COOLING CAPACITY - YCJF48S41S1 With Variable Speed Furnaces (Continued)
VARIABLE SPEED | COIL |
|
|
| COOLING |
|
|
FURNACE MODEL | MODEL1 | W | RATED | Net MBH | SEER | EER | |
| CFM | TOTAL | SENS. | ||||
|
|
|
|
| |||
| 14.5 SEER AC WITH VARIABLE SPEED FURNACES2 |
|
|
| |||
G*9V*C20 | FC/PC60C | 21 | 1655 | 47.0 | 33.0 | 14.75 | 12.50 |
G*9V*D20 | FC/MC/PC60D | 24 | 1615 | 47.0 | 33.0 | 14.75 | 12.50 |
G*9V*C20 | FC/MC62D | 21 | 1655 | 47.0 | 33.2 | 14.75 | 12.50 |
G*9V*D20 | FC/MC62D | 24 | 1630 | 47.0 | 33.4 | 15.00 | 12.75 |
G*9V*D20 | HC60 | 24 | 1615 | 45.0 | 32.4 | 14.50 | 12.00 |
G*9V*C16 | HD48 | 21 | 1590 | 46.5 | 32.4 | 14.50 | 12.25 |
G*9V*C20 | HD48 | 21 | 1655 | 46.5 | 32.4 | 14.50 | 12.25 |
G*9V*D20 | HD48 | 24 | 1645 | 46.5 | 32.6 | 14.50 | 12.25 |
G*9V*C16 | HD60 | 21 | 1590 | 47.0 | 33.4 | 14.75 | 12.50 |
G*9V*C20 | HD60 | 21 | 1655 | 47.0 | 33.4 | 14.75 | 12.50 |
G*9V*D20 | HD60 | 24 | 1615 | 47.0 | 33.4 | 14.75 | 12.50 |
1.MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2.Variable speed furnaces have B.O.D (Blower on Delay) standard.
COOLING CAPACITY - YCJF60S41S1 With Variable Speed Furnaces
VARIABLE SPEED | COIL |
|
|
| COOLING |
|
|
FURNACE MODEL | MODEL1 | W | RATED | Net MBH | SEER | EER | |
| CFM | TOTAL | SENS. | ||||
|
|
|
|
| |||
| 14.5 SEER AC WITH VARIABLE SPEED FURNACES2 |
|
|
| |||
P(C,V)9*D20 | HC60D | 24 | 1600 | 53.5 | 36.4 | 13.50 | 11.75 |
PV8*C20 | HD60 | 21 | 1750 | 56.5 | 39.0 | 13.75 | 12.00 |
P(C,V)9*C20 | HD60 | 21 | 1650 | 56.5 | 39.0 | 14.00 | 12.25 |
P(C,V)9*D20 | HD60 | 24 | 1600 | 56.0 | 37.8 | 14.25 | 12.25 |
PV8*C20 | FC/MC62D | 21 | 1750 | 57.0 | 39.5 | 14.25 | 12.25 |
P(C,V)9*C20 | FC/MC62D | 21 | 1650 | 56.0 | 38.0 | 13.75 | 12.00 |
P(C,V)9*D20 | FC/MC62D | 24 | 1600 | 56.0 | 37.8 | 14.00 | 12.25 |
Y*(8,L)C*C20 | FC/MC62D | 21 | 1615 | 56.5 | 37.6 | 14.60 | 12.60 |
Y*9C*C20 | FC/MC62D | 21 | 1655 | 56.0 | 37.2 | 14.10 | 12.20 |
Y*9C*D20 | FC/MC62D | 24 | 1630 | 56.5 | 37.6 | 14.25 | 12.25 |
Y*9C*D20 | HC60 | 24 | 1615 | 54.5 | 35.8 | 14.00 | 12.00 |
Y*(8,L)C*C20 | HD60 | 21 | 1605 | 56.5 | 38.0 | 14.50 | 12.50 |
Y*9C*C20 | HD60 | 21 | 1655 | 57.0 | 38.0 | 14.25 | 12.25 |
Y*9C*D20 | HD60 | 24 | 1615 | 56.5 | 37.2 | 14.25 | 12.25 |
G*9V*C20 | FC/MC62D | 21 | 1655 | 56.0 | 37.2 | 14.10 | 12.20 |
G*9V*D20 | FC/MC62D | 24 | 1630 | 56.5 | 37.6 | 14.25 | 12.25 |
G*9V*D20 | HC60 | 24 | 1615 | 54.5 | 35.8 | 14.00 | 12.00 |
G*9V*C20 | HD60 | 21 | 1655 | 57.0 | 38.0 | 14.25 | 12.25 |
G*9V*D20 | HD60 | 24 | 1615 | 56.5 | 37.2 | 14.25 | 12.25 |
1.MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2.Variable speed furnaces have B.O.D (Blower on Delay) standard.
18 | Johnson Controls Unitary Products |