Temperature Range: Cool 66-90F (19-32C), Heat 60-80F (16-27C)

Temporary Temperature Override feature: 45-minute default setting, adjustable in 5-minute increments

Humidity control: Dehumidification only, Range 50-75%, Span is 5-10%. Requires special HVAC system with dehumidification circuit

Pre-purge capability: Span 0-7200 seconds, default is 0

CO2 control: Range 500-2000 ppm, Span 50-500 ppm

Can optionally display space humidity, CO2, and outdoor temperature Dedicated ventilation output

Outdoor sensor option, Bard PN 8403-061, can be used to:

oLimit minimum outdoor temperature for cooling operation

oLimit minimum outdoor temperature for heat pump operation (compressor lockout) o Inhibit electric heat operation for heat pumps above selected outdoor temperature

Remote indoor sensor option, Bard PN 8403-062, can be used to with following options:

oUse remote indoor sensor only

oAverage remote indoor sensor and on-board sensor o Highest of connected sensors

o Lowest of connected sensors

Vertical mount, mounts to standard 2x4 handy-box installed vertically or horizontally

Off-white

Controller Connections: Terminal legend

 

 

 

 

Terminal

Function

 

Type

Form

 

D

 

Dehumidification

Output

24VAC

SPST RELAY

 

SC

 

24VAC to Relay Outputs D, A, W2

Power

 

 

 

A

 

Ventilation Call

Output

24VAC

SPST RELAY

 

W2

 

2nd Stage Heating

Output

24VAC

SPST RELAY

 

W1/E

 

1st Stage Heating/Emer. Heat

Output

24VAC

SPST RELAY

 

SC

 

24VAC to Relay Outputs W1/E, Y2, Y1

Power

 

 

 

Y2

 

2nd Stage Compressor

Output

24VAC

SPST RELAY

 

Y1

 

1st Stage Compressor

Output

24VAC

SPST RELAY

 

Y0

 

Economizer

Output

24VAC

SPST RELAY

 

SC

 

24VAC to Relay Outputs YO, O/B, G

Power

 

 

 

O/B

 

Reversing Valve

Output

24VAC

SPST RELAY

 

G

 

Indoor Blower

Output

24VAC

SPST RELAY

 

IN9

 

Not Used

 

 

 

 

ROS

 

Remote Occupancy Sensor

Input

Dry Contact (Input to GND)

 

GND

 

 

 

 

 

 

REM

 

Remote Temperature Sensor

Input

10K Type II Thermistor

 

+B

 

Communications

 

 

 

 

-A

 

Communications

 

 

 

 

OAT

 

Outdoor Air Temperature Sensor

Input

10K Type II Thermistor

 

LAS

 

Leaving Air Temperature Sensor

Input

10K Type II Thermistor

 

GND

 

Control Ground

 

 

 

 

L

 

Lockout Alarm

Input

Dry Contact (Input to GND)

 

Com

 

24VAC Common

Power

 

 

 

24V

 

24VAC Hot

Power

 

 

 

 

 

 

 

 

 

Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com

Due to our continuous product improvement policy, all specifications subject to change without notice.

Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.

Form No.

F1943

May, 2012

Supersedes: F1943-212

Page

2 of 2

Page 2
Image 2
Zyliss CS9B-THO, CS9BE-THO manual Controller Connections Terminal legend Function Type Form