1.5 / .832 = 1.80"

Enter the blower table at 6000 sCFM and static pressure of 1.8". The rpm listed will be the same rpm needed at 5,000 ft.

Suppose that the corresponding BHP listed in the table is 3.2. This value must be corrected for elevation.

BHP at 5,000 ft = 3.2 x .832 = 2.66

24

Unitary Products Group

Page 24
Image 24
York WR 180 warranty Altitude Correction Factors, AIR Temp Altitude Feet

WR 180 specifications

The York WR 180 is a state-of-the-art water-cooled chiller, renowned for its efficiency, flexibility, and reliability in various applications. Designed specifically for commercial and industrial use, the WR 180 stands out as an ideal solution for facilities requiring effective climate control, such as hotels, hospitals, shopping malls, and large office buildings.

One of the primary features of the York WR 180 is its advanced chiller design, which incorporates variable speed technology. This allows the unit to adjust its cooling capacity based on the actual load demands of the building, leading to significant energy savings. By operating at variable speeds instead of a fixed rate, the chiller minimizes energy consumption during lower demand periods while maintaining optimal performance during peak loads.

The WR 180 also employs a reliable and efficient centrifugal compressor, which contributes to its high energy efficiency ratio (EER). This compressor is designed to provide robust cooling while operating quietly, making it suitable for environments where noise reduction is essential. Additionally, the unit features a microprocessor-based control system that offers sophisticated monitoring and control capabilities, allowing operators to fine-tune performance and enhance reliability.

Another notable characteristic of the York WR 180 is its environmentally friendly refrigerant options. The chiller can operate with refrigerants that have a low global warming potential (GWP), aligning with international regulations and environmental sustainability goals. This commitment to eco-friendly designs not only helps reduce the carbon footprint but also ensures compliance with industry standards.

In terms of installation and maintenance, the WR 180 is designed for user-friendliness. Its modular design simplifies transport and installation in various spaces, while easy-access components facilitate routine maintenance. The chiller also offers various connectivity options, enabling integration with building management systems for real-time monitoring and control.

Overall, the York WR 180 combines innovative design, cutting-edge technology, and eco-friendly practices, making it a top choice for industries seeking efficient and sustainable cooling solutions. Its impressive features, coupled with strong operational flexibility, position the WR 180 as a leader in the chiller market.