413437-YTG-C-0908

COOLING CAPACITY - With Air Handler Coils (Continued)

UNIT

AIR HANDLER

COIL

 

 

COOLING

 

 

 

 

 

RATED

NET MBH

 

 

MODEL

MODEL

 

W

MODEL1

SEER

EER

 

CFM

 

 

 

TOTAL

SENS.

 

 

 

 

 

 

 

 

14.5

SEER AC WITH MV - VARIABLE SPEED (Contimued)

 

 

 

 

MV16C

 

21

FC/MC43C

1400

41.0

30.8

15.00

12.75

 

MV16C

 

21

FC/MC48C

1400

41.5

31.2

15.50

13.00

YCJF42S41S1

MV20D

 

24

FC/MC48D

1400

42.0

31.4

15.50

13.00

 

MV20D

 

24

FC/MC60D

1400

41.5

31.4

15.50

13.00

 

MV20D

 

24

FC/MC62D

1400

42.0

31.4

15.75

13.00

 

MV16C

 

21

FC/MC48C

1600

47.0

33.0

15.25

12.75

YCJF48S41S1

MV20D

 

24

FC/MC48D

1600

47.0

33.0

15.25

12.75

MV20D

 

24

FC/MC60D

1600

47.0

33.0

15.25

12.75

 

 

 

MV20D

 

24

FC/MC62D

1600

47.5

33.2

15.25

12.75

YCJF60S41S1

MV20D

 

24

FC/MC60D

1800

55.0

39.0

14.00

11.95

MV20D

 

24

FC/MC62D

1800

57.0

39.5

14.50

12.25

 

 

 

 

14.5

SEER AC

WITH AV / SV / F*FV

- VARIABLE

SPEED

 

 

 

YCJF24S41S1

AV24

 

17

-

750

25.0

17.5

15.75

13.25

AV36

 

21

-

750

25.8

18.2

16.50

13.75

 

 

YCJF30S41S1

AV36

 

21

-

1000

30.4

22.4

16.25

13.50

 

AV36

 

21

-

1250

36.2

27.4

15.75

13.25

YCJF36S41S1

AV/SV48

 

24

-

1200

34.4

25.4

15.25

13.00

 

F4FV060

 

24

-

1200

34.6

25.6

15.50

13.25

 

AV/SV48

 

24

-

1400

40.0

29.4

14.75

12.50

YCJF42S41S1

AV/SV60

 

24

-

1400

40.0

29.4

14.75

12.50

 

F4FV060

 

24

-

1350

40.0

29.6

15.00

12.50

 

AV/SV48

 

24

-

1600

44.5

30.8

14.25

12.00

YCJF48S41S1

AV/SV60

 

24

-

1650

44.0

30.6

14.25

12.00

 

F4FV060

 

24

-

1600

44.5

30.6

14.25

12.00

YCJF60S41S1

AV/SV60

 

24

-

1750

55.0

39.0

14.00

12.00

 

 

 

14.5 SEER AC WITH AHP / SHP / F*FP

 

 

 

 

YCJF24S41S1

AHP24

 

17

-

850

24.8

17.4

14.30

12.20

F4FP030

 

17

-

800

24.8

17.2

14.30

12.20

 

 

YCJF30S41S1

AHP36

 

21

-

1000

29.6

21.4

14.30

12.20

 

AHP36

 

21

-

1200

35.4

26.2

15.00

12.50

 

F4FP036

 

21

-

1200

34.2

25.2

14.00

12.00

YCJF36S41S1

F4FP040

 

21

-

1200

34.4

25.0

14.00

12.00

F4FP042

 

21

-

1200

34.4

25.0

14.00

12.00

 

 

 

F5FP048

 

24

-

1250

36.4

27.4

16.25

13.50

 

F5FP060

 

24

-

1250

34.8

26.0

15.25

13.00

YCJF42S41S1

F5FP048

 

24

-

1450

42.0

32.0

15.50

13.00

F5FP060

 

24

-

1500

40.0

29.8

14.75

12.50

 

 

 

AHP/SHP60

 

24

-

1600

44.0

30.6

14.20

12.00

YCJF48S41S1

F5FP048

 

24

-

1700

47.5

34.0

15.00

12.75

 

F5FP060

 

24

-

1700

44.5

31.2

14.00

12.00

Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.

EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.

1.MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.

— = Not applicable.

6

Johnson Controls Unitary Products

Page 6
Image 6
York YCJF24 warranty Speed, Seer AC with AHP / SHP / F*FP