York YCJD18 THRU 60 YTG-A-0612, Outdoor Unit, Required Orifice or TXV 1,2, Indoor Unit 3,4,5

Models: YCJD18 THRU 60

1 28
Download 28 pages 61.07 Kb
Page 4
Image 4
FOOTNOTES:

840569-YTG-A-0612

System Charge for Various Matched Systems (Continued)

Outdoor Unit

YCJD18

YCJD24

YCJD30

YCJD36

YCJD42

YCJD48

YCJD60

S41S1(H)(E)

S41S1(H)(E)

S41S1(H)(E)

S41S1(H)(E)

S41S2(H)(E)

S41S1(H)(E)

S41S1(E)

 

 

 

 

 

 

 

 

 

Required Orifice or TXV 1,2

0.048/4F1

0.055/4F1

0.061/4F1

0.065/4G1

0.073/4G1

0.073/4H1

0.087/4J1

 

 

 

 

 

 

Indoor Unit 3,4,5

 

 

Additional Charge, oz.

 

 

FC/MC/PC43

4

2

0

0

 

 

 

 

 

 

 

 

FC/MC/PC48

8

10

4

 

 

 

 

 

 

 

 

FC/MC/PC60

9

0

0

 

 

 

 

 

 

 

 

FC/MC62

14

4

 

 

 

 

 

 

 

 

FC64

23

11

 

 

 

 

 

 

 

 

UC18

0

 

 

 

 

 

 

 

 

UC36

0

 

 

 

 

 

 

 

 

UC48

8

4

4

 

 

 

 

 

 

 

 

UC60

9

0

0

Some of the combinations shown in the above System Charge table require Advanced Main Air Circulating Fan indoor product. For approved coil only matches, please see the “COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils” table.

FOOTNOTES:

1.For applications requiring a TXV use S1-1TVM*** series kit.

2.Approved orifice(s) shipped with outdoor unit.

3.Systems matched with furnaces or air handlers not equipped with blower-off delays may require blower Time Delay Kit S1-2FD06700224.

4.PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.

5.Refer to Cooling Performance Data tables for actual system performance for specified system matches.

PROCEDURES:

1.Unit factory charge listed on the unit nameplate includes refrigerant for the outdoor unit, the smallest matched indoor unit, and 15 feet of interconnecting line tubing.

2.Verify the TXV or orifice and additional charge required for specific matched indoor unit in the system using the above table.

3.Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.

4.For indoor matches requiring additional charge, the refrigerant needs to be weighed in for specific matched indoor unit and lineset length.

5.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + charge adder for matched indoor unit + charge adder for line set.

Models 12-48 require Hard Start Kits for TXV matches. Models with “H” on the end of the model number have factory installed Hard Start Kits. For models without an “H” refer to the Hard Start Kit Accessory Installation Manual for the Hard Start Kit part number for each model.

4

Johnson Controls Unitary Products

Page 4
Image 4
York YCJD18 THRU 60 YTG-A-0612, Outdoor Unit, Required Orifice or TXV 1,2, Indoor Unit 3,4,5, Additional Charge, oz