York YCJD18 THRU 60 warranty Cooling Performance Data, Air Conditioner Model No

Models: YCJD18 THRU 60

1 28
Download 28 pages 61.07 Kb
Page 24
Image 24
Manual background

840569-YTG-A-0612

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

YCJD42S41S2(H)(E)

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR COIL MODEL NO.

FC/MC/PC43

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDENSING

IDCFM

 

 

1200

 

 

 

 

1400

 

 

 

 

1600

 

 

ENTERING AIR

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

 

T.C.

41.8

43.9

43.7

47.2

49.9

43.3

45.0

44.7

47.9

50.9

44.7

46.0

45.7

48.5

51.9

65

S.C.

41.6

36.4

30.9

29.8

23.8

43.0

38.5

32.5

31.0

24.2

44.3

40.7

34.0

32.2

24.5

 

KW

2.79

2.81

2.82

2.82

2.85

2.80

2.82

2.82

2.83

2.85

2.80

2.83

2.82

2.84

2.86

 

T.C.

39.8

41.2

41.3

45.1

48.2

41.4

42.3

42.2

45.7

49.0

42.9

43.3

43.2

46.4

49.8

75

S.C.

39.5

35.2

29.8

29.1

23.1

41.0

37.4

31.6

30.6

23.8

42.5

39.7

33.5

32.1

24.5

 

KW

3.08

3.10

3.10

3.13

3.17

3.10

3.11

3.11

3.14

3.18

3.12

3.13

3.12

3.15

3.19

 

T.C.

37.8

38.6

38.8

43.0

46.5

39.4

39.6

39.7

43.6

47.1

41.0

40.6

40.7

44.3

47.7

85

S.C.

37.5

34.1

28.7

28.4

22.4

39.1

36.4

30.8

30.2

23.4

40.7

38.7

32.9

32.0

24.5

 

KW

3.38

3.39

3.39

3.44

3.50

3.41

3.41

3.41

3.46

3.51

3.43

3.42

3.42

3.47

3.52

 

T.C.

35.8

35.9

36.3

40.9

44.8

37.5

36.9

37.3

41.5

45.2

39.2

37.9

38.2

42.1

45.6

95

S.C.

35.4

33.0

27.6

27.7

21.7

37.1

35.3

30.0

29.8

23.0

38.8

37.6

32.3

31.9

24.4

 

KW

3.67

3.68

3.68

3.76

3.82

3.71

3.70

3.70

3.77

3.83

3.75

3.72

3.72

3.79

3.84

 

T.C.

33.1

33.1

32.6

37.0

41.6

34.7

34.2

33.5

37.6

42.0

36.3

35.4

34.4

38.2

42.4

105

S.C.

32.7

31.0

26.3

26.4

20.7

34.3

33.1

28.4

28.6

22.1

35.9

35.2

30.5

30.8

23.5

 

KW

3.98

3.98

3.96

4.05

4.14

4.02

4.01

3.98

4.07

4.16

4.06

4.05

4.01

4.09

4.18

 

T.C.

30.5

30.2

28.9

33.3

38.4

32.0

31.6

29.8

33.8

38.8

33.4

33.0

30.8

34.4

39.3

115

S.C.

30.2

29.1

25.0

25.1

19.8

31.6

30.9

26.8

27.4

21.3

33.1

32.7

28.7

29.6

22.7

 

KW

4.27

4.27

4.22

4.33

4.45

4.32

4.31

4.26

4.36

4.48

4.37

4.36

4.29

4.39

4.51

 

T.C.

27.9

27.4

25.2

29.5

35.2

29.2

29.0

26.2

30.0

35.7

30.6

30.5

27.1

30.5

36.2

125

S.C.

27.6

27.3

23.7

23.8

18.9

28.9

28.8

25.3

26.2

20.4

30.3

30.3

26.9

28.5

21.8

 

KW

4.57

4.56

4.49

4.62

4.77

4.62

4.62

4.53

4.65

4.80

4.67

4.67

4.57

4.68

4.84

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

Air Handlers

Coils

T.C.

S.C.

KW

FC/MC/PC43

1.00

1.00

1.00

FC/MC/PC48

1.01

1.01

1.01

FC/MC/PC60

1.00

0.99

1.00

FC/MC62

1.01

1.02

1.01

FC64

1.01

1.03

0.99

UC48

1.01

1.01

1.01

AHE42D

1.01

1.03

0.93

AHE48D

1.01

1.02

0.93

AHE60D

1.01

1.04

0.93

AHP42

1.01

1.03

1.01

AHP48

1.01

1.01

0.99

AHP60

1.01

1.01

0.95

AHR42C

1.01

1.03

1.01

AHR48D

0.99

0.97

0.99

AHR60D

1.01

1.01

1.01

AHX42

1.01

1.02

0.93

AHX48

1.01

1.03

0.93

AHX60

1.01

1.05

0.93

AV*48

1.01

1.02

0.93

AV*60

1.01

1.02

0.93

F6FP042

1.01

1.04

0.95

F6FP048

1.01

1.01

0.95

F6FP060

1.01

1.05

0.95

MV16C

FC/MC43C

1.01

1.01

0.93

MV16C

FC/MC48C

1.01

1.02

0.95

MV16C

FC60C

1.01

1.01

0.97

MV20D

FC/MC48D

1.01

1.04

0.93

MV20D

FC/MC60D

1.01

1.01

0.95

MV20D

FC/MC62D

1.01

1.03

0.93

MV20D

FC64D

1.01

1.03

0.91

MX16C

FC/MC43C

1.01

1.01

0.93

MX16C

FC/MC48C

1.01

1.01

0.93

MX16C

FC60C

1.01

1.01

0.93

MX20D

FC/MC48D

1.01

1.01

0.93

MX20D

FC/MC60D

1.01

1.03

0.93

MX20D

FC/MC62D

1.01

1.06

0.91

MX20D

FC64D

1.01

1.06

0.89

Furnaces

Coils

T.C.

S.C.

KW

T*(8,L)V*B12

FC/MC/PC43B

0.99

0.97

0.97

T*(8,L)V*C16

FC/MC/PC43C

1.01

1.01

0.97

T*(8,L)V*C16

FC/MC/PC48C

1.01

1.00

0.97

T*(8,L)V*C16

FC/MC/PC48D

1.01

1.00

0.97

T*(8,L)V*C16

FC/MC/PC60D

1.01

1.01

0.97

T*(8,L)V*C16

FC/MC62D

1.01

1.03

0.97

T*(8,L)V*C16

FC/PC60C

1.01

1.01

0.97

T*(8,L)V*C16

FC64D

1.01

1.03

0.93

T*(8,L)V*C16

UC48C

1.01

1.01

0.97

T*(8,L)V*C16

UC60C

1.01

1.01

0.97

T*(8,L)V*C20

FC/MC/PC43C

1.01

1.03

0.99

T*(8,L)V*C20

FC/MC/PC48C

1.01

1.01

0.97

T*(8,L)V*C20

FC/MC/PC48D

1.01

1.01

0.97

T*(8,L)V*C20

FC/MC/PC60D

1.01

1.01

0.95

T*(8,L)V*C20

FC/MC62D

1.01

1.03

0.95

Continued on next page.

24

Johnson Controls Unitary Products

Page 24
Image 24
York YCJD18 THRU 60 warranty Cooling Performance Data, Air Conditioner Model No