York YMA024 warranty 036-21570-002Rev. D, Unitary Products Group, Footnotes, Procedures

Models: YMA024

1 24
Download 24 pages 57.12 Kb
Page 3
Image 3

036-21570-002 Rev. D (0605)

Additional R-22 Charge / TXV Size for Various Matched Systems

Outdoor Unit

 

YMA02411

YMA03011

YMA03611

YMA04211

YMA04811

YMA06011

Unit Orifice (s)

 

63

69

78

87

-

96

Approved System Thermal Expansion Valve1,2

1TV0701

1TV0701

1TV0702

1TV0702

1TV0703

-

Factory R-22 Charge, lbs-oz

 

7 - 2

7 - 12

8 - 6

8 - 12

9 - 1

14 - 2

 

 

 

 

 

 

 

 

Indoor Coil3

Coil Orifice 4

 

 

Orifice - Additional Charge, Oz

 

 

G2FD030(S,H)17

65

63/(701) + 2

69/(701) + 0

 

-

-

-

G2FD035(S,H)14

65

63/(701) + 2

69/(701) + 0

 

-

-

-

G2FD036(S,H)17

65

-

-

78/(702) + 3

-

-

-

G2FD036(S,H)21

75

-

-

78/(702) + 5

-

-

-

G2FD048(S,H)21,24

84

-

-

-

87/(702) + 3

-

-

G2FD060(S,H)24

90

-

-

-

-

703 + 6

96 + 6

G2FD061H24

90

-

-

-

-

703 + 12

96 + 12

G1HA036H14

75

63/(701) + 8

69/(701) + 6

78/(702) + 5

-

-

-

G1HA036H17

78

63/(701) +12

69/(701) + 9

78/(702) + 8

-

-

-

G1HA048H21

84

-

-

-

87/(702) + 4

-

-

G1HA060H24

90

-

-

-

-

703 + 6

96 + 6

G1HD036

69

63/(701) + 8

69/(701) + 5

78/(702) + 5

-

-

-

G1HD048

81

-

-

-

87/(702) + 0

-

-

G1HD060

93

-

-

-

-

703 + 0

96 + 0

G1NA036S17J

67

63/(701) + 4

69/(701) + 2

78/(702) + 1

-

-

-

G1NA036S21C

67

63/(701) + 4

69/(701) + 2

78/(702) + 1

-

-

-

G1NA060S24T

87

-

-

-

87/(702) + 8

703 + 1

96 + 0

G1FA/G1UA036S14

73

63/(701) + 4

69/(701) + 2

78/(702) + 1

-

-

-

G1FA/G1UA036S17,21

73

63/(701) + 2

69/(701) + 0

78/(702) + 0

-

-

-

G1FA/G1UA048S21

84

-

-

-

87/(702) + 5

-

-

G1FA/G1UA060S21,24

90

-

-

-

-

703 + 6

96 + 6

F2RC/F2FC036

75

63/(701) + 2

69/(701) + 0

-

-

-

-

F2RP024

61

63/(701) + 0

-

-

-

-

-

F2RP/F2FP030

65

63/(701) + 2

69/(701) + 0

-

-

-

-

F2RP/F2FP036

75

-

-

78/(702) + 5

-

-

-

F2FP040

63

-

-

78/(702) + 8

-

-

-

F2RP/F2FP042

78

-

-

78/(702) + 8

-

-

-

F2FP045

78

-

-

-

-

703 + 6

-

F2FP048

84

-

-

-

87/(702) + 7

-

-

F2FP060

90

-

-

-

-

703 + 6

96 + 6

F2FV060

90

-

-

-

-

703 + 6

96 + 6

Indoor Coil with factory

Factory installed

 

 

Additional Charge, Oz.

 

 

installed TXV2,4

coil orifice3

 

 

 

 

 

 

 

 

 

 

G2FD030(S,H)17T

-

2

0

 

-

-

-

G2FD035(S,H)14T

-

2

0

 

-

-

-

G2FD036(S,H)17T

-

-

-

3

-

-

-

G2FD036(S,H)21T

-

-

-

5

-

-

-

G2FD060(S,H)24T

-

-

-

-

-

6

-

G1HA036H14T

-

-

-

5

-

-

-

G1HA036H17T

-

-

-

8

-

-

-

G1HA060H24T

-

-

-

-

-

6

-

G1FA/G1UA036S14T

-

-

-

1

-

-

-

G1FA/G1UA036S17,21T

-

-

-

0

-

-

-

G1FA/G1UA060S21,24T

-

-

-

-

-

6

-

F3RP024

-

0

-

-

-

-

-

F3RP030

-

2

0

-

-

-

-

F3RP036

-

-

-

5

-

-

-

F3RP042

-

-

-

8

-

-

-

F3FP040

-

-

-

8

-

-

-

F3FP060

-

-

-

-

-

6

-

F3FV060

-

-

-

-

-

6

-

FOOTNOTES:

 

 

 

 

 

 

 

1Only the TXV kits listed above are approved for use in these systems. The charge adder is the same as that listed for the orifice.

2Models with reciprocating compressors require start kits when matched to TXV indoor coils.

3Systems matched with furnaces or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.

4These orifices or TXVs are factory mounted in the flow device of each indoor coil (701, 702, 703 indicates 1TV07…series). A “T” suffix indicates a coil or air handler with a factory mounted TXV.

PROCEDURES:

1.Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter- connecting line tubing.

2.Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.

3.Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified on the previous page.

4.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line set.

Unitary Products Group

3

Page 3
Image 3
York YMA024 warranty 036-21570-002Rev. D, Unitary Products Group, Footnotes, Procedures