Physical and Electrical Data
MODEL |
| YMA02411 | YMA03011 | YMA03611 | YMA04211 | YMA04811 | YMA06011 | |
|
|
|
|
|
|
|
| |
Unit Supply Voltage |
|
|
|
|
| |||
|
|
|
|
|
|
| ||
Normal Voltage Range 1 |
|
|
| 187 to 252 |
|
| ||
Minimum Circuit Ampacity | 14.3 | 18.1 | 21.9 | 32.6 | 34.7 | 39.0 | ||
|
|
|
|
|
|
| ||
Max. Overcurrent Device Amps 2 | 25 | 30 | 35 | 50 | 60 | 60 | ||
Compressor Type |
| Recip | Recip | Recip | Scroll | Scroll | Scroll | |
|
|
|
|
|
|
|
| |
Compressor Amps | Rated Load | 11.1 | 13.3 | 16.4 | 24.9 | 26.6 | 30 | |
|
|
|
|
|
|
| ||
Locked Rotor | 60 | 68 | 78 | 115 | 150 | 150 | ||
| ||||||||
|
|
|
|
|
|
|
| |
Crankcase Heater |
| Yes | Yes | Yes | No | No | No | |
|
|
|
|
|
|
|
| |
Fan Motor Amps | Rated Load | 0.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | |
|
|
|
|
|
|
|
| |
Fan Diameter Inches |
| 22 | 22 | 22 | 22 | 22 | 22 | |
|
|
|
|
|
|
|
| |
| Rated HP | 1/15 | 1/4 | 1/4 | 1/4 | 1/4 | 1/4 | |
Fan Motor |
|
|
|
|
|
|
| |
Nominal RPM | 850 | 850 | 850 | 850 | 850 | 850 | ||
|
|
|
|
|
|
|
| |
| Nominal CFM | 2,300 | 3,500 | 3,500 | 3,850 | 3,500 | 3,300 | |
|
|
|
|
|
|
|
| |
| Face Area (Sq. Ft.) | 14.86 | 17.15 | 20.58 | 20.58 | 20.58 | 20.58 | |
Coil |
|
|
|
|
|
|
| |
Rows Deep | 1 | 1 | 1 | 1 | 1 | 2 | ||
|
|
|
|
|
|
|
| |
| Fins / Inch | 22 | 22 | 22 | 22 | 22 | 22 | |
|
|
|
|
|
|
|
| |
Liquid Line Set OD (Field Installed) | 3/8 | 3/8 | 3/8 | 3/8 | 3/8 | 3/8 | ||
|
|
|
|
|
|
| ||
Vapor Line Set OD (Field Installed) | 3/4 | 3/4 | 7/8 | 7/8 | 7/8 | |||
|
|
|
|
|
|
| ||
Unit Charge (Lbs. - Oz.) 3 | 7 - 2 | 7 - 12 | 8 - 6 | 8 - 12 | 9 - 1 | 14 - 2 | ||
Charge Per Foot (Oz.) |
| 0.68 | 0.68 | 0.70 | 0.70 | 0.70 | 0.78 | |
|
|
|
|
|
|
|
| |
Operating Weight (Lbs.) |
| 175 | 220 | 225 | 225 | 245 | 285 | |
|
|
|
|
|
|
|
|
1Rated in accordance with ARI Standard 110, utilization range “A”.
2Dual element fuses or HACR circuit breaker.
3The Unit Charge is correct for the outdoor unit, matched indoor coil, and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
|
|
| DIMENSIONS |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
| Unit |
| Dimensions |
| Refrigerant | |||
|
|
|
|
| Connection | |||||
|
|
| Model |
|
| (Inches) |
| |||
|
|
|
|
|
| Service Valve Size | ||||
|
|
|
|
|
|
|
|
| ||
| A |
|
|
|
|
|
|
|
|
|
|
|
| A |
| B |
| C | Liquid | Vapor | |
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| 024 |
| 37 |
| 31 |
| 3/4” | |
|
|
| 030 |
| 37 |
| 31 |
| ||
|
|
|
|
|
|
| ||||
VAPOR | C | B | 036 |
| 37 |
| 31 | 3/8” |
| |
|
|
|
|
|
|
|
| |||
| 042 |
| 37 |
| 31 | 7/8” | ||||
LIQUID |
|
|
|
| ||||||
|
| 048 |
| 37 |
| 31 |
|
| ||
|
|
| 060 |
| 37 |
| 31 |
| 7/8” * |
* Expander fitting required for
2 | Unitary Products Group |