TABLE 4: COOLING CAPACITIES FOR WR180 (CONTINUED)
Air on Evaporator Coil |
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
| |||||||
|
|
| 115°F |
|
|
|
|
|
| 125°F |
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| WB | Total | Total2 |
| Sensible Capacity (MBH)* |
| Total | Total2 |
| Sensible Capacity (MBH)* |
| |||||||
CFM | Cap.1 | Input |
| Return Dry Bulb (°F) |
| Cap.1 | Input |
| Return Dry Bulb (°F) |
| ||||||||
| (°F) | (MBH) | (kW) |
|
|
|
|
|
| (MBH) | (kW) |
|
|
|
|
|
| |
| 90 | 85 | 80 | 75 | 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
| |||||||||||||||||
| 77 | 187 | 15.8 | 73 | 66 | 50 | 34 | 17 | - | 179 | 17.3 | 74 | 60 | 47 | 30 | 13 | - | |
3750 | 72 | 172 | 15.6 | 110 | 93 | 77 | 61 | 44 | 28 | 165 | 17.1 | 108 | 91 | 74 | 57 | 40 | 23 | |
67 | 157 | 15.4 | 146 | 120 | 104 | 88 | 71 | 55 | 151 | 16.9 | 142 | 118 | 101 | 84 | 67 | 50 | ||
| ||||||||||||||||||
| 62 | 147 | 15.2 | 147 | 147 | 121 | 104 | 88 | 72 | 143 | 16.7 | 145 | 143 | 117 | 100 | 83 | 66 | |
| 77 | 193 | 15.9 | 92 | 74 | 55 | 36 | 18 | - | 184 | 17.3 | 92 | 70 | 51 | 32 | 13 | - | |
4500 | 72 | 177 | 15.7 | 122 | 103 | 84 | 66 | 47 | 29 | 169 | 17.1 | 119 | 100 | 81 | 62 | 43 | 24 | |
67 | 162 | 15.5 | 151 | 133 | 114 | 95 | 77 | 58 | 155 | 16.9 | 146 | 130 | 111 | 92 | 73 | 54 | ||
| 62 | 152 | 15.2 | 151 | 151 | 133 | 114 | 96 | 77 | 147 | 16.7 | 147 | 146 | 128 | 109 | 90 | 71 | |
| 57 | 151 | 15.2 | 151 | 151 | 136 | 117 | 99 | 80 | 146 | 16.6 | 146 | 146 | 130 | 111 | 92 | 73 | |
| 77 | 198 | 15.9 | 111 | 81 | 60 | 39 | 18 | - | 188 | 17.4 | 111 | 80 | 56 | 35 | 14 | - | |
5250 | 72 | 183 | 15.7 | 133 | 113 | 92 | 71 | 51 | 30 | 173 | 17.2 | 130 | 109 | 88 | 67 | 46 | 25 | |
67 | 167 | 15.5 | 156 | 145 | 124 | 103 | 83 | 62 | 159 | 17.0 | 150 | 142 | 121 | 100 | 79 | 58 | ||
| 62 | 156 | 15.3 | 156 | 156 | 144 | 124 | 103 | 82 | 151 | 16.8 | 149 | 149 | 139 | 118 | 97 | 76 | |
| 57 | 156 | 15.2 | 156 | 156 | 148 | 127 | 106 | 86 | 150 | 16.7 | 150 | 150 | 141 | 120 | 99 | 78 | |
| 77 | 204 | 16.0 | 130 | 88 | 65 | 42 | 19 | - | 193 | 17.4 | 130 | 90 | 60 | 37 | 14 | - | |
6000 | 72 | 188 | 15.8 | 145 | 122 | 99 | 77 | 54 | 31 | 177 | 17.2 | 142 | 118 | 95 | 72 | 49 | 26 | |
67 | 172 | 15.6 | 160 | 157 | 134 | 111 | 88 | 66 | 162 | 17.0 | 153 | 147 | 131 | 108 | 84 | 61 | ||
| 62 | 161 | 15.4 | 160 | 160 | 156 | 133 | 110 | 87 | 154 | 16.8 | 153 | 153 | 151 | 127 | 104 | 81 | |
| 57 | 160 | 15.3 | 160 | 160 | 160 | 137 | 114 | 91 | 154 | 16.7 | 154 | 154 | 153 | 130 | 107 | 84 | |
| 72 | 193 | 15.8 | 156 | 131 | 106 | 82 | 57 | 32 | 182 | 17.2 | 151 | 127 | 102 | 77 | 52 | 28 | |
6750 | 67 | 176 | 15.6 | 165 | 163 | 144 | 119 | 94 | 69 | 166 | 17.0 | 157 | 154 | 139 | 115 | 90 | 65 | |
62 | 165 | 15.4 | 165 | 165 | 163 | 138 | 113 | 89 | 158 | 16.8 | 157 | 157 | 156 | 131 | 107 | 82 | ||
| ||||||||||||||||||
| 57 | 165 | 15.3 | 165 | 165 | 164 | 140 | 115 | 90 | 157 | 16.7 | 157 | 157 | 157 | 133 | 107 | 83 | |
| 72 | 198 | 15.8 | 167 | 140 | 113 | 87 | 60 | 34 | 186 | 17.1 | 161 | 135 | 108 | 82 | 55 | 29 | |
7500 | 67 | 181 | 15.6 | 169 | 169 | 153 | 126 | 100 | 73 | 170 | 16.9 | 161 | 161 | 148 | 122 | 95 | 69 | |
62 | 169 | 15.3 | 169 | 169 | 169 | 143 | 116 | 90 | 162 | 16.7 | 161 | 161 | 161 | 135 | 109 | 82 | ||
| ||||||||||||||||||
| 57 | 169 | 15.2 | 169 | 169 | 169 | 143 | 116 | 89 | 161 | 16.6 | 161 | 161 | 161 | 136 | 108 | 82 |
1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity
Unitary Products Group | 13 |